Plan Review Details - Permit 18071472
Plan Review Stops For Permit 18071472
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2018-08-30 Cont ID  
Sent By shill Date 2018-08-30 Time 07:34 Rev Time 0.00
Received By shill Date 2018-08-30 Time 07:34 Sent To  
Notes
2018-08-30 07:35:20NEW ADDRESS OF 701 S SAPODILLA AVE ASSIGNED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-31 Cont ID  
Sent By shill Date 2018-08-31 Time 11:57 Rev Time 0.00
Received By shill Date 2018-08-31 Time 11:57 Sent To  
Notes
2018-08-31 11:58:01****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 A. SHEETS GG102 AND GA102 WHICH WERE REVIEWED BY EMAIL
 ARE TO BE SUBMITTED AS A REVISION WITHIN 3 BUSINESS
 DAYS AFTER PERMIT ISSUANCE (BY 9/6/18).
  
 B. THE PRIVATE PROVIDER'S STAMP IS MISSING FROM MANY
 PAGES AND THE VERSION CALLED OUT ON THE PLAN COMPLIANCE
 AFFIDAVIT IS NOT CONSISTENT WITH THE VERSION REVIEWED.
 SUBMIT ONE SET STAMPED BY THE PRIVATE PROVIDER WITH AN
 UPDATED PLAN REVIEW COMPLIANCE AFFIDAVIT. IT IS
 RECOMMENDED THAT YOU HAVE THEM STAMP A COPY OF THE
 ISSUED PERMIT SET.
  
 C. THIS PERMIT IS ISSUED AT APPLICANT'S RISK PER FBC
 105.13:
  
 PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF THE
 APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE. ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 D. ADVISORY FOR BUILDING PERMIT:
 SHORING/RESHORE ENGINEERING IS TO BE SUBMITTED,
 REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 FAILURE TO DO SO ***WILL*** RESULT IN A STOP WORK ORDER
 IF CONTRACTOR PROCEEDS WITHOUT SUBMITTAL OF
 SHORING/RESHORE ENGINEERING (#7, PAGE 4,
 THRESHOLD/SPECIAL INSPECTOR OBLIGATIONS IN THE
 AGREEMENT SIGNED BY ALL PARTIES).
  
 E. ADVISORY FOR BUILDING PERMIT:
 AN ENGINEERED CONSTRUCTION GUARD RAIL DETAIL IS
 REQUIRED PRIOR TO INSTALLATION. THIS IS TO BE SUBMITTED
 WITH THE SHORING/RESHORE ENGINEERING, BUT SUBJECT TO
 FIELD INSPECTOR'S DISCRETION CAN BE PROVIDED IN THE
 FIELD.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-28 Cont ID  
Sent By shill Date 2018-08-28 Time 18:01 Rev Time 0.00
Received By shill Date 2018-08-28 Time 17:45 Sent To  
Notes
2018-08-28 18:01:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1-2 OK
  
 3. SURVEY/SITE PLAN SHOWING COMPLIANCE WITH FBC B
 TABLES 705.8, 602.
  
 2ND REVIEW, GG102 WAS PROVIDED AND SHOWS 15'3" BETWEEN
 DREYFOOS BASEMENT AND PROPOSED PARKING GARAGE. THERE
 ARE ALSO NOTES REFERRING TO FOOTNOTE C AND G.
  
 ASSUMED PROPERTY LINE BETWEEN THE TWO BUILDINGS IS NOT
 CLEAR. PLEASE SEE FBC B CHAPTER 2, DEFINITION OF FIRE
 SEPARATION DISTANCE, ITEM 3. ASSUMED PROPERTY LINE
 BETWEEN THE EXISTING BUILDING AND PROPOSED BUILDING IS
 TO BE INDICATED. REVISE PLAN TO SHOW THE FOLLOWING:
  
 LOCATION OF ASSUMED PROPERTY LINE, DISTANCE TO DREYFOOS
 BASEMENT, DISTANCE TO PROPOSED GARAGE
 COMPLIANCE WITH FBC B TABLES 705.8, 602 FOR THE PARKING
 GARAGE TO THE ASSUMED PROPERTY LINE
 COMPLIANCE WITH FBC B TABLES 705.8, 602 FOR THE
 DREYFOOS BASEMENT
  
 ARCHITECT MAY SEND THIS PAGE TO ME VIA EMAIL FOR
 PRELIMINARY REVIEW.
  
