Plan Review Details - Permit 18071081
Plan Review Stops For Permit 18071081
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-09-27 Cont ID  
Sent By fgiaquin Date 2018-09-27 Time 07:05 Rev Time 0.00
Received By fgiaquin Date 2018-09-27 Time 06:34 Sent To I
Notes
2018-09-27 07:05:27PLAN PASSED WITH PROVISIONS:
  
 EITHER ADD/RELOCATE MAIN THAT IS NOT GROUPED FOR ONE
 METER (RED-LINED ON DRAWING) OR COMPLETELY REMOVE METER
 CAN. MAINS MUST BE GROUPED. NEC 230.72A

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-06 Cont ID  
Sent By jleahy Date 2018-09-06 Time 17:14 Rev Time 0.00
Received By jleahy Date 2018-09-06 Time 17:14 Sent To  
Notes
2018-09-06 17:20:11FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS STILL SHOW 1200 AMPERE SWITCH, NEED TO SHOW THAT
 IT IS ONLY 1200 WITH A 1000A TRIPPING MODUAL SO WIRE
 MATCHES MAIN.
  
 HOW DOES THE KIRK KEY SYSTEM WORK ON A TAP BOX?
  
 ONE METER BEING BLANKED OFF MAIN MISSING FROM THAT
 METER.
  
 SUBMIT CUT SHEETS FOR KIRK KEY SYSTEM
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-28 Cont ID  
Sent By fgiaquin Date 2018-07-28 Time 11:37 Rev Time 0.00
Received By fgiaquin Date 2018-07-28 Time 10:55 Sent To I
Notes
2018-07-28 11:37:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AMPACITY OF WIRE INSUFFICIENT FOR A 1200AMP
 COMMERICAL SERVICE. WIRE SIZE IS TYPICALLY 3- SETS OF
 600MCM WITH 3/0G. 310.15 (B)16 NEC 230.42 NEC
  
 2. SERVICE SIZE IS BEING INCREASED. PROVIDE ACCURATE
 LOAD CALCULATION INCLUDING ALL LOADS. NEC 220
  
 3. EXISTING SERVICE ONE-LINE DIAGRAM SHOWS UPROTECTED
 SERVICE CONDUCTORS AND FEEDER CONDUCTORS IN SAME
 RACEWAY/GUTTER. PROVIDE CORRECTIONS 230.7 NEC
  
 4. SHOW TRANSFORMER SECONDARY CONDUCTORS AND RACEWAY ON
 EXISTING AND NEW PROPOSED ONE-LINE DIAGRAM .FBC 107.2.1
  
 5. SHOW BONDING FOR SERVICE ON NEW PROPOSED ONE-LINE
 DIAGRAM FBC 107.2.1
  
 6. DISCONNECTS NOT GROUPED AS PER 230.72A NEC ON NEW
 PROPOSED ONE-LINE DIAGRAM. WHERE IS DISCONNECT FOR 1ST
 METER AFTER 1200AMP MAIN? PROVIDE CORRECTIONS.
  
 7. PROVIDE UL/NRTL LISTINGS FOR NEW TAP BOX AND 1200AMP
 MAIN. 110.3B NEC, FBC 107.2.1
  
 8. SHOW LOCATION OF ELECTRICAL SERVICE AND NEW TAP BOX
 ON SITE PLAN. FBC 107.2.1
  
 9. VALUE SEEMS LOW, VALUE WILL BE ADDRESSED WHEN RE-SUB
 COMES IN AND WE HAVE ALL THE MISSING REQUIRED
 INFORMATION. FBC 109.3 FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-27 Cont ID  
Sent By fgiaquin Date 2018-09-27 Time 07:05 Rev Time 0.00
Received By fgiaquin Date   Time   Sent To  
Notes
2018-09-26 11:16:43SENT TO FG JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-06 Cont ID  
Sent By jleahy Date 2018-09-06 Time 17:20 Rev Time 0.00
Received By jleahy Date 2018-09-06 Time 16:37 Sent To  
Notes
2018-09-06 16:37:32SPALMER GAVE TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-28 Cont ID  
Sent By fgiaquin Date 2018-07-28 Time 11:37 Rev Time 0.00
Received By fgiaquin Date 2018-07-24 Time 14:25 Sent To  
Notes
2018-07-25 14:25:56ROUTED TO ELECTRICAL INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved