Plan Review Details - Permit 18070624
Plan Review Stops For Permit 18070624
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-09-06 Cont ID  
Sent By tklarge Date 2018-09-06 Time 17:51 Rev Time 0.00
Received By lcrespo Date 2018-09-06 Time 17:51 Sent To  
Notes
2018-09-06 17:53:0509/06/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-07-26 Cont ID  
Sent By rmcdouga Date 2018-07-26 Time 13:13 Rev Time 0.00
Received By tklarge Date 2018-07-26 Time 12:51 Sent To I
Notes
2018-07-26 13:13:161) SHOW THE PIPE SIZE DOWNSTREM OF ALL SHUTOFF VALVES
 2) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2014 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
 3) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2014 FBC RES. SEC. G2413.2, G2413.4.3.
 4) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL
 ADDED GAS EQUIPMENT NOT SHOWN ON ORIGINAL PLAN TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 5) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-06 Cont ID  
Sent By lcrespo Date 2018-09-06 Time 17:53 Rev Time 0.00
Received By lcrespo Date 2018-08-29 Time 16:00 Sent To  
Notes
2018-08-30 16:01:44RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 13:13 Rev Time 0.00
Received By tklarge Date 2018-07-18 Time 15:00 Sent To  
Notes
2018-07-19 15:00:54REVISION ROUTED TO RMCDOUGAL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-09-07 Cont ID  
Sent By rmcdouga Date 2018-09-07 Time 09:24 Rev Time 0.00
Received By rmcdouga Date 2018-09-07 Time 09:24 Sent To I
Notes
***NONE***