Plan Review Details - Permit 18061451
Plan Review Stops For Permit 18061451
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-31 Cont ID  
Sent By scaldero Date 2018-07-31 Time 13:58 Rev Time 0.00
Received By scaldero Date 2018-07-31 Time 13:58 Sent To M
Notes
2018-07-31 13:58:35SEE PREVIOUS REVIEW NOTES BY P. LEDUC ON 7/11/18.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By GJT Date 2018-07-11 Time   Rev Time 0.00
Received By pleduc Date 2018-07-03 Time 13:42 Sent To M
Notes
2018-07-11 17:01:54PASSED WITH THE FOLLOWING PROVISO:
 1. NOZZLE COVERAGE MUST COMPLY WITH NFPA 96
 2. ALL ELECTRICAL UNDERNEATH HOOD MUST "DROP OUT" WITH
 ACTIVATION OF SYSTEM
 3. SUPPLY CLASS K EXTINQUISHER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-04 Cont ID  
Sent By hmoser Date 2018-08-04 Time 07:49 Rev Time 0.00
Received By hmoser Date 2018-07-27 Time 11:33 Sent To  
Notes
2018-07-30 11:33:31RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-07-19 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-29 Time 15:00 Sent To  
Notes
2018-07-02 15:00:15ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-04 Cont ID  
Sent By hmoser Date 2018-08-04 Time 07:49 Rev Time 0.00
Received By hmoser Date 2018-08-04 Time 07:35 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-19 Cont ID  
Sent By ccole Date 2018-07-19 Time 09:14 Rev Time 0.00
Received By ccole Date 2018-07-19 Time 09:14 Sent To I
Notes
2018-07-19 09:26:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18061451
 7/19/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COMPLETE FIRE SUPPRESSION LAYOUT DRAWINGS
 THAT INCLUDES THE FOLLOWING DETAILS AND NOTES:
  
 A) UL LISTING AND CODE COMPLIANCE DATA FOR THE SYSTEMS
  
 B) PIPING RUNS, PIPE SIZES, TYPES OF PIPING.
  
 C) LOCATIONS OF ANSUL TANKS AND TANK SIZES.
  
 D) LOCATIONS AND TYPES OF SUPPRESSION NOZZLES AND
 POINTS ASSOCIATED WITH EACH, AND TOTAL POINTS ALLOWED
 AND TOTAL USED.
  
 E) LOCATION OF GAS VALVE.
  
 F) LOCATION OF MANUAL PULL STATION
  
 G) SEQUENCE OF OPERATION
  
 2) THE SUBMITTED PLAN WAS NOT SIGNED BY THE DESIGNER.
 PLEASE NOTE THAT ALL PLANS MUST BEAR THE SIGNATURE OF
 THE FL. LICENSED DESIGN PROFESSIONAL OR CONTRACTOR
 RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 WPB.
  
 3) THE $3500.00 VALUE FOR THE PROPOSED FIRE SUPPRESSION
 SYSTEMS IS A LOW VALUE FOR THE SYSTEMS. PROVIDE A
 CONTRACT AND/OR DETAILED ESTIMATES INVOICES TO VERIFY
 THE TOTAL COST WHICH SHALL INCLUDE LABOR, MATERIALS,
 EQUIPMENT, DESIGN FEES, OVERHEAD AND PROFIT- SECTION
 109.3 WPB. PLEASE NOTE THAT FIRE SUPPRESSION SYSTEMS
 EXCEEDING AT TOTAL VALUE OVER $5000.00 SHALL HAVE
 CONSTRUCTION DOCUMENTS PREPARED BY, OR UNDER THE
 DIRECTION OF AN ENGINEER REGISTERED UNDER CHAPTER 471,
 FLORIDA STATUTES- SECTION 105.3.1.2(4) WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  