Plan Review Details - Permit 18070082
Plan Review Stops For Permit 18070082
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-02 Cont ID  
Sent By shill Date 2018-08-02 Time 09:32 Rev Time 0.00
Received By shill Date 2018-08-02 Time 09:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By shill Date 2018-07-26 Time 07:24 Rev Time 0.00
Received By shill Date 2018-07-26 Time 07:24 Sent To  
Notes
2018-07-26 07:26:09PROVISO
 COMPONENT & CLADDING DESIGN PRESSURES WERE NOT PROVIDED
 ROOF, STOREFRONT, OH DOOR, AND OTHER PRODUCT APPROVALS
 ARE TO BE SUBMITTED PRIOR TO INSTALLATION. WHEN THEY
 ARE SUBMITTED, PROVIDE A SIGNED AND SEALED LETTER FROM
 THE STRUCTURAL ENGINEER OF RECORD WHICH SPECIFY DESIGN
 PRESSURES, FBC B 1609.
 PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By shill Date 2018-07-23 Time 14:25 Rev Time 0.00
Received By shill Date 2018-07-23 Time 14:25 Sent To  
Notes
2018-07-23 14:26:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PLANS ARE NOT DIGITALLY SIGNED AND SEALED, FS471,
 FS481.
  
 DUE TO THE WAY THEY WERE UPLOADED, THEY ARE DIFFICULT
 TO REVIEW. PLEASE OBTAIN DIGITALLY SIGNED AND SEALED
 DOCUMENTS FROM THE DESIGN PROFESSIONALS. PLEASE SEND
 SAMPLE PAGES TO ME VIA EMAIL IF YOU ARE NOT SURE IF
 THEY ARE COMPLIANT.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-02 Cont ID  
Sent By jleahy Date 2018-08-02 Time 08:14 Rev Time 0.00
Received By jleahy Date 2018-08-02 Time 08:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-07-26 Cont ID  
Sent By jpearson Date 2018-07-26 Time 11:35 Rev Time 0.00
Received By jpearson Date 2018-07-26 Time 11:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-08-03 Cont ID  
Sent By scaldero Date 2018-08-03 Time 10:46 Rev Time 0.00
Received By scaldero Date 2018-08-03 Time 10:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By scaldero Date 2018-07-26 Time 10:40 Rev Time 0.00
Received By scaldero Date 2018-07-26 Time 10:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-05 Cont ID  
Sent By scaldero Date 2018-07-05 Time 09:21 Rev Time 0.00
Received By scaldero Date 2018-07-05 Time 08:28 Sent To  
Notes
2018-07-05 09:21:43PERMIT # 18070082
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) ADDITIOMAL DETAILS REQUIRED REGARDING NEW "HARD
 CANOPY" TO BE INSTALLED ALONG THE LENGTH OF THE STORE
 FRONT. PLEASE PROVIDE DIMENSIONS AND MATERIAL DETAILS.
 PER NFPA 1, CHAPTER 13:
 13.3.2.6* EXTERIOR ROOFS, CANOPIES, PORTE-COCHERES,
 BALCONIES, DECKS, OR SIMILAR PROJECTIONS. IN BUILDINGS
 PROTECTED THROUGHOUT BY AUTOMATIC SPRINKLERS IN
 ACCORDANCE WITH NFPA 13, AUTOMATIC SPRINKLER PROTECTION
 SHALL BE PROVIDED FOR THE EXTERIOR SPACES IN ACCORDANCE
 WITH 13.3.2.6.
  
 13.3.2.6.1 UNLESS THE REQUIREMENTS OF 13.3.2.6.2,
 13.3.2.6.3, OR 13.3.2.6.4 ARE MET, SPRINKLERS SHALL BE
 INSTALLED UNDER EXTERIOR PROJECTIONS EXCEEDING 4 FT
 (1.2 M) IN WIDTH. [13:8.15.7.1]
  
 13.3.2.6.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH
 MATERIALS THAT ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE,
 OR FIRE RETARDANT ?TREATED WOOD AS DEFINED IN NFPA 703.
 [13:8.15.7.2]
  
