Plan Review Details - Permit 18061452
Plan Review Stops For Permit 18061452
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-10-29 Cont ID  
Sent By jgomez Date 2018-10-29 Time 10:13 Rev Time 0.00
Received By jgomez Date 2018-10-29 Time 09:57 Sent To  
Notes
2018-10-29 10:11:31BUILDING REVIEW APPROVED WITH PROVISO:
 1- ROOF TO WALL CONNECTIONS ARE DONE UNDER PERMIT
 16061174.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-10-22 Cont ID  
Sent By jgomez Date 2018-10-22 Time 12:35 Rev Time 0.00
Received By jgomez Date 2018-10-19 Time 18:36 Sent To  
Notes
2018-10-19 18:53:06RESIDENTIAL (R3) RE-ROOF FOURTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 ORIGINAL COMMENT:
 1- IT LOOKS LIKE THE HOUSE WAS DESIGNED FOR SHINGLES AS
 A ROOF COVERING. PROPOSED ROOFING MATERIAL IS CONCRETE
 TILES. PROVIDE ENGINEERING ANALYSIS SHOWING THAT THE
 EXISTING STRUCTURE IS CAPABLE OF SUPPORTING THE
 ADDITIONAL LOAD. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE:
 ENGINEER'S CERTIFICATION LETTER OF CONCRETE TILE REROOF
 SUBMITTED IS NOT CLEAR. IT SAYS THAT THE PROPOSED
 REROOFING ACTIVITIES WILL NOT REQUIRE MODIFICATIONS BUT
 AT THE SAME TIME IS SAYING THAT ADDITIONAL PLYWOOD AND
 WOOD FRAMING MEMBERS MAY BE REQUIRED. ENGINEER NEEDS TO
 BE SPECIFIC IF ADDITIONAL REINFORCEMENT IS REQUIRED AND
 NEEDS TO POINT OUT THE EXACT LOCATIONS. CLEARLY
 DESCRIBE EXISTING ROOFING SYSTEM.
 ALSO, CLARIFY THE LIMITATIONS. THE LIMITATIONS STATE
 THAT THE AREAS OF THE STRUCTURE BEYOND THE LIMITS OF
 THE ROOF FRAMING WERE NOT REVIEWED AND THAT THE SUBJECT
 ROOF ANALYSIS DOES NOT INDICATE SATISFACTORY OR MINIMUM
 COMPLIANCE WITH THE CURRENT EDITION OF THE FLORIDA
 BUILDING CODE. THE PURPOSE OF THE ENGINEER ANALYSIS IS
 TO SHOW THAT EXISTING STRUCTURE IN ITS ENTIRETY IS
 CAPABLE OF SUPPORTING THE ADDITIONAL LOAD. SEC. 707.2
 FBC-EXISTING BUILDING.
  
  
 ORIGINAL COMMENT:
 2- HOUSE VALUE IS MORE THAN $300.000. NEED TO COMPLY
 WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED BY SEC.
 706.8 FBC-EXISTING-BUILDING.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 SEC. 706.8:
 WHEN A ROOF COVERING ON AN EXISTING SITE-BUILT
 SINGLE-FAMILY RESIDENTIAL STRUCTURE IS REMOVED AND
 REPLACED ON A BUILDING THAT IS LOCATED IN THE
 WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE
 OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR
 FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT
 PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR
 PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE:
 (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS
 REQUIRED BY SECTION 706.8.1.
 (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION
 SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN
 THE COST OF REROOFING.
 EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES
 PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT
 REQUIRED TO COMPLY WITH THIS SECTION.
  
 NOTE: ROOF TO WALL WORK NEED TO BE DONE UNDER A
 SUBPERMIT. ACCORDING TO ROBERT (BROWN (BUILDING
 OFFICIAL) ROOFING CONTRACTOR CAN NOT DO THIS WORK
 UNLESS LICENSE TO DO SO.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
2018-10-18 18:43:59 
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-10-03 Cont ID  
Sent By jgomez Date 2018-10-03 Time 12:48 Rev Time 0.00
Received By jgomez Date 2018-10-03 Time 12:24 Sent To  
Notes
2018-10-03 12:24:3210/03/18 READ E-MAIL FROM GERI SHUBERT.
  
 HAVE A GREAT DAY
 GERI SHUBERT
 DIVERSIFIED ROOFING SOLUTIONS, INC
 450 SOUTH OLD DIXIE HWY #1
 JUPITER, FL 33458
 561-841-5676
  
  
  
  
 THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 NOTE:
 IT IS NOT CLEAR WHY SUBMITTING A TWO STORY WALL
 SECTION. THE ITEMS BELOW ARE THE ONES THAT NEED TO BE
 ADDRESSED. PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS,
 SO WE CAN FINISH PROCESSING THIS PERMIT. NOTE: ROOF TO
 WALL WORK NEED TO BE DONE UNDER A SUBPERMIT. ACCORDING
 TO ROBERT (BROWN (BUILDING OFFICIAL) ROOFING CONTRACTOR
 CAN NOT DO THIS WORK UNLESS LICENSE TO DO SO.
  
