Plan Review Details - Permit 18071054
Plan Review Stops For Permit 18071054
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-08-29 Cont ID  
Sent By jleahy Date 2018-08-29 Time 12:30 Rev Time 0.00
Received By jleahy Date 2018-08-29 Time 12:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-20 Cont ID  
Sent By hmoser Date 2018-08-20 Time 13:40 Rev Time 0.00
Received By hmoser Date 2018-08-14 Time 14:19 Sent To  
Notes
2018-08-15 14:20:08RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-28 Cont ID  
Sent By hmoser Date 2018-07-28 Time 10:53 Rev Time 0.00
Received By hmoser Date 2018-07-24 Time 09:20 Sent To  
Notes
2018-07-26 09:20:25ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-20 Cont ID  
Sent By hmoser Date 2018-08-20 Time 13:40 Rev Time 0.00
Received By hmoser Date 2018-08-20 Time 13:17 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-28 Cont ID  
Sent By hmoser Date 2018-07-28 Time 10:53 Rev Time 0.00
Received By hmoser Date 2018-07-28 Time 10:06 Sent To  
Notes
2018-07-28 10:53:18PLAN DENIED
 1) REFER TO SECTION 107.2.1 FBC 2017 PROVIDE
 SIGNATURE ON PLAN.
 2) PROVIDE SEER OF EQUIPMENT ON PLAN. SECTION
 107 FBC 2017.
 3) ONE STACK OF PLANS HAS NO R-405 ENERGY
 FORM ( INFORMATION ON CONDENSER )
 4) OTHER STACK OF PLANS HAS FIVE HEAT LODE
 CALCULATION OTHER HAS THREE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676