 13.3.2.6.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM BELOW THE EXTERIOR PROJECTIONS OF COMBUSTIBLE
 CONSTRUCTION, PROVIDED THE EXPOSED FINISH MATERIAL ON
 THE EXTERIOR PROJECTIONS ARE NONCOMBUSTIBLE,
 LIMITED-COMBUSTIBLE, OR FIRE RETARDANT ?TREATED WOOD AS
 DEFINED IN NFPA 703, AND THE
 EXTERIOR PROJECTIONS CONTAIN ONLY SPRINKLERED CONCEALED
 SPACES OR ANY OF THE FOLLOWING UNSPRINKLERED
 COMBUSTIBLE CONCEALED SPACES:
 (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH
 NONCOMBUSTIBLE INSULATION
 (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE
 NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE CEILINGS ARE
 DIRECTLY ATTACHED TO THE BOTTOM OF SOLID WOOD JOISTS SO
 AS TO CREATE ENCLOSED JOIST SPACES 160 FT3 (4.5 M3) OR
 LESS IN VOLUME, INCLUDING SPACE BELOW INSULATION THAT
 IS LAID DIRECTLY ON TOP OR WITHIN THE
 CEILING JOISTS IN AN OTHERWISE SPRINKLERED ATTIC [SEE
 11.2.3.1.4(4)(D) OF NFPA 13]
 (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR
 PROJECTIONS NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA
 [13:8.15.7.3]
  
 13.3.2.6.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF
 THE CORRIDOR ARE AT LEAST 50 PERCENT OPEN AND WHEN THE
 CORRIDOR IS ENTIRELY OF NONCOMBUSTIBLE CONSTRUCTION.
 [13:8.15.7.4]
  
 13.3.2.6.5* SPRINKLERS SHALL BE INSTALLED UNDER
 EXTERIOR PROJECTIONS GREATER THAN 2 FT (0.6 M) WIDE
 OVER AREAS WHERE COMBUSTIBLES ARE STORED. [13:8.15.7.5]
  
 13.3.2.6.5.1 THE REQUIREMENT OF 13.3.2.6.5 MAY BE
 OMITTED IF THE SEPARATION OF ROOFS, CANOPIES,
 PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR
 PROJECTIONS ARE A MINIMUM OF 5 FT (1.5 M) FROM THE
 SPRINKLERED BUILDING. THIS PROVISION IS EFFECTIVE FOR
 NEW CONSTRUCTION PROJECTS ONLY.
  
 2) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 3) SHEET A500: THE REQUIRED LOCKING MECHANISM IS NOT
 SPECIFICALLY IDENTIFIED. ENTRY DOORS: THUMB-TURN LOCK
 TO BE EQUIPPED WITH A LOCK/UNLOCK INDICATOR.
  
 4) EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE BARRIER-PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2018-08-01 Time 15:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-26 Cont ID  
Sent By jpearson Date 2018-07-26 Time 14:17 Rev Time  
Received By cpuell Date 2018-07-03 Time 16:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-08-02 Cont ID  
Sent By skennedy Date 2018-08-02 Time 09:36 Rev Time 0.00
Received By skennedy Date 2018-08-02 Time 09:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-08-02 Cont ID  
Sent By ccole Date 2018-08-02 Time 07:42 Rev Time 0.00
Received By ccole Date 2018-08-02 Time 07:42 Sent To  
Notes
2018-08-02 07:44:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18070082
 8/2/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED M101 & M102 PLAN SHEETS REQUIRE
 ELECTRONIC SIGNATURES AND SEALS BY THE EOR FOR FINAL
 APPROVAL- SECTION 61G15-23.005 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-25 Cont ID  
Sent By ccole Date 2018-07-25 Time 16:05 Rev Time 0.00
Received By ccole Date 2018-07-25 Time 14:06 Sent To  
Notes
2018-07-25 16:30:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18070082
 7/25/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE FOLLOWING COMMENTS ARE ADDRESSING THE MECHANICAL
 PLANS THAT WERE DESIGNED BY FELIX MENDEZ P.E. OF 3FM
 CONSULTING ENGINEERS. PLEASE NOTE THERE IS A SEPARATE
 SET OF MECHANICAL PLANS DESIGNED BY ROBERT L. QUETHEM
 P.E. THAT WERE APPROVED UNDER PERMIT #18051434. THERE
 CANNOT BE TWO ENGINEERS OF RECORD FOR THE PROPOSED
 PROJECT PER FLORIDA STATUTE 471.
  