  
  
 PLAN REVIEW COMMENTS:
 1- IT LOOKS LIKE THE HOUSE WAS DESIGNED FOR SHINGLES AS
 A ROOF COVERING. PROPOSED ROOFING MATERIAL IS CONCRETE
 TILES. PROVIDE ENGINEERING ANALYSIS SHOWING THAT THE
 EXISTING STRUCTURE IA CAPABLE OF SUPPORTING THE
 ADDITIONAL LOAD. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 2- HOUSE VALUE IS MORE THAN $300.000. NEED TO COMPLY
 WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED BY SEC.
 706.8 FBC-EXISTING-BUILDING.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 SEC. 706.8:
 WHEN A ROOF COVERING ON AN EXISTING SITE-BUILT
 SINGLE-FAMILY RESIDENTIAL STRUCTURE IS REMOVED AND
 REPLACED ON A BUILDING THAT IS LOCATED IN THE
 WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE
 OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR
 FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT
 PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR
 PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE:
 (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS
 REQUIRED BY SECTION 706.8.1.
 (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION
 SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN
 THE COST OF REROOFING.
 EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES
 PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT
 REQUIRED TO COMPLY WITH THIS SECTION.
  
 3- NEW FLAT ROOF NOA 15-0622.21 AND ENGINEER RAS 117
 CALCULATIONS SUBMITTED ARE OK. NEED TO PROVIDE TWO
 COPIES OF ENGINEER CALCULATIONS WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 WHEN ENGINEER IS SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
  
 NEW COMMENTS:
 4- NEW ROOF TILE PRODUCT APPROVAL WAS SUBMITTED. ONLY
 THE COVER PAGES OF FLORIDA PRODUCT APPROVAL FL7849-R11
 WAS SUBMITTED. NEED TO PROVIDE COMPLETE INSTALLATION
 INSTRUCTIONS FOR SPECIFIC ROOF TILE TO BE INSTALLED.
 AND CLEARLY SPECIFY/MARK ADHESIVE PADDY SIZE AND RIDGE
 MATERIAL TO BE USED. PROVIDE 2 COPIES.
 FAC 61G20-3.001.
  
 5- NEW ROOF TILE ADHESIVE PRODUCT APPROVAL WAS
 SUBMITTED. ONLY THE COVER PAGES OF FLORIDA PRODUCT
 APPROVAL FL6332-R8 WAS SUBMITTED. NEED TO PROVIDE
 COMPLETE INSTALLATION INSTRUCTIONS AND CLEARLY
 SPECIFY/MARK ADHESIVE PADDY SIZE AND RIDGE MATERIAL ON
 PAGES 3 AND 4 OF INSTALLATION INSTRUCTIONS. PROVIDE 2
 COPIES.
 FAC 61G20-3.001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-01 Cont ID  
Sent By jgomez Date 2018-08-01 Time 11:47 Rev Time 0.00
Received By jgomez Date 2018-08-01 Time 10:31 Sent To  
Notes
2018-08-01 10:42:3208/01/18 RECEIVED E-MAIL FROM CONTRACTOR.
  
 SEE ATTACHED PER YOUR CORRECTION
  
 HAVE A GREAT DAY
 GERI SHUBERT
 DIVERSIFIED ROOFING SOLUTIONS, INC
 450 SOUTH OLD DIXIE HWY #1
 JUPITER, FL 33458
 561-841-5676
  
  
  
  
  
 SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- IT LOOKS LIKE THE HOUSE WAS DESIGNED FOR SHINGLES AS
 A ROOF COVERING. PROPOSED ROOFING MATERIAL IS CONCRETE
 TILES. PROVIDE ENGINEERING ANALYSIS SHOWING THAT THE
 EXISTING STRUCTURE IA CAPABLE OF SUPPORTING THE
 ADDITIONAL LOAD. SEC. 107.2.1.2 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 2- HOUSE VALUE IS MORE THAN $300.000. NEED TO COMPLY
 WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED BY SEC.
 706.8 FBC-EXISTING-BUILDING.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 SEC. 706.8:
 WHEN A ROOF COVERING ON AN EXISTING SITE-BUILT
 SINGLE-FAMILY RESIDENTIAL STRUCTURE IS REMOVED AND
 REPLACED ON A BUILDING THAT IS LOCATED IN THE
 WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE
 OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR
 FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT
 PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR
 PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE:
 (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS
 REQUIRED BY SECTION 706.8.1.
 (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION
 SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN
 THE COST OF REROOFING.
 EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES
 PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT
 REQUIRED TO COMPLY WITH THIS SECTION.
  
 3- NEW FLAT ROOF NOA 15-0622.21 AND ENGINEER RAS 117
 CALCULATIONS SUBMITTED ARE OK. NEED TO PROVIDE TWO
 COPIES OF ENGINEER CALCULATIONS WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 WHEN ENGINEER IS SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
  
 NEW COMMENTS:
 4- NEW ROOF TILE PRODUCT APPROVAL WAS SUBMITTED. ONLY
 THE COVER PAGES OF FLORIDA PRODUCT APPROVAL FL7849-R11
 WAS SUBMITTED. NEED TO PROVIDE COMPLETE INSTALLATION
 INSTRUCTIONS FOR SPECIFIC ROOF TILE TO BE INSTALLED AND
 PROVIDE TWO COPIES.
 FAC 61G20-3.001.
  
 5- NEW ROOF TILE ADHESIVE PRODUCT APPROVAL WAS
 SUBMITTED. ONLY THE COVER PAGES OF FLORIDA PRODUCT
 APPROVAL FL6332-R8 WAS SUBMITTED. NEED TO PROVIDE
 COMPLETE INSTALLATION INSTRUCTIONS AND CLEARLY
 SPECIFY/MARK ADHESIVE PADDY SIZE AND RIDGE MATERIAL ON
 PAGES 3 AND 4 OF INSTALLATION INSTRUCTIONS. PROVIDE 2
 COPIES.
 FAC 61G20-3.001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-02 Cont ID  
Sent By jgomez Date 2018-07-02 Time 14:02 Rev Time 0.00
Received By jgomez Date 2018-07-02 Time 13:32 Sent To  
Notes
2018-07-02 14:15:24BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- IT LOOKS LIKE THE HOUSE WAS DESIGNED FOR SHINGLES AS
 A ROOF COVERING. PROPOSED ROOFING MATERIAL IS CONCRETE
 TILES. PROVIDE ENGINEERING ANALYSIS SHOWING THAT THE
 EXISTING STRUCTURE IA CAPABLE OF SUPPORTING THE
 ADDITIONAL LOAD. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2- HOUSE VALUE IS MORE THAN $300.000. NEED TO COMPLY
 WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED BY SEC.
 706.8 FBC-EXISTING-BUILDING.
  
 SEC. 706.8:
 WHEN A ROOF COVERING ON AN EXISTING SITE-BUILT
 SINGLE-FAMILY RESIDENTIAL STRUCTURE IS REMOVED AND
 REPLACED ON A BUILDING THAT IS LOCATED IN THE
 WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE
 OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR
 FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT
 PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR
 PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE:
 (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS
 REQUIRED BY SECTION 706.8.1.
 (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION
 SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN
 THE COST OF REROOFING.
 EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES
 PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT
 REQUIRED TO COMPLY WITH THIS SECTION.
  
 3- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R4
 SUBMITTED:
 A) SELECTED ASSEMBLY ON PAGE 8 OF 14 CAN NOT BE USED.
 ROOF ZONE #3 IS N/A. NEED ASSEMBLY THAT PROVIDE
 FASTENING FOR ALL ROOF ZONES. SEC. 1609.1 FBC
  
 B) PRODUCT APPROVAL SUBMITTED IS INCOMPLETE. PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO
 INFORMATION SUBMITTED.
 FAC 61G20-3.001.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-10-29 Cont ID  
Sent By jgomez Date 2018-10-29 Time 10:13 Rev Time 0.00
Received By jgomez Date 2018-10-29 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-10-22 Cont ID  
Sent By jgomez Date 2018-10-22 Time 15:35 Rev Time 0.00
Received By jgomez Date 2018-10-15 Time 13:45 Sent To I
Notes
2018-10-16 13:45:40RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-03 Cont ID  
Sent By jgomez Date 2018-10-03 Time 14:56 Rev Time 0.00
Received By jgomez Date 2018-10-03 Time 12:23 Sent To I
Notes
2018-10-03 12:24:17E-MAIL FROM GERI SHUBERT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-01 Cont ID  
Sent By jgomez Date 2018-08-01 Time 11:47 Rev Time 0.00
Received By jgomez Date 2018-08-01 Time 10:31 Sent To  
Notes
2018-08-01 10:31:49RECEIVED -MAIL FROM CONTRACTOR.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-02 Cont ID  
Sent By jgomez Date 2018-07-02 Time 14:48 Rev Time 0.00
Received By jgomez Date 2018-06-29 Time 13:08 Sent To I
Notes
2018-06-29 13:08:50GIVEN TO JGOMEZ