Plan Review Details - Permit 18070628
Plan Review Stops For Permit 18070628
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 08:54 Rev Time 0.00
Received By tklarge Date 2018-07-20 Time 14:47 Sent To  
Notes
2018-07-23 14:47:51RESUB ROUTED TO THUNT
 **TRAVELLING WITH 18070628**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-17 Cont ID  
Sent By thunt Date 2018-07-17 Time 15:19 Rev Time 0.00
Received By thunt Date 2018-07-13 Time 13:18 Sent To I
Notes
2018-07-16 13:18:48PLUMB <5K
 *TRAVELLING WITH 18070627*

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 08:53 Rev Time 0.00
Received By tklarge Date 2018-07-26 Time 08:35 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-17 Cont ID  
Sent By thunt Date 2018-07-17 Time 15:15 Rev Time 0.00
Received By thunt Date 2018-07-17 Time 15:15 Sent To  
Notes
2018-07-17 15:19:3807/17/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) PROVIDE WASHER AND DRYERS INSTALLATION MANUAL AND
 SHOW EXISTING LOCATION OF UNIT AND VERIFY ACCESS TO
 SHUT-OFF VALVE LOCATION. FBC 107.3.5
  
 2) AAV'S ARE NOT PERMITTED ON A 2" HORIZONTAL BUILDING
 DRAIN. FBC 303.2
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]