Plan Review Details - Permit 18070525
Plan Review Stops For Permit 18070525
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-09-04 Cont ID  
Sent By jleahy Date 2018-09-04 Time 13:44 Rev Time 0.00
Received By jleahy Date 2018-09-04 Time 13:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-08-21 Cont ID  
Sent By fgiaquin Date 2018-08-21 Time 07:04 Rev Time 0.00
Received By fgiaquin Date 2018-08-21 Time 06:58 Sent To I
Notes
2018-08-21 07:04:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALC NOT TO NEC 220.84 REQUIREMENTS. DEMAND
 FACTOR OF 45% IS ONLY APPLIED ONE TIME TO THE ENTIRE
 LOAD. SQUARE FOOTAGE FOR APARTMENTS IS 24,984 BUT VA IS
 24,984 ALSO???
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-10 Cont ID  
Sent By fgiaquin Date 2018-08-10 Time 07:19 Rev Time 0.00
Received By fgiaquin Date 2018-08-10 Time 06:36 Sent To I
Notes
2018-08-10 07:19:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. INACCURATE LOAD CALCULATION. NO HOUSE LOAD INCLUDED
 IN CALCULATION. ACTUAL CALCULATED LOAD (NOT INCLUDING
 HOUSE LOAD BECAUSE IT WAS NOT PROVIDED) IS 320AMPS NOT
 292AMPS. PLEASE SEE MULTI-FAMILY DWELLING LOAD CALC
 REQUIREMENTS 220.84 B&C NEC AND TABLE 220.84 NEC
  
 2. SHOW EXISING WIRE SIZE TO FPL TRANSFORMER TO VERIFY
 IT CAN SUPPORT THE LOAD. NEC 220.16A1&2, 220.12, 220.14
 FBC RE 3602.1, FBC RE 3602.2, FBC 107.2.1
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-19 Cont ID  
Sent By fgiaquin Date 2018-07-19 Time 06:24 Rev Time 0.00
Received By fgiaquin Date 2018-07-19 Time 06:11 Sent To I
Notes
2018-07-19 06:24:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLEAS
 PROVIDE CLEARLY DRAWN, LEGIBLE PLAN. PLEASE REVIEW THE
 FOLLOWING SECTIONS FROM THE WEST PALM BEACH AMENDMENTS
 TO THE FBC:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
  
 2. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
  
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-09-04 Cont ID  
Sent By jleahy Date 2018-09-04 Time 13:44 Rev Time 0.00
Received By jleahy Date 2018-08-29 Time 15:12 Sent To  
Notes
2018-08-30 15:12:34RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-21 Cont ID  
Sent By fgiaquin Date 2018-08-21 Time 07:04 Rev Time 0.00
Received By fgiaquin Date 2018-08-17 Time 14:15 Sent To  
Notes
2018-08-20 14:15:34RESUB ROUTED TO FGIAQUIN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-10 Cont ID  
Sent By fgiaquin Date 2018-08-10 Time 07:19 Rev Time 0.00
Received By fgiaquin Date 2018-08-08 Time 15:30 Sent To  
Notes
2018-08-09 15:30:22RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-19 Cont ID  
Sent By fgiaquin Date 2018-07-19 Time 06:24 Rev Time 0.00
Received By fgiaquin Date 2018-07-12 Time 13:28 Sent To  
Notes
2018-07-13 13:28:32ROUTED TO ELECTRICAL INBOX