Plan Review Details - Permit 18070315
Plan Review Stops For Permit 18070315
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-16 Cont ID  
Sent By shill Date 2018-08-16 Time 10:30 Rev Time 0.00
Received By shill Date 2018-08-16 Time 10:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-10 Cont ID  
Sent By shill Date 2018-08-10 Time 06:58 Rev Time 0.00
Received By shill Date 2018-08-10 Time 06:58 Sent To  
Notes
2018-08-10 07:09:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 PLEASE CONTACT ME IF YOU WANT ASSISTANCE WITH
 SUBMITTING.
  
 2. DELEGATED ENGINEERING WAS SUBMITTED.
  
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS.
 2017 FBC-B 2204.1 WELDING, 2204.2 BOLTING.
  
 PROVIDE INFORMATION AS TO WHO WILL BE PERFORMING THESE
 INSPECTIONS. REVISE PLAN TO CLARIFY INSTALLATION
 LOCATION.
  
 3. OK
  
 4. NOAS WERE SUBMITTED AS INDIVIDUAL PAGES. ALL PRODUCT
 APPROVALS SHOULD BE UPLOADED AS ONE PDF INTO
 "SUPPORTING DOCUMENTS" FOLDER.
  
 2ND REVIEW - THE NUMEROUS INDIVIDUAL PAGES HAVE BEEN
 DELETED FOR YOU. THE NEW DOCUMENT NAMED "NOA PDF.PDF"
 INCLUDES THE FIRST TWO NOA PAGES UPSIDE DOWN, THEN
 DELEGATED ENGINEERING SHOP DRAWINGS (WHICH WERE ALSO
 INCLUDED IN THE DRAWINGS FOLDER), THEN WHAT APPEARS TO
 BE PAGES FROM A FLORIDA STATE PRODUCT APPROVAL.
  
 PROVIDE A CLEAN PRODUCT APPROVAL; EITHER NOA OR FLORIDA
 STATE PRODUCT APPROVAL IS ACCEPTABLE. IF USING A
 FLORIDA STATE PRODUCT APPROVAL, INCLUDE THE COVER PAGE
 WHICH SHOWS THE STATUS AND OTHER INFORMATION
 (WWW.FLORIDABUILDING.ORG). IF USING A NOA, INCLUDE TH
 ENTIRE DOCUMENT, IN ORDER. ALL PAGES SHOULD BE IN
 PORTRAIT ORIENTATION.
  
 FILES SHOULD BE NAMED IN A LOGICAL NAMING CONVENTION.
 THE NOA PAGES WHICH I DELETED HAD COMPUTER GENERATED
 NAMES (APPEARED TO BE SCANS) WHICH WERE ARBITRARY.
  
 IF YOU ARE UNABLE TO FOLLOW DIGITAL SUBMITTAL
 PROCEDURES, PLEASE CONVERT THIS SUBMITTAL TO PAPER.
 DIGITAL SUBMITTALS ARE SUITED TO DIGITAL DOCUMENTS. IT
 APPEARS THAT THESE DOCUMENTS WERE ORIGINALLY DIGITAL,
 PRINTED, SCANNED, UPLOADED. THIS IS RESULT IN DIFFICULT
 TO READ DOCUMENTS.
  
 WE DISCUSSED HAVING THE WINDOW DELEGATED ENGINEERING
 REMOVED BECAUSE IT DUPLICATES THE PRODUCT APPROVAL. IN
 REVIEWING, THE DELEGATED ENGINEERING ALSO INCLUDES
 OTHER DETAILS WHICH ARE NOT IN THE PRODUCT APPROVAL AND
 ARE SITE SPECIFIC. THESE DOCUMENTS ARE NEEDED FOR
 INSPECTIONS.
  
 IF YOU CHOOSE TO KEEP THIS SUBMITTAL DIGITAL, PLEASE
 UPLOAD THE WINDOW DELEGATED ENGINEERING AS ONE DOCUMENT
 RATHER THAN SEPARATE PAGES.
  
 5. OK
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-21 Cont ID  
Sent By shill Date 2018-07-21 Time 15:11 Rev Time 0.00
Received By shill Date 2018-07-21 Time 15:11 Sent To  
Notes
2018-07-21 15:11:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, PROVIDE ROOM DESIGNATION FOR 1-100, A1.1.
  
 2. DELEGATED ENGINEERING WAS SUBMITTED.
  
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS.
 2017 FBC-B 2204.1 WELDING, 2204.2 BOLTING.
  
 PROVIDE INFORMATION AS TO WHO WILL BE PERFORMING THESE
 INSPECTIONS. REVISE PLAN TO CLARIFY INSTALLATION
 LOCATION.
  
 3. WINDOW DETAILS WERE PROVIDED. PLEASE REMOVE. ALL
 DOOR INSTALLATION DETAILS SHOULD BE INCLUDED IN THE
 PRODUCT APPROVAL, WHICH WAS NOT PROVIDED. SUPPLEMENTARY
 SHOP DRAWINGS DO NOT NEED TO BE SUBMITTED FOR REVIEW
 UNLESS THEY DEVIATE FROM THE PRODUCT APPROVAL, FBC 107.
  
 4. NOAS WERE SUBMITTED AS INDIVIDUAL PAGES. ALL PRODUCT
 APPROVALS SHOULD BE UPLOADED AS ONE PDF INTO
 "SUPPORTING DOCUMENTS" FOLDER.
  
 5. REVISE PLAN TO CLARIFY - INTERIOR AND EXTERIOR
 STOREFRONT IS PROPOSED. IS EXTERIOR STOREFRONT PROPOSED
 FOR BOTH INTERIOR AND EXTERIOR LOCATIONS?
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-16 Cont ID  
Sent By shill Date 2018-08-16 Time 10:31 Rev Time 0.00
Received By shill Date 2018-08-13 Time 13:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-10 Cont ID  
Sent By shill Date 2018-08-10 Time 07:09 Rev Time 0.00
Received By shill Date 2018-08-06 Time 10:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-21 Cont ID  
Sent By shill Date 2018-07-21 Time 15:13 Rev Time 0.00
Received By shill Date 2018-07-09 Time 13:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-08-16 Cont ID  
Sent By shill Date 2018-08-16 Time 10:30 Rev Time 0.00
Received By shill Date 2018-08-16 Time 10:30 Sent To  
Notes
2018-08-16 10:30:51PROVIDE ORIGINAL PAPER S&S DELEGATED ENGINEER SHOP
 DRAWINGS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-08-10 Cont ID  
Sent By shill Date 2018-08-10 Time 07:09 Rev Time 0.00
Received By shill Date 2018-08-10 Time 07:09 Sent To  
Notes
2018-08-10 07:09:46DOCUMENTS SIGNED AND SEALED BY TOM TWOMEY, PE ARE NOT
 DIGITALLY SIGNED AND SEALED
 STRUCTURAL & A SHEETS OK
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-07-21 Cont ID  
Sent By shill Date 2018-07-21 Time 15:11 Rev Time 0.00
Received By shill Date 2018-07-21 Time 15:11 Sent To  
Notes
2018-07-21 15:13:09DOCUMENTS SIGNED AND SEALED BY TOM TWOMEY, PE ARE NOT
 DIGITALLY SIGNED AND SEALED
 STRUCTURAL & A SHEETS OK
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-18 Cont ID  
Sent By eschneid Date 2018-07-18 Time 13:58 Rev Time 0.50
Received By eschneid Date 2018-07-18 Time 13:58 Sent To  
Notes
***NONE***