 4-6. OK
  
 THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISOS
  
 A. PERMIT IS ISSUED AT RISK
 B. SHORING/RESHORE ENGINEERING IS TO BE SUBMITTED,
 REVIEWED AND ISSUED PRIOR TO INSTALLATION. FAILURE TO
 DO SO ***WILL*** RESULT IN A STOP WORK ORDER IF
 CONTRACTOR PROCEEDS WITHOUT SUBMITTAL OF
 SHORING/RESHORE ENGINEERING (#7, PAGE 4,
 THRESHOLD/SPECIAL INSPECTOR OBLIGATIONS IN THE
 AGREEMENT SIGNED BY ALL PARTIES).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-13 Cont ID  
Sent By shill Date 2018-08-13 Time 16:54 Rev Time 0.00
Received By shill Date 2018-08-13 Time 16:38 Sent To  
Notes
2018-08-13 16:55:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. FOUNDATION AND STRUCTURE PERMITS REQUIRE THE
 FOLLOWING:
  
 ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING
 SURVEY DRAWING
 STORM WATER POLLUTION PREVENTION PLAN
 SITE PLAN
  
 3. SURVEY/SITE PLAN SHOWING COMPLIANCE WITH FBC B
 TABLES 705.8, 602.
  
 4. SOME ARCHITECTURAL PAGES WERE SIGNED AND SEALED BY
 PAUL TWITTY, OTHERS BY WILLIAM HANSER. THIS IS
 ACCEPTABLE BUT CLARIFY WHO IS THE ARCHITECT OF RECORD
 FOR THE PROJECT.
  
 5. ADVISORY ONLY; CONTRACTOR IS TO TAKE NOTE OF THE
 REQUIREMENT THAT SHORING/RESHORE ENGINEERING IS TO BE
 SUBMITTED, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 FAILURE TO DO SO ***WILL*** RESULT IN A STOP WORK ORDER
 IF CONTRACTOR PROCEEDS WITHOUT SUBMITTAL OF
 SHORING/RESHORE ENGINEERING.
  
 THIS IS ITEM #7, PAGE 4, THRESHOLD/SPECIAL INSPECTOR
 OBLIGATIONS IN THE AGREEMENT SIGNED BY ALL PARTIES.
  
 6. FOR FUTURE REFERENCE, THE FOLLOWING IS INFORMATION
 REQUIRED FOR FOUNDATION PERMITS:
  
 PERMIT APPLICATION WHICH STATES SCOPE (FOR FOUNDATION
 PERMIT, TYPICALLY FOOTINGS OR FOOTINGS AND SLAB)
 GEOTECHNICAL REPORT
 SURVEY DRAWING
 STORM WATER POLLUTION PREVENTION PLAN
 SITE PLAN
 1ST FLOOR ARCHITECTURAL PLAN
 ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING
 FOUNDATION PLAN
 FOUNDATION DETAILS AND CROSS SECTIONS
 STRUCTURAL ENGINEER'S GENERAL NOTES
 UNDERGROUND PLUMBING PLAN (IF APPLICABLE)
 ELECTRICAL PLAN SHOWING ANY UNDERGROUND CONDUIT (IF
 APPLICABLE)
 ELECTRICAL GROUNDING TO STEEL DETAIL, IF APPLICABLE (OR
 EXPLAIN WHY THIS IS NOT APPLICABLE FOR THIS PROJECT).
 IF REQUIRED, A DETAIL IS REQUIRED AS A REVIEW, PERMIT,
 AND INSPECTION ARE REQUIRED PRIOR TO CONCRETE POUR
 PLAN SHOWING UNDERGROUND FIRE LINE
 THRESHOLD INSPECTION PLAN OR RESIDENT INSPECTION PLAN
 (AS APPLICABLE)
 SI OR RESIDENT INSPECTOR AGREEMENT (AS APPLICABLE)
 THRESHOLD STATEMENT ON PLAN (IF APPLICABLE)
 THREE SETS OF PLANS FOR RESIDENT INSPECTOR OR THRESHOLD
 PROJECT
  
