Plan Review Stops For Permit 18071458 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2018-10-22 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-10-22 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-10-22 |
Time |
09:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-08-13 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-08-13 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-08-13 |
Time |
11:08 |
Sent To |
|
|
Notes |
2018-08-13 11:08:49 | ****CORRECTIONS**** | | W.P.B. PERMIT: 18071458 | | REVIEWED: AUGUST 13, 2018 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC EB = FBC EXISTING BUILDING | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | SHEET A-2 IN DESIGN PARAMETERS, THE CODE FOR THIS | | PROJECT SHOULD BE FBC 2017 6TH EDITION. | | | | SHEET A-2 REFERS TO (SEE ENERGY CALCS). ARE THESE TO BE | | PROVIDED, OR IS THE REPAIR WORK FOLLOWING PRESCRIPTIVE | | METHOD? | | | | PLEASE PROVIDE MORE DETAIL OF THE REPAIR WORK TO BE | | DONE. THE PLANS DON?T SHOW ENOUGH ABOUT REPAIRS TO BE | | COMPLETED TO MATCH THE $60,000.00 VALUE OF PROJECT. DID | | THE FIRE BURN THROUGH THE ROOF? | | | | NOTE: | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | EACH COMMENT IS BEING ADDRESSED. | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | OF MATERIALS REQUESTED. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-09-26 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-09-26 |
Time |
13:51 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-09-26 |
Time |
13:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-08-06 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-08-06 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-08-06 |
Time |
13:17 |
Sent To |
M |
|
Notes |
2018-08-06 13:25:13 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | MAIN DOES NOT SHOW SIZE IF IT IS 200A THEN WIRE TO | | PANEL NEEDS TO BE 2/0 | | | | ALL NEW OUTLETS NEED TO BE WIRED PER 201.12(A), 210.8, | | 210.52 | | | | ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH | | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT | | KITCHENS, LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS, | | LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, | | SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR | | SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION. | | NEC 210.12; FBC RE3902.16 | | | | E3902.9 LAUNDRY AREAS. 125-VOLT, SINGLE-PHASE, 15- AND | | 20-AMPERE RECEPTACLES INSTALLED IN LAUNDRY | | AREAS SHALL HAVE GROUND-FAULT CIRCUIT INTERRUPTER | | PROTECTION FOR PERSONNEL. [210.8(A)(9)] | | | | PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE. NEC | | 210.8; FBC RE3902.2 | | | | PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A NOTE | | WILL SUFFICE. NEC 406.12; FBC RE4002.14 | | | | E3901.2.2 WALL SPACE. | | AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE | | FOLLOWING: [210.52(A)(2)] | | | | 1. 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN | | WIDTH, INCLUDING SPACE MEASURED AROUND CORNERS, | | AND THAT IS UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS | | AND SIMILAR OPENINGS, FIREPLACES, AND FIXED CABINETS. | | 2. 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR | | WALLS, EXCLUDING SLIDING PANELS. | | 3. 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS | | RAILINGS AND FREESTANDING BAR-TYPE COUNTERS | | | | SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING | | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE | | INSTALLED | | SO THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR | | LINE OF ANY WALL SPACE IS MORE THAN 6 FEET FROM A | | RECEPTACLE | | OUTLET. PROVIDE CORRECTION. NEC 210.52; FBC RE3901.2.1 | | | | OUTLET SPACING DOES NOT MEET CODE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-01-24 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2019-01-24 |
Time |
08:49 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2019-01-04 |
Time |
13:21 |
Sent To |
|
|
Notes |
2019-01-07 13:21:40 | RESUB ROUTED TO HMOSER |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-10-22 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-10-22 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-09-17 |
Time |
14:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-08-13 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-08-13 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-07-31 |
Time |
15:13 |
Sent To |
|
|
Notes |
2018-08-06 10:11:46 | R30 | 2018-08-01 15:13:57 | LIBRARY |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2019-01-24 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2019-01-24 |
Time |
08:49 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2019-01-24 |
Time |
08:31 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2018-10-13 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2018-10-13 |
Time |
07:34 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2018-10-13 |
Time |
06:21 |
Sent To |
|
|
Notes |
2018-10-13 07:34:02 | PLAN DENIED | | EQUIPMENT SCHEDULE NOT COMPLETE NEED MODEL NUMBER OF | | EQUIPMENT | | BRAND NAME OF EQUIPMENT, SEER, SIZE AND HEATER SIZE. | | PLAN SHOWS | | SPLIT SYSTEM SCHEDULE SHOWS PACKAGE UNIT. REFER TO | | SECTION | | 107 FBC 2017 | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-08-10 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2018-08-10 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2018-08-10 |
Time |
12:52 |
Sent To |
B |
|
Notes |
2018-08-10 13:27:31 | PLAN DENIED | | 1) PROVIDE CFM ON ALL SUPPLY GRILS | | SECTION 107 FBC 2317 | | 2) PROVIDE DUCT SIZE ON ALL DUCT WORK SUPPLY AND | | RETURN. | | SECTION 107 FBC 2017 | | 3) REFER TO SECTION M1602.3 BALANCED RETURN AIR. | | 2017 RESIDENTIAL CODE | | 4) MARK ON THE PLAN IF THE DUCTWORK IS NEW OR EXISTING | | SECTION 107 FBC 2017 | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2018-10-11 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2018-10-11 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2018-10-11 |
Time |
10:23 |
Sent To |
|
|
Notes |
2018-10-11 10:28:41 | 2ND REVIEW: | | PLUMBING COMMENTS: APPROVED | | PROVISO | | 1. RE: PLAN SHEET A1; PLUMBING SCOPE IS REDLINED AND | | STATES "REMOVE AND REPLACE ALL PLUMBING FIXTURES, | | PLUMBING LINES ABOVE THE FLOOR (SUPPLY, WASTE AND | | VENTS)" | | | | | | JERALD SMITH | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | EMAIL [email protected] | | PHONE 561-805-6715 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-08-06 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-08-06 |
Time |
12:27 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-08-06 |
Time |
12:25 |
Sent To |
|
|
Notes |
2018-08-06 12:27:34 | CLEARLY INDICATE ON BOTH SETS OF PLANS THE SCOPE OF THE | | PLUMBING WORK TO BE DONE. IDENTIFY ON THE PLANS THE | | AREAS OF THE STRUCTURE WHERE THE WORK WILL BE DONE. WPB | | AMEND. TO FBC SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|