Plan Review Details - Permit 18070134
Plan Review Stops For Permit 18070134 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2018-07-12 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-07-12 |
Time |
18:51 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-07-12 |
Time |
18:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-07-12 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-07-12 |
Time |
17:19 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-07-12 |
Time |
17:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2018-07-23 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-23 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-23 |
Time |
13:09 |
Sent To |
|
|
Notes |
2018-07-23 13:09:41 | THERE IS NO HEATER ON THIS POOL. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-08-07 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-08-07 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-08-01 |
Time |
11:31 |
Sent To |
|
|
Notes |
2018-08-02 11:32:11 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-07-23 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-23 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-03 |
Time |
13:21 |
Sent To |
|
|
Notes |
2018-07-05 13:21:17 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2018-08-07 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-08-07 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-08-07 |
Time |
10:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-07-23 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-23 |
Time |
13:01 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-23 |
Time |
12:27 |
Sent To |
I |
|
Notes |
2018-07-23 13:08:21 | 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE | | MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM | | ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN | | DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC | | 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION | | ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT | | REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED | | THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET | | FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS | | MUST INCLUDE ALL OF THE SYSTEM COMPONENTS IN THE PIPING | | SYSTEM INCLUDING THE FILTER. | | 2) SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE. | | IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC | | TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS | | NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH | | CALCULATIONS. | | 3) INDICATE ON THE POOL PUMP SPECS WHICH PUMP IS BEING | | INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1. | | 4) SHT. 4 OF 4 - PLEASE REVISE NOTES #7 & #8 - | | REFERENCE IS MADE TO 2017 FBCR SEC. R 4101.6.6. THIS | | SECTION HAS NOTHING TO DO WITH SWIMMING POOLS. | | 5) SHTS.1 & 2 - THERE IS A NOTE IN THE UPPER LEFT | | CORNER OF THE SHEET NOTING THAT THE POOL PIPING HAS | | BEEN DESIGNED BASED ON THE MAXIMUM FLOW CAPACITY OF THE | | SWIMMING POOL PUMP. THIS DESIGN IS NO LONGER PERMITTED | | BY APSP-7 2013. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2018-08-03 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-08-03 |
Time |
16:38 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-08-03 |
Time |
16:38 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-07-11 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-07-11 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-07-11 |
Time |
14:36 |
Sent To |
|
|
Notes |
2018-07-11 14:40:13 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | 1) INDICATE THE LOCATION OF THE POOL EQUIPMENT. | | | | NOTE: PURSUANT TO 94-305(B)(4) - MECHANICAL EQUIPMENT | | MAY NOT PROJECT MORE THAN 4 FEET INTO A SETBACK. | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | PLANNING DEPARTMENT WEBSITE AT | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | | | MAGGIE CRUZ | | ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: 561-822-1442 | | E-MAIL: [email protected] | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |