Plan Review Stops For Permit 18080231 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-09-05 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-09-05 |
Time |
09:24 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-09-05 |
Time |
08:58 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-08-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-08-24 |
Time |
16:09 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-08-24 |
Time |
16:09 |
Sent To |
I |
|
Notes |
2018-08-24 16:29:28 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR PAD ENGINEERING IS NOT VALID WITHOUT | | THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE. SUBMIT | | ONE SET OF DRAWINGS FOR PUBLIC RECORD WITH A VALID SEAL | | AND SIGNATURE. FAC 61G15-23.003 PROCEDURES FOR | | PHYSICALLY SIGNING AND SEALING PLANS, SPECIFICATIONS, | | REPORTS OR OTHER DOCUMENTS. ENGINEERING PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH MUST | | BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE | | PROVISIONS OF SECTION 471.025, F.S., AND RULE | | 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED | | AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL | | ENGINEER IN RESPONSIBLE CHARGE. | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE | | USED. | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-08-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-08-20 |
Time |
07:35 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-08-20 |
Time |
07:35 |
Sent To |
I |
|
Notes |
2018-08-20 07:40:16 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR PAD ENGINEERING IS NOT VALID WITHOUT | | THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE. SUBMIT | | ONE SET OF DRAWINGS FOR PUBLIC RECORD WITH A VALID SEAL | | AND SIGNATURE. FAC 61G15-23.003 PROCEDURES FOR | | PHYSICALLY SIGNING AND SEALING PLANS, SPECIFICATIONS, | | REPORTS OR OTHER DOCUMENTS. ENGINEERING PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH MUST | | BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE | | PROVISIONS OF SECTION 471.025, F.S., AND RULE | | 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED | | AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL | | ENGINEER IN RESPONSIBLE CHARGE. | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE | | USED. | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2018-08-28 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-08-28 |
Time |
06:29 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-08-28 |
Time |
06:21 |
Sent To |
|
|
Notes |
2018-08-28 06:28:35 | PASSED: FILED BACK IN SMALL DENIED-BIN A |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2018-08-23 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-08-23 |
Time |
07:11 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-08-23 |
Time |
06:51 |
Sent To |
B |
|
Notes |
2018-08-23 07:11:17 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL | | LOADS AND DENOTING WHAT LOADS ARE TO BE SHED/MANAGED. | | ALL THAT WAS PROVIDED WAS A SIZING REPORT FOR | | RECOMMENDED SIZE OF GENERATOR TO BE INSTALLED. NEC 220; | | FBC RE E3602.2 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-08-16 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-08-16 |
Time |
06:29 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-08-16 |
Time |
06:28 |
Sent To |
|
|
Notes |
2018-08-16 06:29:04 | PUT BACK IN GENERATOR BIN | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND | | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE | | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | (PRINT AND SIGN, LICENSE #, AND ADDRESS) | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2018-08-10 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2018-08-10 |
Time |
17:47 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2018-08-10 |
Time |
17:47 |
Sent To |
|
|
Notes |
2018-08-10 17:50:00 | 08/10/18 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-09-05 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-09-05 |
Time |
09:24 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-08-30 |
Time |
12:49 |
Sent To |
|
|
Notes |
2018-08-31 12:49:20 | RESUB ROUTED TO RMCDOUGAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-08-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-08-24 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-08-20 |
Time |
15:32 |
Sent To |
|
|
Notes |
2018-08-21 15:33:14 | RESUB ROUTED TO FGIAQUINTO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-08-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-08-20 |
Time |
07:35 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-08-06 |
Time |
13:32 |
Sent To |
|
|
Notes |
2018-08-07 13:32:32 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-08-08 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-08-08 |
Time |
17:04 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-08-08 |
Time |
17:02 |
Sent To |
|
|
Notes |
|
|