Plan Review Details - Permit 18071140
Plan Review Stops For Permit 18071140
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-30 Cont ID  
Sent By jpearson Date 2018-08-30 Time 10:11 Rev Time 0.00
Received By jpearson Date 2018-08-30 Time 10:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-13 Cont ID  
Sent By jleahy Date 2018-08-13 Time 09:44 Rev Time 0.00
Received By jpearson Date 2018-08-13 Time 09:44 Sent To  
Notes
2018-08-13 09:44:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONLY ONE SERVICE IS PERMITTED. REVISED PLAN SHOWS
 TWO SEPARATE DROPS AND SERVICES TO THE SAME OCCUPANCY.
 PROVIDE CORRECTION. NEC 230.2
 2. FOR THE GENERATOR FEED, A DISCONNECT AND EMERGENCY
 STOP BUTTON IS ALSO REQUIRED AT THE BUILDING SERVED.
 PROVIDE CORRECTION. NEC 225.32
 3. PROVIDE BLOCK NOTE THAT THE GENERATOR REQUIRES
 SEPARATE PERMIT AND PLAN SUBMITTAL. WPB FBC 105.1
 4. VALUE FOR WORK STATED ON REVISION APPLICATION
 APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE
 AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR.
 FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-28 Cont ID  
Sent By scaldero Date 2018-08-28 Time 09:45 Rev Time 0.00
Received By scaldero Date 2018-08-28 Time 09:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-07-31 Cont ID  
Sent By scaldero Date 2018-07-31 Time 15:09 Rev Time 0.00
Received By scaldero Date 2018-07-31 Time 14:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-08-30 Cont ID  
Sent By gjohnson Date 2018-08-30 Time 13:32 Rev Time 0.00
Received By gjohnson Date 2018-08-30 Time 13:32 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-08-22 Cont ID  
Sent By gjohnson Date 2018-08-22 Time 11:23 Rev Time 0.00
Received By gjohnson Date 2018-08-22 Time 11:23 Sent To  
Notes
2018-08-22 11:46:581ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE FIRST SECTION OF PIPE UPSTEAM OF THE METER IS
 UNDERSIZED IT SHALL BE 1" FOR 2014 MBTU @ 70" FBC FG
 TABLE 402.4(5)(22)
  
 2. THE TOTAL MBTU LOAD FOR THE KITCHEN, PIZZA OVEN AND
 TANLESS WATER HEATER ADDS UP TO 1144 MBTU THE PLAN
 SHOWS 994 MBTU PLEASE CLARIFY. PER WPB AMEND TO FBC
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-30 Cont ID  
Sent By gjohnson Date 2018-08-30 Time 13:33 Rev Time 0.00
Received By gjohnson Date 2018-08-24 Time 12:52 Sent To  
Notes
2018-08-27 12:56:27B04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-22 Cont ID  
Sent By gjohnson Date 2018-08-22 Time 11:47 Rev Time 0.00
Received By gjohnson Date 2018-07-25 Time 15:13 Sent To  
Notes
2018-07-26 15:13:57B14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-29 Cont ID  
Sent By ccole Date 2018-08-29 Time 16:23 Rev Time 0.00
Received By hmoser Date 2018-08-29 Time 16:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-14 Cont ID  
Sent By ccole Date 2018-08-14 Time 08:12 Rev Time 0.00
Received By ccole Date 2018-08-13 Time 17:21 Sent To  
Notes
2018-08-14 08:19:131ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18071140
 8/14/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED AC SIZING CALCULATIONS FOR RTU #2
 INDICATE AN 8-TON SYSTEM IS REQUIRED, HOWEVER THE
 CALCULATIONS SUBMITTED UNDER THE HOOD PERMIT #17110388
 INDICATE A 10-TON SYSTEM IS REQUIRED- PLEASE CORRECT.
  
 2) SHEET M0.1: THE EXHAUST FAN AND SUPPLY FAN CFMS
 SHOWN IN THE O/A BALANCE DIAGRAM DO NOT MATCH THE CFM
 CAPACITIES SHOWN ON THE HOOD PLAN- PLEASE CORRECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-30 Cont ID  
Sent By gjohnson Date 2018-08-30 Time 13:33 Rev Time 0.00
Received By gjohnson Date 2018-08-30 Time 13:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-22 Cont ID  
Sent By gjohnson Date 2018-08-22 Time 11:05 Rev Time 0.00
Received By gjohnson Date 2018-08-22 Time 08:34 Sent To  
Notes
2018-08-22 11:23:361ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE 3 COMPARTMENT SINK SHALL HAVE HOT WATER NOT
 TEMPERED WATER AS REQUIRED FOR THE PUBLIC HAND WASHING
 LAVATORY'S. IT APPEARS THAT YOU HAVE IT CONNECTED TO
 THE 110 DEG. WATER LINE WHICH IS TEMPERED IT SHOULD BE
 CONNECTED TO THE 140 DEG. PER FBC PL 607.1
  
 2. PLACE NOTE ON PLAN A SEPARATE PERMIT IS REQUIRED FOR
 THE GREASE INTERCEPTOR. WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE SIZING CALCULATION FROM SCHIER FOR GREASE
 INTERCEPTOR THIS WAS A COMMENT FROM THE FIRST ROUND OF
 COMMENTS ON THE ORIGINAL PLANS THAT WAS NEVER COMPLIED
 WITH. WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2018-08-02 Cont ID  
Sent By aaponte Date 2018-08-02 Time 17:00 Rev Time 0.00
Received By aaponte Date 2018-08-02 Time 17:00 Sent To  
Notes
***NONE***