Plan Review Details - Permit 18070844
Plan Review Stops For Permit 18070844
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-07-31 Cont ID  
Sent By dbattles Date 2018-07-31 Time 16:37 Rev Time 0.00
Received By dbattles Date 2018-07-31 Time 16:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-08-30 Cont ID  
Sent By jpearson Date 2018-08-30 Time 16:38 Rev Time 0.00
Received By jpearson Date 2018-08-30 Time 16:38 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-21 Cont ID  
Sent By jpearson Date 2018-08-21 Time 07:20 Rev Time 0.00
Received By jpearson Date 2018-08-21 Time 07:20 Sent To I
Notes
2018-08-21 07:20:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (BOTH
 COPIES) IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. THIS
 PERSON MUST BE A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION.
 WPB FBC 107.1, 107.2; FS 471, 481 (PLAN NOT SIGNED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-10 Cont ID  
Sent By jpearson Date 2018-08-10 Time 16:28 Rev Time 0.00
Received By jpearson Date 2018-08-10 Time 16:28 Sent To I
Notes
2018-08-10 16:27:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (BOTH
 COPIES) IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. THIS
 PERSON MUST BE A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION.
 WPB FBC 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-07-25 Cont ID  
Sent By pleduc Date 2018-07-25 Time   Rev Time 0.00
Received By pleduc Date 2018-07-25 Time 10:43 Sent To I
Notes
2018-07-25 12:53:46THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE
 SHOP DRAWINGS BY CERIFIED LIFE SAFETY CONTRACTOR.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-08-30 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-29 Time 15:07 Sent To  
Notes
2018-08-30 15:07:21RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-08-21 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-17 Time 14:21 Sent To  
Notes
2018-08-20 14:21:50RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-08-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-18 Time 15:37 Sent To  
Notes
2018-07-19 15:37:41B16

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-08-07 Cont ID  
Sent By ccole Date 2018-08-07 Time 17:09 Rev Time 0.00
Received By ccole Date 2018-08-07 Time 17:09 Sent To  
Notes
***NONE***