Plan Review Details - Permit 18070095
Plan Review Stops For Permit 18070095
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-01-04 Cont ID  
Sent By shill Date 2019-01-04 Time 17:41 Rev Time 0.00
Received By shill Date 2019-01-04 Time 17:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 17:25 Rev Time 0.00
Received By shill Date 2018-12-08 Time 17:25 Sent To  
Notes
2018-12-08 17:25:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THIS APPEARS TO BE LOCATED IN EXPOSURE C DUE TO THE
 LARGE OPEN AREAS WHICH LACK BUILDINGS (OKEECHOBEE, PALM
 BEACH LAKES, PARKING LOT). PLEASE CONTACT ME IF YOU
 WISH TO DISCUSS.
  
 PLEASE LET ME KNOW WHEN THIS IS RESUBMITTED SO I CAN
 PRIORITIZE THIS REVIEW.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-05 Cont ID  
Sent By shill Date 2018-09-05 Time 18:35 Rev Time 0.00
Received By shill Date 2018-09-05 Time 18:35 Sent To  
Notes
2018-09-05 18:35:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, REVISE PLAN TO INCLUDE WIND DESIGN
 CRITERIA.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-07 Cont ID  
Sent By jpearson Date 2018-11-07 Time 09:11 Rev Time 0.00
Received By jpearson Date 2018-11-07 Time 09:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-20 Cont ID  
Sent By jpearson Date 2018-09-20 Time 12:04 Rev Time 0.00
Received By jpearson Date 2018-09-20 Time 12:04 Sent To I
Notes
2018-09-20 12:04:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 17:26 Rev Time 0.00
Received By shill Date 2018-10-29 Time 14:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-09-20 Time   Rev Time 0.00
Received By lmarchan Date 2018-09-04 Time 13:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-25 Cont ID  
Sent By lmarchan Date 2018-07-25 Time 13:10 Rev Time 0.00
Received By lmarchan Date 2018-07-03 Time 15:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-11-07 Cont ID  
Sent By jpearson Date 2018-11-07 Time 08:55 Rev Time 0.00
Received By jpearson Date 2018-11-07 Time 08:55 Sent To  
Notes
2018-11-07 08:55:11ALL SHEETS OK. IF RE-SUBMITTAL REQUIRED, NEW SHEETS
 WILL NEED TO BE CONFIRMED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-09-05 Cont ID  
Sent By shill Date 2018-09-05 Time 18:31 Rev Time 0.00
Received By shill Date 2018-09-05 Time 18:31 Sent To  
Notes
2018-09-05 18:36:21SIGNATURES OK
 NEW PAGES SUBMITTED NEXT REVIEW CYCLE REQUIRE
 VERIFICATION
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-11-26 Cont ID  
Sent By eschneid Date 2018-11-26 Time 13:48 Rev Time 0.50
Received By eschneid Date 2018-11-26 Time 13:48 Sent To  
Notes
2018-11-26 13:51:34PASSED W/PROVISOS
  
 1) THE LANDSCAPE FOR THE ENCLOSURE MUST BE INSTALLED
 PRIOR TO THE 104 FINAL INSPECTION. THE LANDSCAPE MUST
 BE SHOWN ON AN APPROVED, REVISED LANDSCAPE PERMIT.
  
 2) PRIOR TO THE C.O. OF EITHER THE CAR WASH OR BENTLEY
 SHOWROOM, WHICHEVER OCCURS 1ST, A MINOR PLANNED
 DEVELOPMENT AMENDMENT MUST BE SUBMITTED TO THE PLANNING
 DIVISION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2018-09-19 Cont ID  
Sent By eschneid Date 2018-09-19 Time 17:11 Rev Time 0.50
Received By eschneid Date 2018-09-18 Time 12:35 Sent To  
Notes
2018-09-18 14:56:34FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE SUBMITTED PLANS DO NOT MATCH THE PLANS APPROVED
 AS PART OF THE LATEST MINOR PLANNED DEVELOPMENT
 AMENDMENT ON APRIL 4, 2018.
  
 A. THE ENTRANCE TO THE COMPACTOR ENCLOSURE AND THE
 LANDSCAPE HAVE BEEN SHIFTED.
 B. THE TIRE STORAGE NOW SHOWS A SLIDE GATE. THIS IS NOT
 PERMITTED WITH THE CURRENT WIDTH OF THE ADJACENT
 LANDSCAPE AREA SINCE THERE IS NOT SUFFICIENT ROOM FOR
 THE GATE TO SLIDE PAST THE SABLE PALM TREE. IF THE
 SLIDE GATE WILL BE USED, THEN THE LANDSCAPE AREA NEEDS
 TO BE WIDENED.
 C. PRIOR TO THE C.O. OF EITHER THE CAR WASH OR THE
 BENTLEY SHOW ROOM, WHICHEVER OCCURS FIRST, A MINOR
 AMENDMENT TO SHOW THE ACCURATE CONDITIONS IS REQUIRED.
  
 2) PLEASE CLARIFY IF THE SLIDE GATE WILL BE MANUAL OR
 ELECTRIC. IF ELECTRIC, YOU MUST SHOW THE GATE EQUIPMENT
 ON THE PLANS.
  
 3) THE LANDSCAPE FOR THE ENCLOSURE NEEDS TO BE
 INSTALLED PRIOR TO THE FINAL INSPECTION (104) FOR THE
 DUMPSTER ENCLOSURE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-18 Cont ID  
Sent By LL Date 2018-07-18 Time 11:38 Rev Time 0.50
Received By eschneid Date 2018-07-18 Time 11:38 Sent To  
Notes
2018-07-18 12:03:14FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE SUBMITTED PLANS DO NOT MATCH THE PLANS AND
 CONDITIONS APPROVED BY ZONING ON APRIL 4, 2018, AS PART
 OF THE LATEST MINOR PLANNED DEVELOPMENT AMENDMENT.
  
 A. THE REQUIRED FIVE (5) FOOT WIDE LANDSCAPE BUFFER
 ALONG EXCHANGE COURT HAS BEEN REMOVED ON THIS SET OF
 PLANS.
 B. THE TRASH ENCLOSURE GATES (BOTH VEHICLE AND
 PEDESTRIAN) ARE REQUIRED TO PROVIDE OPAQUE SCREENING.
 THE USE OF SLATS WITHIN THE CHAIN LINK IS NOT
 PERMITTED.
  
 2) THE ENCLOSURE DOOR MAY NOT SWING INTO THE EXCHANGE
 COURT RIGHT-OF-WAY AND BLOCK THE SIDEWALK.
  
 3) THE LANDSCAPE FOR THE ENCLOSURE NEEDS TO BE
 INSTALLED PRIOR TO THE FINAL INSPECTION (104) FOR THE
 DUMPSTER ENCLOSURE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]