Plan Review Details - Permit 18071126
Plan Review Stops For Permit 18071126
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-12-04 Cont ID  
Sent By pvalenti Date 2018-12-04 Time 08:41 Rev Time 0.00
Received By pvalenti Date 2018-12-04 Time 07:43 Sent To  
Notes
2018-12-04 08:12:23PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH PROVISO:
  
 PRIOR TO INSPECTIONS, PLEASE RESOLVE EXPIRED PERMIT
 ISSUE FOR PERMIT # 12080369 (A/C CHANGE-OUT).
  
 PRIOR TO ROOF WORK, PLEASE HAVE ROOFING PRODUCT
 APPROVALS ON SITE FOR INSPECTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 20:57 Rev Time 0.00
Received By shill Date 2018-11-02 Time 20:10 Sent To  
Notes
2018-11-02 20:59:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. A1A STATES THAT THE EXISTING PARKING LOT IS TO
 REMAIN. SEE FBC A 202.1, 202.4, PATH OF TRAVEL IS TO BE
 ACCESSIBLE. A2 DOES NOT SHOW ANY ACCESSIBLE SPACES; A1A
 DOES NOT SHOW AN ACCESS AISLE FOR THE "EXISTING
 HANDICAP PARKING SPACE". AERIALS APPEAR TO SHOW NO
 STRIPING. THERE IS NO RECORD OF A PAVING OR RESTRIPE
 PERMIT.
  
 ALSO PLEASE CONFIRM THAT THE "EXISTING RAMP" COMPLIES
 WITH FBC ACCESSIBILITY AS I WAS UNABLE TO FIND A PERMIT
 FOR THIS WORK. IF IT COMPLIES, PLEASE NOTE THAT YOU
 HAVE CONFIRMED COMPLIANCE ON THE PLAN. IF IT DOES NOT
 COMPLY, PLEASE REVISE PLAN.
  
 SEE ALSO PLUMBING COMMENTS.
  
 2ND REVIEW - SEE FBC A 502.4 AND ADVISORY. THE ACCESS
 AISLE IS TO BE THE LENGTH OF THE ACCESSIBLE SPACE PER
 502.3.2 AND IS REQUIRED TO BE LEVEL. THE RAMP
 ENCROACHES ONTO THE AREA WHICH SHOULD BE ACCESS AISLE.
 ACCESS AISLE IS TOO SHORT. NO DIMENSIONS WERE PROVIDED.
  
 THERE IS A STATEMENT THAT THE RAMP COMPLIES AND IS
 1:12. HOWEVER, THERE IS NO INFORMATION REGARDING EDGE
 PROTECTION OR RAILINGS (CANNOT DETERMINE IF THEY ARE
 REQUIRED AS DIMENSION/RUN NOT PROVIDED), LANDINGS NOT
 SHOWN 405.7 (NOTE 60X60 REQUIRED AT TOP WHERE THERE IS
 A CHANGE IN DIRECTION).
  
 PARKING IS NOT CONSIDERED "EXISTING" AS THERE IS NO
 PERMIT FOR THE STRIPING. A PERMIT APPLICATION AND PLAN
 SHOULD BE SUBMITTED AFTER THE ACCESSIBLE ROUTE ISSUE IS
 RESOLVED.
  
 2-4. OK
  
 5. ON THE DOOR PRODUCT APPROVAL, INDICATE WHICH
 THRESHOLD OPTION IS SELECTED TO SHOW COMPLIANCE WITH
 FBC A 303.
  
 2ND REVIEW, A SILL RATHER THAN A THRESHOLD WAS
 INDICATED. HEIGHT THAT CONTRACTOR MARKED IS 1.376; SEE
 FBC A 303.2, .25" MAX VERTICAL CHANGE ALLOWED.
  
 6. FIXED GLASS PRODUCT APPROVALS - SUBMITTED AND OK
  
 ROOF PRODUCT APPROVALS WERE NOT SUBMITTED. DO YOU WANT
 FOR THIS TO BE DEFFERED? FBC 107. IF NOT PROVIDED, THIS
 PERMIT WILL BE ISSUED WITH PROVISO, ROOF PRODUCT
 APPROVALS REVIEWED BY DESIGNER OF RECORD REQUIRED WITH
 ROOF PERMIT APPLICATION PRIOR TO INSTALLATION.
  
 7-8. OK
  
 NEW COMMENTS:
  
 9. THE STRUCTURAL PAGES ARE NOT SIGNED AND SEALED,
 FS471.
  
 10. A SECOND RAMP IS SHOWN AT THE REAR OF THE BUILDING,
 NEAR THE OUTDOOR COOLER. IT IS NOT CLEAR WHAT THE
 PURPOSE OF THIS RAMP IS. IT DOES NOT APPEAR TO BE IN
 THE ACCESSIBLE ROUTE; IF NOT IN THE ACCESSIBLE ROUTE,
 THE NOTE IS NOT NECESSARY, FBC 107.
  
 11. "ROUGH ESTIMATE" APPEARS LOW FBC 109.
  
 12. IF THE ACCESSIBLE ROUTE AND FRENCH DOOR ISSUES CAN
 BE RESOLVED VIA EMAIL, MEETING, OR TELEPHONE CALL, IT
 IS POSSIBLE THAT THIS REVIEW CAN BE PASSED WITH PROVISO
 FOR A REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 19:10 Rev Time 0.00
Received By shill Date 2018-08-25 Time 19:10 Sent To  
Notes
2018-08-25 19:10:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. A1A STATES THAT THE EXISTING PARKING LOT IS TO
 REMAIN. SEE FBC A 202.1, 202.4, PATH OF TRAVEL IS TO BE
 ACCESSIBLE. A2 DOES NOT SHOW ANY ACCESSIBLE SPACES; A1A
 DOES NOT SHOW AN ACCESS AISLE FOR THE "EXISTING
 HANDICAP PARKING SPACE". AERIALS APPEAR TO SHOW NO
 STRIPING. THERE IS NO RECORD OF A PAVING OR RESTRIPE
 PERMIT.
  
 ALSO PLEASE CONFIRM THAT THE "EXISTING RAMP" COMPLIES
 WITH FBC ACCESSIBILITY AS I WAS UNABLE TO FIND A PERMIT
 FOR THIS WORK. IF IT COMPLIES, PLEASE NOTE THAT YOU
 HAVE CONFIRMED COMPLIANCE ON THE PLAN. IF IT DOES NOT
 COMPLY, PLEASE REVISE PLAN.
  
 SEE ALSO PLUMBING COMMENTS.
  
 2. A5, SOME NOTES ARE TOO SMALL TO READ, REVISE, FBC
 107.
  
 3. FBC B 1004, REVISE PLAN TO INCLUDE OCCUPANCY
 CLASSIFICATION AND OCCUPANT LOAD.
  
 4. FBC B 107, IF THIS IS A2 WITH AN OCCUPANT LOAD OVER
 50, PANIC BARS REQUIRED. IF REQUIRED, INDICATE THIS
 OPTION ON THE DOOR PRODUCT APPROVAL.
  
 5. ON THE DOOR PRODUCT APPROVAL, INDICATE WHICH
 THRESHOLD OPTION IS SELECTED TO SHOW COMPLIANCE WITH
 FBC A 303.
  
 6. FIXED GLASS PRODUCT APPROVALS AND ROOF PRODUCT
 APPROVALS WERE NOT SUBMITTED. DO YOU WANT FOR THIS TO
 BE DEFFERED? FBC 107.
  
