2018-07-31 10:54:45 | ROUTED TO MECHANICAL INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-08-02 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2018-08-02 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2018-08-02 |
Time |
14:36 |
Sent To |
I |
|
Notes |
2018-08-02 15:04:22 | PLAN DENIED | | 1) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION | | DOCUMENTS. | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DETA SHALL | | BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | FOR THE DESIGN. | | 2014 FBC. | | 2) REFER TO SECTION 107.3.5.1.4 MECHANICAL. # 3 PROVIDE | | EQUIPMENT SCHEDULE | | ON THE PLAN. 2017 FBC | | 3) CLARIFY ON THE PLAN IF THE RETURN AIR IS ABOVE | | CEILING OR DUCTED SECTION 107 FBC | | 2014 | | 4) REFER TO SECTION 312 HEATING & COOLING CALCULATIONS | | 2017 FBC (M) | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|
|
|