2018-07-28 10:16:47 | 1) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYER PER |
| THE 2017 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES |
| DRYERS) OR 2017 FBC-RES. SEC.G 2407.1 AND G2439.4. |
| 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. |
| REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING |
| SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON |
| THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING |
| INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR |
| CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017 |
| FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. |
| 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1. |
| 4) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3. THE SIZING TABLES THAT |
| HAVE BEEN SUBMITTED ARE FROM A PREVIOUS EDITION OF THE |
| CODE. |
| 5) SHOW THE TOTAL LENGTH OF THE PIPING FROM THE POINT |
| OF DELIVERY TO THE MOST REMOTE OUTLET ON THE 2 PSI |
| SYSTEM AND FOR THE LOW PRESSURE SYSTEM. 2017 FBC-FUEL |
| GAS SEC.402.4.1. |
| 6) THE GAS RISER SHOWS A 2 PSI SYSTEM TO THE INTERIOR |
| BUT IT ALSO SHOWS AN MP REGULATOR ON THE EXTERIOR OF |
| THE STRUCTURE. HOW CAN YOU HAVE 2 PSI INTO THE |
| STRUCTURE IF YOU HAVE A REGULATOR ON THE LINE ON THE |
| EXTERIOR OF THE BUILDING? CLARIFY. |
| 7) IDENTIFY WHICH LINE IS THE 2 PSI LINE AND WHICH ONE |
| IS THE 1/2 PSI LINE ON BOTH GAS RISERS. IT IS |
| DIFFFICULT TO TELL WHICH ONE IS WHICH. WPB AMEND. TO |
| FBC SEC. 107.2.1. |
| 8) LIST THE CORRESPONDING EHD FOR THE CSST ON THE GAS |
| RISERS. WPB AMEND. TO FBC SEC. 107.2.1. |
| 9) INDICATE THE TYPE AND SIZE OF THE PIPE AT THE OUTLET |
| OF THE GAS METER. WPB AMEND. TO FBC SEC. 107.2.1. |
| 10) THE TOTAL RUN OF THE LOW PRESSURE SYSTEN ON THE GAS |
| RISER ADDS TO 100 FEET, NOT 90 FEET AS SHOWN. CLARIFY. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |