Plan Review Details - Permit 18061434
Plan Review Stops For Permit 18061434
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-23 Cont ID  
Sent By dbattles Date 2019-03-23 Time 09:05 Rev Time 0.00
Received By dbattles Date 2019-03-23 Time 09:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-03 Cont ID  
Sent By dbattles Date 2018-08-03 Time 08:06 Rev Time 0.00
Received By dbattles Date 2018-08-02 Time 09:32 Sent To  
Notes
2018-08-03 08:08:13****CORRECTIONS****
 W.P.B. PERMIT: 18061434
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.3.5.3] PROVIDE SEDIMENT CONTROL PLAN TO
 KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT
 PROPERTIES AND STORM DRAINS.
  
 2. [FBC R403.1.7.3] FOUNDATION ELEVATION. ON GRADED
 SITES, THE TOP OF ANY EXTERIOR FOUNDATION SHALL EXTEND
 ABOVE THE ELEVATION OF THE STREET GUTTER AT POINT OF
 DISCHARGE OR THE INLET OF AN APPROVED DRAINAGE DEVICE A
 MINIMUM OF 12 INCHES (305 MM) PLUS 2 PERCENT. ALTERNATE
 ELEVATIONS ARE PERMITTED SUBJECT TO THE APPROVAL OF THE
 BUILDING OFFICIAL, PROVIDED IT CAN BE DEMONSTRATED THAT
 REQUIRED DRAINAGE TO THE POINT OF DISCHARGE AND AWAY
 FROM THE STRUCTURE IS PROVIDED AT ALL LOCATIONS ON THE
 SITE.
  
 3. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN. WATER IS TO
 BE MANAGED ON SITE AND IS NOT TO DRAIN INTO ADJACENT
 PROPERTIES.
  
 4. [FBC R401.4]PROVIDE SOIL REPORT.-NOT REQUIRED FOR
 THIS PROJECT DB-10-24-18
  
 5. [FBC R2319.17.2.1.1]PREFABRICATED WOOD TRUSSES SHALL
 BE DESIGNED BY A REGISTERED ENGINEER.
  
 6. [FBC 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS, OR
 INDICATE THAT THE SUBMITTAL WILL BE DEFERRED. DEFERRED
 SUBMITTALS TO BE REVIEWED PRIOR TO INSTALLATION.
  
 7. ARE YOU ISOLATING THE FRONT AND REAR PATIO FROM THE
 MAIN HOUSE WITH ICYNENE? WHAT WILL BE THE THERMAL
 BARRIER, 1/2 DRYWALL? SHOW ON PLANS HOW INSULATION
 FILLS FROM ROOF DECK TO BEAM BELOW AND WHAT THE
 INSULATION ATTACHES TO. ALSO, SEE FOLLOWING COMMENT
 ABOUT ATTIC ACCESS.
  
 8. [FBC R807]BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO
 ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES OR
 GREATER OVER AN AREA OF NOT LESS THAN 30 SQUARE FEET.
  
 9. WHAT IS HAPPENING BETWEEN THE HOUSE AND GARAGE WITH
 THE THERMAL ENVELOPE? PLANS SHOW ICYNENE AT THE GARAGE
 ROOF AND INSULATION AT WALL IN BETWEEN HOUSE AND
 GARAGE. WHAT HAPPENS AT GARAGE CEILING AND IN BETWEEN
 GARAGE/HOUSE FROM ROOF DECK TO BEAM BELOW?
  
 10. PLEASE RE-PRINT THE FOLLOWING PRODUCT APPROVALS FOR
 THE DRAWING PORTION THAT SHOULD BE PRINTED IN LANDSCAPE
 FORMAT. MUCH OF THE DATA, INCLUDING DESIGN
 PRESSURES/ATTACHMENT, IS CUT OFF.
 18-0503.06, 18-0529.03, 17-1212.13, 17-1212.22 AND
 17-1212.21
  