 1) SHEET M101: DUCT SMOKE DETECTORS ARE REQUIRED FOR
 EACH OF THE RTU'S IN ACCORDANCE WITH SECTION 606.2.1
 FBC- M. PLEASE SHOW THE LOCATIONS OF THE REQUIRED
 DEVICES AND INDICATE COMPLIANCE WITH THE FOLLOWING CODE
 SECTIONS:
  
 606.4 CONTROLS OPERATION.
 UPON ACTIVATION, THE SMOKE DETECTORS SHALL SHUT DOWN
 ALL OPERATIONAL CAPABILITIES OF THE AIR DISTRIBUTION
 SYSTEM IN ACCORDANCE WITH THE LISTING AND LABELING OF
 APPLIANCES USED IN THE SYSTEM. AIR DISTRIBUTION SYSTEMS
 THAT ARE PART OF A SMOKE CONTROL SYSTEM SHALL SWITCH TO
 THE SMOKE CONTROL MODE UPON ACTIVATION OF A DETECTOR.
  
 606.4.1 SUPERVISION.
 THE DUCT SMOKE DETECTORS SHALL BE CONNECTED TO A FIRE
 ALARM SYSTEM WHERE A FIRE ALARM SYSTEM IS REQUIRED BY
 THE FLORIDA FIRE PREVENTION CODE. THE ACTUATION OF A
 DUCT SMOKE DETECTOR SHALL ACTIVATE A VISIBLE AND
 AUDIBLE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION. IN FACILITIES THAT ARE REQUIRED TO BE
 MONITORED BY A SUPERVISING STATION, DUCT SMOKE
 DETECTORS SHALL REPORT ONLY AS A SUPERVISORY SIGNAL,
 NOT AS A FIRE ALARM.
  
 EXCEPTIONS:
 1.THE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION IS NOT REQUIRED WHERE THE DUCT SMOKE DETECTOR
 ACTIVATES THE BUILDING'S ALARM-INDICATING APPLIANCES.
 2.IN OCCUPANCIES NOT REQUIRED TO BE EQUIPPED WITH A
 FIRE ALARM SYSTEM, ACTUATION OF A SMOKE DETECTOR SHALL
 ACTIVATE A VISIBLE AND AUDIBLE SIGNAL IN AN APPROVED
 LOCATION. DUCT SMOKE DETECTOR TROUBLE CONDITIONS SHALL
 ACTIVATE A VISIBLE OR AUDIBLE SIGNAL IN AN APPROVED
 LOCATION AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR
 TROUBLE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 10:35 Rev Time 0.00
Received By tklarge Date 2018-07-26 Time 10:35 Sent To  
Notes
2018-07-26 10:36:04REMOVAL OF EXISTING BREAK ROOM SINK ONLY.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-07-26 Cont ID  
Sent By shill Date 2018-07-26 Time 07:20 Rev Time 0.00
Received By shill Date 2018-07-26 Time 07:20 Sent To  
Notes
2018-07-26 07:23:00PROVISO - NO ROOF INFORMATION PROVIDED WITH MASTER
  
 PRIOR TO INSTALLATION, SUBMIT A ROOF SUB PERMIT
 APPLICATION WITH PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, AND ENGINEERING FOR ENHANCED
 FASTENING (IF REQUIRED). DESIGN PRESSURES TO COMPLY
 WITH DESIGN PRESSURES SPECIFIED BY SEOR.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-08-02 Cont ID  
Sent By shill Date 2018-08-02 Time 09:26 Rev Time 0.00
Received By shill Date 2018-08-02 Time 09:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-07-26 Cont ID  
Sent By shill Date 2018-07-26 Time 06:54 Rev Time 0.00
Received By shill Date 2018-07-26 Time 06:54 Sent To  
Notes
2018-07-26 06:55:03SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. OK - DIGITAL SIGNATURES/SEALS (PLAN PAGES,
 CALCULATIONS) ARE IN ACCORDANCE WITH FS 471, FS 481 AS
 (A,S,M,E,P). NEW SHEETS SUBMITTED IN THE NEXT REVIEW
 CYCLE REQUIRE REVIEW.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By shill Date 2018-07-23 Time 14:27 Rev Time 0.00
Received By shill Date 2018-07-23 Time 14:27 Sent To  
Notes
2018-07-23 14:28:05SEE BUILDING REVIEW
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-08-06 Cont ID  
Sent By eschneid Date 2018-08-06 Time 16:40 Rev Time 0.50
Received By eschneid Date 2018-08-06 Time 16:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-26 Cont ID  
Sent By eschneid Date 2018-07-26 Time 13:58 Rev Time 0.50
Received By eschneid Date 2018-07-26 Time 13:58 Sent To  
Notes
2018-07-26 13:59:45THE PALM BEACH OUTLETS DESIGN GUIDELINES DO NOT PERMIT
 BANNERS ON THIS BUILDING SO THE FASTENERS FOR BANNERS
 ARE NOT PERMITTED.