Plan Review Details - Permit 18070655
Plan Review Stops For Permit 18070655
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-21 Cont ID  
Sent By dbattles Date 2018-09-21 Time 14:53 Rev Time 0.00
Received By dbattles Date 2018-09-21 Time 14:51 Sent To  
Notes
2018-09-21 14:54:22ADJUST FEE VALUE FOR BUILDING AND ELECTRICAL COSTS
 COMBINED TO $14,400.00
 MECHANICAL PERMIT WILL BE SEPARATE PERMIT AND THE VALUE
 IS EXCLUDED FORM THIS PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-31 Cont ID  
Sent By dbattles Date 2018-07-31 Time 11:44 Rev Time 0.00
Received By dbattles Date 2018-07-31 Time 10:58 Sent To  
Notes
2018-07-31 11:44:51****CORRECTIONS****
 W.P.B. PERMIT: 18070655
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 109]PROVIDE COPY OF PROPOSAL WITH CONTRACTOR TO
 SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN ON PERMIT
 APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL COST OF
 WORK. VALUE WILL BE FOR ALL WORK INCLUDING MECHANICAL
 AND ELECTRICAL.
  
 2. [FBC 107.2.5]HEAD AND SILL DETAIL ARE FOR WOOD FRAME
 2X6. PROVIDE DETAILS FOR SITE CONDITIONS(2X4
 CONSTRUCTION AND MASONRY CONSTRUCTION).
 ALSO, BUCK DETAILS FOR BOTH CONDITIONS.
  
 3. [FBC 107.2.5]PROVIDE INFILL DETAILS IF OPENINGS ARE
 BEING ADJUSTED.
  
 4. [FBC 107.2.5]THE WINDOW PRODUCT APPROVAL ALLOWS FOR
 OPENINGS UP TO 52".
 PLEASE ADJUST WINDOWS TO MEET PRODUCT APPROVAL. I WOULD
 SUGGEST A WINDOW SCHEDULE. SELECT WINDOW TYPE FOR WALL
 TYPE (NAIL FIN OR THROUGH FRAME, IF WINDOW IS EGRESS,
 PROVIDE BOTH R.O. AND WINDOW SIZE FOR EACH
 WINDOW.(WINDOW SCHEDULE)
  
 5. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN
 EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW
 FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE
 REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE
 REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE
 R402.1.2.
 YOUR WINDOWS SHOULD HAVE U-FACTOR OF 0.75 AND SHGC OF
 0.25THE WINDOWS SHOULD COME WITH STICKERS ON THEM.
 LEAVE THE STICKERS ON WINDOWS UNTIL YOU PASS
 INSPECTION.
  
 6. [FBC R317.1] 5.WOOD SIDING, SHEATHING AND WALL
 FRAMING ON THE EXTERIOR OF A BUILDING HAVING A
 CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE
 GROUND OR LESS THAN 2 INCHES (51 MM) MEASURED
 VERTICALLY FROM CONCRETE STEPS, PORCH SLABS, PATIO
 SLABS AND SIMILAR HORIZONTAL SURFACES EXPOSED TO THE
 WEATHER.
  
 7. WHEN RE-SUBMITTING HAVE THE PERMIT APPLICATION
 NOTARIZED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-09-26 Cont ID  
Sent By jpearson Date 2018-09-26 Time 13:24 Rev Time 0.00
Received By jpearson Date 2018-09-26 Time 13:24 Sent To  
Notes
2018-09-26 13:24:28PROVISO ADDED TO PLAN.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-25 Cont ID  
Sent By jpearson Date 2018-09-25 Time 08:58 Rev Time 0.00
Received By jpearson Date 2018-09-25 Time 08:58 Sent To I
Notes
2018-09-25 08:57:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3 (COPY OF CONTRACT NOT PROVIDED.)
 2. CORRECTED.
 3. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902 (NOT CORRECTED, NOTE STILL
 STATES BEDROOMS TO BE AFCI, PANEL SCHEDULE DOES NOT
 SHOW ALL AREAS REQUIRED.)
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3 (THIS IS REQUIRED IN
 RESIDENTIAL INSTALLATIONS, WHICH IS WHY IT IS LISTED IN
 THE FBC RESIDENTIAL R3606.3. PROVIDE AS REQUESTED.)
 5. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1 (NOTE NOT PROVIDED.)
 6. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-10 Cont ID  
Sent By jpearson Date 2018-08-10 Time 11:26 Rev Time 0.00
Received By jpearson Date 2018-08-10 Time 11:26 Sent To I
Notes
2018-08-10 11:26:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
 2. SCOPE OF WORK STATES ALL NEW WIRING. PLAN MUST SHOW
 EACH LOCATION OF RECEPTACLES AND LIGHTING REQUIRED BY
 CODE. APARTMENT 738 DOES NOT SHOW THIS. PROVIDE
 CORRECTION. NEC 210.52; FBC RE E3901.2.1
 3. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3
 5. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-09-25 Time   Rev Time 0.00
Received By lmarchan Date 2018-09-11 Time 10:29 Sent To  
Notes
2018-09-13 10:29:41R22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-08-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-16 Time 09:43 Sent To  
Notes
2018-07-18 09:43:29R11

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-08-06 Cont ID  
Sent By cmontell Date 2018-08-06 Time 13:12 Rev Time 0.00
Received By cmontell Date 2018-08-06 Time 13:11 Sent To  
Notes
2018-08-06 13:12:40MECHANICAL CONTRACTOR TO PULL PERMIT FOR NEW A/C AND
 DUCTWORK
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]