 ADDITIONAL INFORMATION MAY BE REQUIRED ON A CASE BY
 CASE BASIS.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-29 Cont ID  
Sent By jpearson Date 2018-08-29 Time 09:39 Rev Time 0.00
Received By jpearson Date 2018-08-29 Time 09:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-14 Cont ID  
Sent By jpearson Date 2018-08-14 Time 10:02 Rev Time 0.00
Received By jpearson Date 2018-08-14 Time 10:02 Sent To  
Notes
2018-08-14 10:02:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 2. PROVIDE LOAD CALCULATION FOR SERVICE TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-08-15 Cont ID  
Sent By mgonzale Date 2018-08-28 Time 11:16 Rev Time 1.00
Received By mgonzale Date 2018-08-28 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-08-13 Cont ID  
Sent By shill Date 2018-08-13 Time 16:55 Rev Time 0.00
Received By shill Date 2018-08-13 Time 16:55 Sent To  
Notes
2018-08-13 16:55:55CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-30 Cont ID  
Sent By pleduc Date 2018-08-30 Time   Rev Time 0.00
Received By pleduc Date 2018-08-30 Time 09:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-09 Cont ID  
Sent By pleduc Date 2018-08-09 Time   Rev Time 0.00
Received By pleduc Date 2018-08-08 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-31 Cont ID  
Sent By shill Date 2018-08-31 Time 11:58 Rev Time 0.00
Received By shill Date 2018-08-23 Time 15:30 Sent To  
Notes
2018-08-24 15:30:51C04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-21 Cont ID  
Sent By gjohnson Date 2018-08-21 Time 15:32 Rev Time 0.00
Received By gjohnson Date 2018-07-31 Time 15:07 Sent To  
Notes
2018-08-01 15:08:00C08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2018-08-28 Cont ID  
Sent By shill Date 2018-08-28 Time 17:26 Rev Time 0.00
Received By shill Date 2018-08-28 Time 17:26 Sent To  
Notes
2018-08-28 17:27:15PLAN STAMPED, $0 DUE
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-13 Cont ID  
Sent By shill Date 2018-08-13 Time 16:38 Rev Time 0.00
Received By shill Date 2018-08-13 Time 16:38 Sent To  
Notes
2018-08-13 16:38:43PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-29 Cont ID  
Sent By gjohnson Date 2018-08-29 Time 09:07 Rev Time 0.00
Received By gjohnson Date 2018-08-29 Time 09:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-21 Cont ID  
Sent By gjohnson Date 2018-08-21 Time 15:00 Rev Time 0.00
Received By gjohnson Date 2018-08-21 Time 14:59 Sent To  
Notes
2018-08-21 15:32:051ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE A FLOOR PLAN SHOWING ALL UNDERGROUND
 PLUMBING AND A STORM DRAIN ISOMETRIC DRAWING WITH
 SIZING CALCULATIONS. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2018-08-13 Cont ID  
Sent By shill Date 2018-08-13 Time 17:24 Rev Time 0.00
Received By shill Date 2018-08-13 Time 17:24 Sent To  
Notes
2018-08-13 17:25:20MEP STRUCTURAL ENGINEERING AND INSPECTIONS
 OTTO J. LETZELTER, PE
 JACK BOTHE, BN5957
  
 THRESHOLD INSPECTION PLAN ON PAGE GS004
 THRESHOLD STATEMENT ON ALL PAGES
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-08-31 Cont ID  
Sent By eschneid Date 2018-08-31 Time 16:51 Rev Time 0.00
Received By eschneid Date 2018-08-31 Time 16:51 Sent To  
Notes
2018-08-31 16:53:55PASSED W/PROVISO
  
 SUBMIT A PLAN REVISION TO THIS PERMIT WITH THE FULL
 SIZED SIGNED AND SEALED SHEET GA 102 SHOWING THE 22
 FOOT WIDTH.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-08-31 Cont ID  
Sent By eschneid Date 2018-08-31 Time 11:27 Rev Time 0.25
Received By eschneid Date 2018-08-31 Time 11:27 Sent To  
Notes
2018-08-31 11:50:18FAILED
  
 1) REPEAT COMMENT: THE PLANS APPROVED BY THE CITY
 COMMISSION AS PART OF RESOLUTION NO. 68-18 WERE FOR A
 22 FOOT DRIVEWAY OPENING ON IRIS STREET. THE SUBMITTED
 PLANS (SHEET GA102) SHOW A 24 FOOT OPENING. SHEET GA102
 MUST BE CORRECTED TO SHOW THE CITY COMMISSION APPROVED
 22 FOOT WIDE DRIVEWAY OPENING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-20 Cont ID  
Sent By eschneid Date 2018-08-20 Time 14:36 Rev Time 0.50
Received By eschneid Date 2018-08-17 Time 16:53 Sent To  
Notes
2018-08-20 14:57:38FAILED
  
 1) THE PLANS APPROVED BY THE CITY COMMISSION AS PART OF
 RESOLUTION NO. 68-18 WERE FOR A 22 FOOT DRIVEWAY
 OPENING ON IRIS STREET. THE SUBMITTED PLANS SHOW A 24
 FOOT OPENING. THE PLANS MUST BE CORRECTED TO SHOW THE
 CITY COMMISSION APPROVED 22 FOOT WIDE DRIVEWAY OPENING.
  
 2) ONE OF THE SPACES ON THE NORTH WALL OF THE GRADE
 LEVEL PLAN APPEARS TO HAVE A COLUMN ENCROACHMENT AND
 WOULD NEED TO SHOW THAT IT CAN BE A COMPACT SPACE.
  
 3) PROVIDE A SURVEY OR SITE PLAN THAT SHOWS THE
 DIMENSIONS OF THE PROPOSED GARAGE TO THE CURB LINES,
 WHICH IS THE SETBACK MEASURE POINT FOR THE GARAGE AS
 APPROVED BY THE CITY COMMISSION IN RESOLUTION NO.
 68-18.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]