Plan Review Details - Permit 18080595
Plan Review Stops For Permit 18080595
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-08-31 Cont ID  
Sent By rmcdouga Date 2018-08-24 Time 15:00 Rev Time 0.00
Received By rmcdouga Date 2018-08-24 Time 15:00 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-08-27 Cont ID  
Sent By jleahy Date 2018-08-27 Time 12:59 Rev Time 0.00
Received By jleahy Date 2018-08-27 Time 12:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-08-30 Cont ID  
Sent By lcrespo Date 2018-08-30 Time 17:37 Rev Time 0.00
Received By lcrespo Date 2018-08-30 Time 17:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-13 Cont ID  
Sent By lcrespo Date 2018-09-13 Time 17:20 Rev Time 0.00
Received By lcrespo Date 2018-09-11 Time 15:16 Sent To  
Notes
2018-09-12 15:16:16RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-31 Cont ID  
Sent By rmcdouga Date 2018-08-31 Time 15:00 Rev Time 0.00
Received By rmcdouga Date 2018-08-13 Time 14:47 Sent To  
Notes
2018-08-14 14:47:30ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-09-13 Cont ID  
Sent By lcrespo Date 2018-09-13 Time 17:14 Rev Time 0.00
Received By lcrespo Date 2018-09-13 Time 17:14 Sent To  
Notes
2018-09-13 17:15:3409/13/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-30 Cont ID  
Sent By lcrespo Date 2018-08-30 Time 17:37 Rev Time 0.00
Received By lcrespo Date 2018-08-30 Time 17:37 Sent To  
Notes
2018-08-30 17:38:3908/30/2018 1ST PLUMBING/POOL REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS
 SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN AND THE PUMP. WPB AMENDMENTS TO FBC SEC. 107.2.1.
 3. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST
 PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A
 LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES
 PRIOR TO FINAL INSPECTION. A DUAL CHECK VALVE MAY BE
 USED IF NO POOL FILL IS INSTALLED AT THE METER AND
 INSTALLED BY UTILITIES WHICH DOES NOT REQUIRE A PERMIT
 SO PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240
 FOR FURTHER DIRECTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-08-22 Cont ID  
Sent By mcruz Date 2018-08-22 Time 14:05 Rev Time 0.00
Received By mcruz Date 2018-08-22 Time 14:02 Sent To  
Notes
***NONE***