Plan Review Details - Permit 18071450
Plan Review Stops For Permit 18071450
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-30 Cont ID  
Sent By cthroop Date 2018-08-30 Time 15:50 Rev Time 0.00
Received By cthroop Date 2018-08-30 Time 14:39 Sent To P
Notes
2018-08-30 15:51:20ADDED PROVISO'S FOR ACCESSIBLE CLEAR PATH. RETURNED TO
 PLUMB. PER GJ. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-08-16 Cont ID  
Sent By cthroop Date 2018-08-16 Time 11:36 Rev Time 0.00
Received By cthroop Date 2018-08-16 Time 11:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-08-21 Cont ID  
Sent By jpearson Date 2018-08-21 Time 08:13 Rev Time 0.00
Received By jpearson Date 2018-08-21 Time 08:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-06 Cont ID  
Sent By scaldero Date 2018-08-06 Time 11:44 Rev Time 0.00
Received By scaldero Date 2018-08-06 Time 11:39 Sent To  
Notes
2018-08-06 11:44:10PERMIT # 18071450
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-09-04 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-31 Time 15:15 Sent To  
Notes
2018-08-01 15:15:58B25

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-09-04 Cont ID  
Sent By ccole Date 2018-09-04 Time 11:48 Rev Time 0.00
Received By ccole Date 2018-09-04 Time 11:48 Sent To I
Notes
2018-09-04 11:49:23NO MECHANICAL PLANS PROVIDED.
 SEPARATE PERMIT REQYUIRED FOR MECHANICAL ALTERATION
 WORK
 CCOLE- 9/4/18
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-04 Cont ID  
Sent By ccole Date 2018-09-04 Time 09:09 Rev Time 0.00
Received By ccole Date 2018-09-04 Time 09:09 Sent To I
Notes
2018-09-04 09:14:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18071450
 9/4/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A.1: NO MECHANICAL PLANS HAVE BEEN SUBMITTED
 HOWEVER THE FLOOR PLAN SHOWS NEW ROOMS WHICH WILL
 REQUIRE SUPPLY AND RETURN AIR. PLEASE SHOW ALL REQUIRED
 HVAC ALTERATIONS- SECTION 601.6 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-08-31 Cont ID  
Sent By gjohnson Date 2018-08-29 Time 13:18 Rev Time 0.00
Received By gjohnson Date 2018-08-31 Time 09:59 Sent To  
Notes
2018-08-29 14:05:29PLUMBING PROVISO:
 1. IN ORDER TO COMPLY WITH FBC ACC 202.4 GRAB BARS WILL
 BE INSTALLED IN BOTH EXISTING BATHROOMS THE GRAB BARS
 SHALL COMPLY WITH FBC ACC 604.5.1, 604.5.2 AND 609.4
 2. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606.3
 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED WITH
 THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE
 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 606.2CLEAR FLOOR SPACE. 30? X 48? FOR PARALLEL
 APPROACH.
  
  
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  