Plan Review Details - Permit 18071136
Plan Review Stops For Permit 18071136
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-12 Cont ID  
Sent By dbattles Date 2018-09-12 Time 10:42 Rev Time 0.00
Received By dbattles Date 2018-09-12 Time 10:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-27 Cont ID  
Sent By dbattles Date 2018-07-27 Time 11:31 Rev Time 0.00
Received By dbattles Date 2018-07-27 Time 11:31 Sent To  
Notes
2018-07-27 11:31:34****CORRECTIONS****
 W.P.B. PERMIT: 18071136
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC R 301]COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 WHAT I'M LOOKING FOR IS THE SIZE OF EACH WINDOW AND IF
 ITS IN A BEDROOM. JUST LABEL YOUR WINDOWS ON PROPERTY
 APPRAISER SHEET AS 1,2..ETC AND LABEL WHICH ONES ARE IN
 BEDROOMS.
 PUT THE SIZE OF EACH WINDOW ON THE FORM FROM WEBSITE,
 OR ON YOUR OWN SPREADSHEET.
 YOU DONT NEED TO FILL OUT ALL THE INFO ON THE SHEET.
 JUST MARK TYPE OF CONSTRUCTION AS WOOD, PUT THE ROOF
 HEIGHT, WHERE IT SAYS DESIGN PRESSURE DERIVED FROM PUT
 [FBC R301.2(2), OPENING NUMBER AND OPENING SIZE. FOR
 WALL PRESSURE PUT +31.2 & -33.0. IF WINDOW IS LESS THAT
 4 FEET FROM CORNER THAN PUT +31.2 & -41.0(THE PROPOSED
 WINDOWS WILL MEET PRESSURES)
 ALL OTHER COULMNS ON FORM WON'T APPLY SINCE YOUR USING
 IMPACT WINDOWS AND NO SHUTTER IS REQUIRED.
  
 2. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN
 EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW
 FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE
 REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE
 REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE
 [FBC ENERGY 402.1.2]
 YOUR WINDOWS SHOULD HAVE U-FACTOR OF 0.75 AND SHGC OF
 0.25
 ASK WINDOW SUPPLIER AND THEY CAN VERIFY THEY WILL MEET.
 THE WINDOWS SHOULD COME WITH STICKERS ON THEM. LEAVE
 THE STICKERS ON WINDOWS UNTIL YOU PASS INSPECTION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-12 Cont ID  
Sent By dbattles Date 2018-09-12 Time 10:42 Rev Time 0.00
Received By dbattles Date 2018-09-07 Time 14:56 Sent To  
Notes
2018-09-11 14:56:22RESUB ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-27 Cont ID  
Sent By dbattles Date 2018-07-27 Time 11:31 Rev Time 0.00
Received By dbattles Date 2018-07-25 Time 13:07 Sent To  
Notes
2018-07-26 13:07:22BLDG MISC 1