Plan Review Details - Permit 18080553
Plan Review Stops For Permit 18080553
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-18 Cont ID  
Sent By rmcdouga Date 2018-10-18 Time 15:54 Rev Time 0.00
Received By rmcdouga Date 2018-10-18 Time 15:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-25 Cont ID  
Sent By rmcdouga Date 2018-09-25 Time 15:48 Rev Time 0.00
Received By rmcdouga Date 2018-09-25 Time 15:48 Sent To I
Notes
2018-09-25 16:40:46PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE STORM PANELS ARE NOT CODE COMPLIANT BASED ON THE
 DOCUMENTS THAT WERE SUBMITTED. FBC-R 301.2.1.2
  
 1) FROM THE TABLE FOR WOOD ON SHEET 10 OF THE PRODUCT
 APPROVAL, THE MAXIMUM PANEL LENGTH 6'-0" (72") FOR A
 DESIGN PRESSURE OF MORE THAN -45.8 PSF. YOUR PANEL
 SPANS ARE 90-1/2" AND 106-1/2" PER THE INSTALLATION
 SCHEDULE.
  
 2) THE TABLES ON SHEET 7 FOR CONCRETE AND MASONRY GO UP
 TO A MAXIMUM SPAN OF 7'-4" (88") FOR DESIGN PRESSURES
 OF MORE THAN -45.8 PSF. YOUR PANEL SPANS ARE 90-1/2"
 AND 106-1/2" PER THE INSTALLATION SCHEDULE.
  
 3) THE EDGE DISTANCE FOR CONCRETE AND MASONRY
 INSTALLATIONS IS REQUIRED TO BE 3-1/2" TO USE THE
 ANCHOR SPACING IN THE TABLES ON SHEET 7.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By rmcdouga Date 2018-08-27 Time 07:10 Rev Time 0.00
Received By rmcdouga Date 2018-08-27 Time 06:51 Sent To I
Notes
2018-08-27 07:10:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE DESIGNER OF RECORD FOR THIS PROJECT IS TO REVIEW
 AND APPROVE THE PRODUCT APPROVALS IN WRITING. FBC
 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001
 PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN
 INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING
 THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-18 Cont ID  
Sent By rmcdouga Date 2018-10-18 Time 15:54 Rev Time 0.00
Received By rmcdouga Date 2018-10-18 Time 15:54 Sent To  
Notes
2018-10-18 15:55:47GAVE TO S PALMER TO PROCESS OUT. RM

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-25 Cont ID  
Sent By rmcdouga Date 2018-09-25 Time 16:41 Rev Time 0.00
Received By rmcdouga Date 2018-09-21 Time 14:20 Sent To  
Notes
2018-09-24 14:20:23RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-27 Cont ID  
Sent By rmcdouga Date 2018-08-27 Time 07:10 Rev Time 0.00
Received By rmcdouga Date 2018-08-10 Time 12:50 Sent To  
Notes
2018-08-14 12:50:52ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-08-22 Cont ID  
Sent By mcruz Date 2018-08-22 Time 11:37 Rev Time 0.00
Received By mcruz Date 2018-08-22 Time 11:29 Sent To B
Notes
***NONE***