Plan Review Details - Permit 18070938
Plan Review Stops For Permit 18070938
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-13 Cont ID  
Sent By ppetty Date 2018-08-13 Time 13:39 Rev Time 0.00
Received By ppetty Date 2018-08-13 Time 13:39 Sent To  
Notes
2018-08-13 13:43:12CONDUIT IN SHELL ONLY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-31 Cont ID  
Sent By fgiaquin Date 2018-07-31 Time 06:53 Rev Time 0.00
Received By fgiaquin Date 2018-07-31 Time 06:17 Sent To I
Notes
2018-07-31 06:37:25ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A FULL AND COMPLETE ELECTRICAL REVIEW IS NOT
 POSSIBLE AT THIS TIME. THE ENGINEERED DRAWINGS SHOW 7
 PAGES OF (E) DRAWINGS AND ONLY 4 HAVE BEEN SUBMITTED.
 PLEASE SUBMIT FULL SET OF ENGINEERED DRAWINGS.
  
 THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLEASE REVIEW
 THE FOLLOWING SECTIONS FROM THE WEST PALM BEACH
 AMENDMENTS TO THE FBC:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2. ZERO INCREASE IN VALUE? THE VALUE FOR THE ELECTRICAL
 INSTALLATION OF THIS BUILDING WAS NOT INCLUDED IN THE
 REFERENCED MASTER PERMIT. PROVIDE CORRECTION.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-31 Cont ID  
Sent By fgiaquin Date 2018-07-31 Time 06:53 Rev Time 0.00
Received By fgiaquin Date 2018-07-20 Time 09:44 Sent To  
Notes
2018-07-24 09:44:55REVISION ROUTED TO ELECTRICAL INBOX