2018-07-17 07:21:05 | 07/16/2018 GAS/LP/TANK REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. I HAVE RESEARCHED CITY RECORDS BACK TO 1996 AND |
| THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF |
| AN LP TANK. SINCE THERE IS NO RECORD OF A PERMIT FOR |
| THE LP TANK, THE TANK MUST BE INCLUDED IN THIS PERMIT |
| FOR THIS SCOPE OF WORK. WPB AMENDMENTS TO THE FBC SEC. |
| 105.1.2. |
| |
| 2. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| 3. SHOW THE METHOD OF REQUIRED PROTECTION FOR THE LP |
| TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS |
| BELOW GROUND IT SHALL BE ANCHORED PER NFPA 58 |
| SEC.3-2.2.7 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW GRADE. |
| COMPLY WITH NFPA 58 SEC. 6.6.6.1. |
| |
| 5. A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER |
| NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE |
| MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS |
| ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS.) & A |
| NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE. |
| |
| 6. THE TANK SHALL BE A MIN OF 10' FROM ANY SOURCE OF |
| IGNITION ACCORDING TO NFPA TABLE 6.3.4.3 SEPARATION |
| DISTANCE BETWEEN CONTAINER PRESSURE RELIEF VALVE AND |
| BUILDING OPENINGS. |
| |
| 7. THE LOCATION OF THE UNDERGROUND LP TANK SHALL COMPLY |
| WITH TABLE 6.3.1 OF NFPA 58-11. SHOW THE DISTANCE OF |
| THE LP TANK FROM THE EXTERIOR WALL OF THE STRUCTURE. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |