Plan Review Details - Permit 18070669
Plan Review Stops For Permit 18070669 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-08-09 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-08-09 |
Time |
05:56 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-08-09 |
Time |
05:56 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-07-20 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-07-20 |
Time |
06:26 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-07-20 |
Time |
06:16 |
Sent To |
M |
|
Notes |
2018-07-20 06:25:59 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON | | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS | | 481.229; WPB FBC 107.2.1, 107.3.5.1.2 | | | | 2. CORRECT ADDRESS ISSUE. PERMIT APPLICATION SAYS SUITE | | #1, PLANS SAY SUITE #B9, I'M THE ELECTRICAL INSPECTOR | | FOR THE DUNKIN DONUTS PROJECT AND THE CORRECT ADDRESS | | IS B7 OR #007. FBC 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-08-08 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-08-08 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-08-07 |
Time |
16:23 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2018-07-17 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-07-17 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-07-17 |
Time |
13:59 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-08-10 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2018-08-10 |
Time |
11:28 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2018-07-30 |
Time |
13:55 |
Sent To |
|
|
Notes |
2018-07-31 13:56:15 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-07-20 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2018-07-20 |
Time |
11:41 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2018-07-16 |
Time |
11:13 |
Sent To |
|
|
Notes |
2018-07-17 11:13:45 | ROUTED TO FIRE INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2018-08-10 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2018-08-10 |
Time |
11:28 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2018-08-10 |
Time |
11:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2018-07-20 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2018-07-20 |
Time |
11:41 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2018-07-20 |
Time |
11:12 |
Sent To |
I |
|
Notes |
|
|
|