Plan Review Details - Permit 18071389
Plan Review Stops For Permit 18071389
Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2018-08-02 Cont ID  
Sent By hmoser Date 2018-08-02 Time 15:04 Rev Time 0.00
Received By hmoser Date 2018-07-30 Time 10:54 Sent To  
Notes
2018-07-31 10:54:45ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-02 Cont ID  
Sent By hmoser Date 2018-08-02 Time 15:04 Rev Time 0.00
Received By hmoser Date 2018-08-02 Time 14:36 Sent To I
Notes
2018-08-02 15:04:22PLAN DENIED
 1) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DETA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
 2014 FBC.
 2) REFER TO SECTION 107.3.5.1.4 MECHANICAL. # 3 PROVIDE
 EQUIPMENT SCHEDULE
 ON THE PLAN. 2017 FBC
 3) CLARIFY ON THE PLAN IF THE RETURN AIR IS ABOVE
 CEILING OR DUCTED SECTION 107 FBC
 2014
 4) REFER TO SECTION 312 HEATING & COOLING CALCULATIONS
 2017 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER