Plan Review Details - Permit 18071458
Plan Review Stops For Permit 18071458
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-22 Cont ID  
Sent By dbattles Date 2018-10-22 Time 09:03 Rev Time 0.00
Received By dbattles Date 2018-10-22 Time 09:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-13 Cont ID  
Sent By dbattles Date 2018-08-13 Time 11:08 Rev Time 0.00
Received By dbattles Date 2018-08-13 Time 11:08 Sent To  
Notes
2018-08-13 11:08:49****CORRECTIONS****
 W.P.B. PERMIT: 18071458
 REVIEWED: AUGUST 13, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SHEET A-2 IN DESIGN PARAMETERS, THE CODE FOR THIS
 PROJECT SHOULD BE FBC 2017 6TH EDITION.
  
 SHEET A-2 REFERS TO (SEE ENERGY CALCS). ARE THESE TO BE
 PROVIDED, OR IS THE REPAIR WORK FOLLOWING PRESCRIPTIVE
 METHOD?
  
 PLEASE PROVIDE MORE DETAIL OF THE REPAIR WORK TO BE
 DONE. THE PLANS DON?T SHOW ENOUGH ABOUT REPAIRS TO BE
 COMPLETED TO MATCH THE $60,000.00 VALUE OF PROJECT. DID
 THE FIRE BURN THROUGH THE ROOF?
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-26 Cont ID  
Sent By jleahy Date 2018-09-26 Time 13:51 Rev Time 0.00
Received By jleahy Date 2018-09-26 Time 13:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-06 Cont ID  
Sent By jleahy Date 2018-08-06 Time 13:17 Rev Time 0.00
Received By jleahy Date 2018-08-06 Time 13:17 Sent To M
Notes
2018-08-06 13:25:13FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 MAIN DOES NOT SHOW SIZE IF IT IS 200A THEN WIRE TO
 PANEL NEEDS TO BE 2/0
  
 ALL NEW OUTLETS NEED TO BE WIRED PER 201.12(A), 210.8,
 210.52
  
 ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT
 KITCHENS, LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR
 SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION.
 NEC 210.12; FBC RE3902.16
  
 E3902.9 LAUNDRY AREAS. 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN LAUNDRY
 AREAS SHALL HAVE GROUND-FAULT CIRCUIT INTERRUPTER
 PROTECTION FOR PERSONNEL. [210.8(A)(9)]
  
 PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE. NEC
 210.8; FBC RE3902.2
  
 PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A NOTE
 WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
 E3901.2.2 WALL SPACE.
 AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE
 FOLLOWING: [210.52(A)(2)]
  
 1. 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN
 WIDTH, INCLUDING SPACE MEASURED AROUND CORNERS,
 AND THAT IS UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS
 AND SIMILAR OPENINGS, FIREPLACES, AND FIXED CABINETS.
 2. 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR
 WALLS, EXCLUDING SLIDING PANELS.
 3. 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS
 RAILINGS AND FREESTANDING BAR-TYPE COUNTERS
  
 SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED
 SO THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR
 LINE OF ANY WALL SPACE IS MORE THAN 6 FEET FROM A
 RECEPTACLE
 OUTLET. PROVIDE CORRECTION. NEC 210.52; FBC RE3901.2.1
  
 OUTLET SPACING DOES NOT MEET CODE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-24 Cont ID  
Sent By hmoser Date 2019-01-24 Time 08:49 Rev Time 0.00
Received By hmoser Date 2019-01-04 Time 13:21 Sent To  
Notes
2019-01-07 13:21:40RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-22 Cont ID  
Sent By dbattles Date 2018-10-22 Time 09:03 Rev Time 0.00
Received By dbattles Date 2018-09-17 Time 14:48 Sent To  
Notes
2018-09-18 14:48:52R16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-13 Cont ID  
Sent By dbattles Date 2018-08-13 Time 11:09 Rev Time 0.00
Received By dbattles Date 2018-07-31 Time 15:13 Sent To  
Notes
2018-08-06 10:11:46R30
2018-08-01 15:13:57LIBRARY

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-01-24 Cont ID  
Sent By hmoser Date 2019-01-24 Time 08:49 Rev Time 0.00
Received By hmoser Date 2019-01-24 Time 08:31 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-13 Cont ID  
Sent By hmoser Date 2018-10-13 Time 07:34 Rev Time 0.00
Received By hmoser Date 2018-10-13 Time 06:21 Sent To  
Notes
2018-10-13 07:34:02PLAN DENIED
 EQUIPMENT SCHEDULE NOT COMPLETE NEED MODEL NUMBER OF
 EQUIPMENT
 BRAND NAME OF EQUIPMENT, SEER, SIZE AND HEATER SIZE.
 PLAN SHOWS
 SPLIT SYSTEM SCHEDULE SHOWS PACKAGE UNIT. REFER TO
 SECTION
 107 FBC 2017
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-10 Cont ID  
Sent By hmoser Date 2018-08-10 Time 13:27 Rev Time 0.00
Received By hmoser Date 2018-08-10 Time 12:52 Sent To B
Notes
2018-08-10 13:27:31PLAN DENIED
 1) PROVIDE CFM ON ALL SUPPLY GRILS
 SECTION 107 FBC 2317
 2) PROVIDE DUCT SIZE ON ALL DUCT WORK SUPPLY AND
 RETURN.
 SECTION 107 FBC 2017
 3) REFER TO SECTION M1602.3 BALANCED RETURN AIR.
 2017 RESIDENTIAL CODE
 4) MARK ON THE PLAN IF THE DUCTWORK IS NEW OR EXISTING
 SECTION 107 FBC 2017
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-11 Cont ID  
Sent By jesmith Date 2018-10-11 Time 10:29 Rev Time 0.00
Received By jesmith Date 2018-10-11 Time 10:23 Sent To  
Notes
2018-10-11 10:28:412ND REVIEW:
 PLUMBING COMMENTS: APPROVED
 PROVISO
 1. RE: PLAN SHEET A1; PLUMBING SCOPE IS REDLINED AND
 STATES "REMOVE AND REPLACE ALL PLUMBING FIXTURES,
 PLUMBING LINES ABOVE THE FLOOR (SUPPLY, WASTE AND
 VENTS)"
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-06 Cont ID  
Sent By tklarge Date 2018-08-06 Time 12:27 Rev Time 0.00
Received By tklarge Date 2018-08-06 Time 12:25 Sent To  
Notes
2018-08-06 12:27:34CLEARLY INDICATE ON BOTH SETS OF PLANS THE SCOPE OF THE
 PLUMBING WORK TO BE DONE. IDENTIFY ON THE PLANS THE
 AREAS OF THE STRUCTURE WHERE THE WORK WILL BE DONE. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy