Plan Review Details - Permit 18070821
Plan Review Stops For Permit 18070821 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2018-08-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-25 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-25 |
Time |
13:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-08-03 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-08-03 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-08-03 |
Time |
16:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2018-07-27 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-07-27 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-07-27 |
Time |
08:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-09-21 |
Time |
|
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-09-05 |
Time |
16:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-08-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-25 |
Time |
13:13 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-18 |
Time |
14:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2018-09-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-09-21 |
Time |
12:47 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-09-21 |
Time |
12:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-08-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-08-10 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-08-10 |
Time |
15:05 |
Sent To |
|
|
Notes |
2018-08-10 16:48:32 | 1ST REVIEW FBC-2010 MECHANICAL | | REVISION #18070821 | | PERMIT #15111020 | | 8/10/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M2-90-15A: PLEASE IDENTIFY THE DUCTS THAT ARE | | PENETRATING THE FIRE-RATED LAUNDRY/CORE COMMON WALLS. | | SHOW DUCT SIZES AND DAMPER SYMBOLS AT THE PENETRATIONS. | | | | 2) M2-90A-15A: IT DOES NOT APPEAR THAT ALL AIR FROM THE | | MASTER SUITES, INCLUDING THE CLOSETS AND BATHS, IS | | BEING RETURNED AS REQUIRED BY SECTION 601.4 (3). | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2018-08-22 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-08-22 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-08-22 |
Time |
15:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2018-08-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-25 |
Time |
13:13 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-25 |
Time |
13:13 |
Sent To |
|
|
Notes |
|
|
|