 7. THIS PROPERTY HAS TWO EXPIRED PERMITS, PLEASE
 ADDRESS, FBC 107.
  
 8. FBC 107, PRODUCT APPROVALS TO BE REVIEWED BY
 DESIGNER OF RECORD.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-11-27 Cont ID  
Sent By jpearson Date 2018-11-27 Time 14:54 Rev Time 0.00
Received By jpearson Date 2018-11-27 Time 14:54 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-09 Cont ID  
Sent By jpearson Date 2018-10-09 Time 08:03 Rev Time 0.00
Received By jpearson Date 2018-10-09 Time 08:03 Sent To  
Notes
2018-10-09 08:03:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. BASED ON THE LAST PERMIT THAT WAS
 ISSUED FOR THIS LOCATION, PERMIT 12010158, THERE ARE
 MANY ITEMS INSTALLED THAT ARE NOT INCLUDED IN THE LOAD
 CALCULATION, INCLUDING WALK IN COOLER, ADDITIONAL WINE
 COOLER AND BEER COOLERS, A SUB-PANEL NAMED PANEL B, AND
 MINI-SPLIT UNITS. NEC 215.2, 220, 408.30 (PROVIDE
 DETAIL OF KITCHEN EQUIPMENT THAT IS INCLUDED IN THE
 65%DEMAND FACTOR USED. I DO NOT SEE 6 ITEMS THAT
 QUALIFY FOR THIS DEMAD ON PANEL SCHEDULE AS EXPLAINED
 IN NEC 220.56. PROVIDE ACCURATE CALCULATION AS
 PREVIOUSLY REQUESTED.)
 2. IF ABOVE CALCULATION RESULTS IN EXCEEDING THE
 CAPACITY OF THE CURRENT SERVICE, PROVIDE CORRECTION.
 NEC 215.2, 240.4, 310.15, 408.30, 408.36 (AFTER
 CORRECTION IN COMMENT 1, APPLY AS APPLICABLE.)
 3. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30 (NO ELECTRICAL RISER DIAGRAM ON
 PLAN.)
 4. CORRECTED.
  
 NEW COMMENT:
  
 5. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC
 210.63
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-16 Cont ID  
Sent By jpearson Date 2018-08-16 Time 14:41 Rev Time 0.00
Received By jpearson Date 2018-08-16 Time 14:41 Sent To  
Notes
2018-08-16 14:41:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. BASED ON THE LAST PERMIT THAT WAS
 ISSUED FOR THIS LOCATION, PERMIT 12010158, THERE ARE
 MANY ITEMS INSTALLED THAT ARE NOT INCLUDED IN THE LOAD
 CALCULATION, INCLUDING WALK IN COOLER, ADDITIONAL WINE
 COOLER AND BEER COOLERS, A SUB-PANEL NAMED PANEL B, AND
 MINI-SPLIT UNITS. NEC 215.2, 220, 408.30
 2. IF ABOVE CALCULATION RESULTS IN EXCEEDING THE
 CAPACITY OF THE CURRENT SERVICE, PROVIDE CORRECTION.
 NEC 215.2, 240.4, 310.15, 408.30, 408.36
 3. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 4. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-09 Cont ID  
Sent By scaldero Date 2018-10-09 Time 11:46 Rev Time 0.00
Received By scaldero Date 2018-10-09 Time 11:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-31 Cont ID  
Sent By scaldero Date 2018-07-31 Time 15:17 Rev Time 0.00
Received By scaldero Date 2018-07-31 Time 15:09 Sent To  
Notes
2018-07-31 15:17:32PERMIT # 18071126
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-04 Cont ID  
Sent By pvalenti Date 2018-12-04 Time 08:42 Rev Time 0.00
Received By pvalenti Date 2018-11-19 Time 09:37 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 20:59 Rev Time 0.00
Received By shill Date 2018-10-02 Time 10:22 Sent To  
Notes
2018-10-04 10:22:46B11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 19:11 Rev Time 0.00
Received By shill Date 2018-07-24 Time 09:31 Sent To  
Notes
2018-07-26 09:31:35B09

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-11-26 Cont ID  
Sent By pvalenti Date 2018-12-04 Time 08:42 Rev Time 0.00
Received By ccole Date 2018-11-26 Time 17:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-22 Cont ID  
Sent By ccole Date 2018-10-22 Time 12:47 Rev Time 0.00
Received By ccole Date 2018-10-22 Time 12:41 Sent To  
Notes
2018-10-22 13:01:382ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18071126
 10/22/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION C403.2.1 FBC-17 ENERGY CONSERVATION.
  
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 DINING AND BAR ROOMS- TABLE 403.3.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PROVIDE AN AIR DEVICE SCHEDULE AND INDICATE THE
 SUPPLY CFMS AT EACH DIFFUSER ON THE PLAN. SHOW THE
 LOCATION OF THE MAIN RETURN GRILL AND PROVIDE
 DIMENSIONS- SECTION 603.1 FBC M.
  
 4) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307 FBC
 M. SHOW THE TYPE OF PRIMARY PIPING, THE PIPING RUN AND
 DISCHARGE LOCATION.
  
