Plan Review Details - Permit 18061476
Plan Review Stops For Permit 18061476
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-16 Cont ID  
Sent By cthroop Date 2018-08-16 Time 13:25 Rev Time 0.00
Received By cthroop Date 2018-08-16 Time 12:30 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-27 Cont ID  
Sent By cthroop Date 2018-07-27 Time 07:51 Rev Time 0.00
Received By cthroop Date 2018-07-26 Time 17:06 Sent To  
Notes
2018-07-27 07:55:11BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1. PROVIDE DESIGN WIND LOADS FOR OPENINGS TO RECEIVE
 NEW DOORS. CANNOT VERIFY DESIGN PRESSURES OF NEW DOORS
 ARE ADEQUATE.
 2. PROVISO - WELDER CERTIFICATIONS SHALL BE MADE
 AVAILABLE AT TIME OF INSPECTION.
  
 FBC 107.3.5.1.1(8) ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-07-25 Cont ID  
Sent By jleahy Date 2018-07-25 Time 11:27 Rev Time 0.00
Received By jleahy Date 2018-07-25 Time 11:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-08 Cont ID  
Sent By pleduc Date 2018-08-08 Time   Rev Time 0.00
Received By pleduc Date 2018-08-07 Time 16:21 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-05 Cont ID  
Sent By pleduc Date 2018-07-05 Time   Rev Time 0.00
Received By pleduc Date 2018-07-05 Time 12:28 Sent To  
Notes
2018-07-05 13:29:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) IT IS NOT CLEAR IF THE ADDED DEMO AND ALTERATION OF
 THE NORTH TOWER LOBBY OR OTHER WORK WAS PART OF THE
 MASTER.
  
 THOSE PLAN SHEETS ARE NOT MARKED WITH REVISION CLOUDS
 OR REVISION NARRATIVES.
  
 THOSE PLAN SHEETS MAY NEED TO BE UNDER SEPARATE PERMITS
 OR FURTHER CLARIFIED WITH GREATER DETAIL.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-08-20 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-01 Time 14:44 Sent To  
Notes
2018-08-02 14:44:36RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-27 Cont ID  
Sent By cthroop Date 2018-07-27 Time 07:55 Rev Time 0.00
Received By cthroop Date 2018-06-29 Time 10:38 Sent To I
Notes
2018-07-03 10:38:32B15

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-20 Cont ID  
Sent By ccole Date 2018-08-20 Time 13:27 Rev Time 0.00
Received By ccole Date 2018-08-20 Time 07:46 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-16 Cont ID  
Sent By ccole Date 2018-07-16 Time 11:15 Rev Time 0.00
Received By ccole Date 2018-07-16 Time 09:47 Sent To  
Notes
2018-07-16 11:36:481ST REVIEW FBC-2017 MECHANICAL
 REVISION #18061476
 MASTER #18040489
 7/1618
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS DM-101 & M-101: PROVIDE COOLING AND HEATING
 CALCULATIONS FOR THE NEW WSHP-1. IT APPEARS BY THE DEMO
 DRAWINGS THAT THIS AREA WAS NEVER FULLY CONDITIONED
 BEFORE- SECTION C403.2.1 FBC EC.
  
 2) M-101: PROVIDE AN ACCESS PANEL FOR THE NEW WSHP-1 IN
 COMPLIANCE WITH SECTION 306.1 FBC M.
  
 3) M-101: PROVIDE A FLORIDA PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE O/A LOUVER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  