Plan Review Details - Permit 18080085
Plan Review Stops For Permit 18080085
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-08-11 Cont ID  
Sent By pvalenti Date 2018-08-11 Time 16:29 Rev Time  
Received By pvalenti Date   Time   Sent To E
Notes
2018-08-11 16:32:45PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED PV
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-14 Cont ID  
Sent By fgiaquin Date 2018-08-14 Time 07:00 Rev Time 0.00
Received By fgiaquin Date 2018-08-14 Time 06:54 Sent To I
Notes
2018-08-14 07:00:22ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. AS OF JAN 1, 2018 WE
 ARE ON THE 2014 NEC.
  
 3. NOTE STATING "PRIMARY ELECTRIC SUPPLIED BY OTHERS IS
 NOT ACCEPTABLE". WHO WILL BE INSTALLING THE NEW
 DISCONNECT AND TIMECLOCK? PLEASE SEE NOTES BELOW.
  
  
 INFORMATIONAL NOTE: NEW DISCONNECT REQUIRED BY NEC 2014
 600.6A1 AND ASTRONOMICAL TIMECLOCK REQUIRED BY FBC
 EC405.2.4 CANNOT BE INSTALLED BY AN ES CONTRACTOR. A
 LICENSED ELECTRICIAN WILL BE NEEDED AND NO
 ELECTRICAL-SUB PERMIT FOR THIS SIGN INSTALLATION WILL
 BE ISSUED TO AN ES LICENSE HOLDER. PLEASE SEE SCOPE OF
 WORK FOR ES LICENSE PROVIDED BELOW:
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-14 Cont ID  
Sent By fgiaquin Date 2018-08-14 Time 07:00 Rev Time 0.00
Received By fgiaquin Date 2018-08-02 Time 10:52 Sent To  
Notes
2018-08-03 10:52:40ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-08 Cont ID  
Sent By elevesqu Date 2018-08-08 Time 11:20 Rev Time 0.00
Received By elevesqu Date 2018-08-08 Time 11:14 Sent To B
Notes
2018-08-08 11:20:49PLEASE PROVIDE DIMENSIONS OF OFFICE BAY STOREFRONT
 WIDTH OF EAST ELEVATION. PLEASE PROVIDE FLOOR PLAN
 SHOWING LOCATION OF SELF STORAGE OFFICE. PERMITTED SIZE
 OF SIGN IS 60% OF STOREFRONT (OFFICE) WIDTH PER EACH
 FACADE.
  
 PLEASE PUT AN "X" THROUGH OR REMOVE THE OTHER PROPOSED
 SIGN FROM THIS PERMIT AS IT IS BEING REVIEWED THROUGH
 SEPARATE PERMIT.
  
 SIGNS, INCLUDING LOGO CANNOT EXCEED 36" IN HEIGHT.
 PLEASE REVISE ACCORDINGLY.
  
 EMAIL LIZ LEVESQUE, URBAN DESIGN PLANNER AT
 [email protected] WITH ANY QUESTIONS 561 822 1426
  
  
  