 5) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 NEW CONDENSER- SECTION 301.15
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-08 Cont ID  
Sent By ccole Date 2018-08-08 Time 08:48 Rev Time 0.00
Received By ccole Date 2018-08-08 Time 08:48 Sent To  
Notes
2018-08-08 08:54:281ST REVIEW FBC-2017 MECHANICAL
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE SUBMITTED WITH THE PLAN
 SETS, HPOWEVER A NEW AC SYSTEM IS REFERENCED IN THE
 ARCHITECTURAL PLANS. PLEASE PROVIDE COMPLETE MECHANICAL
 PLANS AND SPECIFICATIONS FOR REVIEW FOR THE PROPOSED
 PROJECT- SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2018-10-31 Cont ID  
Sent By gjohnson Date 2018-10-31 Time 15:28 Rev Time 0.00
Received By gjohnson Date 2018-10-31 Time 15:28 Sent To  
Notes
2018-10-31 15:30:471ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: NO PLUMBING SHOWN ON PLAN, PER
 RESPONSE LETTER FROM ARCHITEC PLUMBING IS EXISTING TO
 REMAIN.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By gjohnson Date 2018-08-24 Time 08:46 Rev Time 0.00
Received By gjohnson Date 2018-08-24 Time 06:41 Sent To  
Notes
2018-08-24 10:03:371ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. NO PLUMBING SHOWN ON PLAN PLEASE PROVIDE DETAILED
 SCOPE OF ANY PLUMBING WORK BEING DONE ON THIS PROJECT.
 PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE INDICATE LEVEL OF ALTERATION ON THE PLAN. PER
 FBC EX CH 5
  
 3. PLEASE PROVIDE A COST BREAK DOWN TO SHOW COMPLIANCE
 WITH
  
 FBC ACC 202.4 ALTERATIONS AFFECTING PRIMARY FUNCTION
 AREAS.IN ADDITION TO THE REQUIREMENTS OF 202.3, AN
 ALTERATION THAT AFFECTS OR COULD AFFECT THE USABILITY
 OF OR ACCESS TO AN AREA CONTAINING A PRIMARY FUNCTION
 SHALL BE MADE SO AS TO ENSURE THAT, TO THE MAXIMUM
 EXTENT FEASIBLE, THE PATH OF TRAVEL TO THE ALTERED
 AREA, INCLUDING THE REST ROOMS, TELEPHONES, AND
 DRINKING FOUNTAINS SERVING THE ALTERED AREA, ARE
 READILY ACCESSIBLE TO AND USABLE BY INDIVIDUALS WITH
 DISABILITIES, UNLESS SUCH ALTERATIONS ARE
 DISPROPORTIONATE TO THE OVERALL ALTERATIONS IN TERMS OF
 COST
  
 FBC ACC 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
  
 FBC ACC 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
 PER FBC EX 705
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-16 Cont ID  
Sent By llouie Date 2018-10-16 Time   Rev Time 0.00
Received By llouie Date 2018-10-15 Time   Sent To  
Notes
2018-10-16 15:26:32LANDSCAPE INSPECTION REQUIRED PRIOR TO CERTIFICATE OF
 OCCUPANCY TO DETERMINE IF THE EXISTING LANDSCAPING
 MATCHES THE 2009 LANDSCAPE PLAN, SUBMITTED WITH THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-20 Cont ID  
Sent By llouie Date 2018-08-20 Time   Rev Time  
Received By llouie Date 2018-08-20 Time   Sent To  
Notes
2018-08-20 10:34:13** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED, SIGNED AND SEALED SURVEY IS REQUIRED.
 SURVEY SUBMITTED WITH THE PERMIT APPLICATION IS A COPY
 AND IT IS OUTDATED.
  
 2.) MISSING DATA IN THE SITE PLAN TABULAR (SHEET A-IA),
 INCLUDING THE LOT COVERAGE AND FLOOR AREA RATIO (FAR),
 ETC.
  
 3.) HEIGHT DIMENSION MISSING FROM THE ELEVATIONS.
  
 4.) SHOW SETBACK DISTANCE OF THE FUTURE A/C UNIT
 CONDENSER IN THE SITE PLAN. A/C UNIT CONDENSER CANNOT
 ENCROACH MORE THAN 4 FT. INTO A SETBACK. [ZLDR
 S.94-305(A)]
  
 5.) THE VALUE OF THE CONSTRUCTION ($65,000.00) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($62,661.00) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: NC
  
  
  