 11. PROVIDE PRODUCT APPROVAL FOR THE ATTACHMENT OF
 CEMENT ROOF TILE, OR INDICATE THAT IT WILL BE DEFFERED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-08 Cont ID  
Sent By ppetty Date 2019-04-08 Time 12:51 Rev Time 0.00
Received By ppetty Date 2019-04-08 Time 12:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-27 Cont ID  
Sent By jpearson Date 2018-07-27 Time 08:01 Rev Time 0.00
Received By jpearson Date 2018-07-27 Time 07:06 Sent To  
Notes
2018-07-27 08:01:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE 13 STATES THAT 50% OF LIGHTING SHALL BE HIGH
 EFFICACY. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT
 OF THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES
 SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT
 OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 2. NOTE 21 NEEDS TO BE CORRECTED. FIRST ITEM, ALL
 RECEPTACLES SHOULD BE TAMPER RESISTANT IF THEY ARE
 INSTALLED PER NEC 210.52 OR NOT,BASED ON NEC 406.11.
 SECOND ITEM IS THE AFCI NOTE. THIS MENTIONS RECEPTACLES
 ONLY, THE SAME FOR THE BLOCK NOTE ON THE PLAN
 DISCUSSING LAUNDRY AREAS. ALL BRANCH CIRCUITS THAT
 SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902, E4002.14
 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 4. PANEL SCHEDULE SHOWS NUMBER 8 WIRE ON 50 AMP BREAKER
 FOR THE CU'S, AND NUMBER 6 WIRE ON 60 AMP BREAKER FOR
 THE AHU'S. ROMEX WIRE, WHICH IS TYPICAL IN RESIDENTIAL
 WIRING, IS NOT RATED FOR THIS AMPERAGE, RESPECTIVE.
 PROVIDE CORRECTION. NEC 334.80; FBC RE E3705.4.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2019-03-27 Cont ID  
Sent By thunt Date 2019-03-27 Time 17:11 Rev Time 0.00
Received By thunt Date 2019-03-27 Time 17:11 Sent To  
Notes
2019-03-27 17:11:36GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BEIS
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE
 ENTIRE SCOPE OF GAS WORK TO BE DONE. AT THIS TIME. WPB
 AMEND. TO FBC SEC. 107.2.1.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-08-15 Cont ID  
Sent By lcrespo Date 2018-08-15 Time 17:19 Rev Time 0.00
Received By lcrespo Date 2018-08-15 Time 17:19 Sent To  
Notes
2018-08-15 17:19:43GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. AT
 THIS TIME. WPB AMENDMENTS TO FBC SEC. 107.2.1.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-09 Cont ID  
Sent By dbattles Date 2019-05-09 Time 15:30 Rev Time 0.00
Received By dbattles Date 2019-05-08 Time 07:59 Sent To  
Notes
2019-05-09 08:00:11ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-08 Cont ID  
Sent By ppetty Date 2019-04-08 Time 12:51 Rev Time 0.00
Received By ppetty Date 2019-03-15 Time 16:11 Sent To  
Notes
2019-03-18 16:11:21R28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-15 Cont ID  
Sent By lcrespo Date 2018-08-15 Time 17:45 Rev Time 0.00
Received By lcrespo Date 2018-06-29 Time 15:10 Sent To  
Notes
2018-07-02 15:10:28R27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-05-09 Cont ID  
Sent By dbattles Date 2019-05-09 Time 10:57 Rev Time 0.00
Received By dbattles Date 2019-05-09 Time 10:57 Sent To  
Notes
2019-05-09 10:59:37MU-2019-011872-0000
 RECEIVED RECIEPT OF PAYMENT-OK
 STAMP ON PLANS-OK

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-03 Cont ID  
Sent By dbattles Date 2018-08-03 Time 08:10 Rev Time 0.00
Received By dbattles Date 2018-08-03 Time 08:10 Sent To  
Notes
2018-08-03 08:14:37[FBC 109] PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE
 OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-04-06 Cont ID  
Sent By cmontell Date 2019-04-06 Time 07:01 Rev Time 0.00
Received By cmontell Date 2019-04-06 Time 07:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-29 Cont ID  
Sent By hmoser Date 2018-08-29 Time 14:42 Rev Time 0.00
Received By hmoser Date 2018-08-29 Time 13:33 Sent To  
Notes
2018-08-29 14:42:20PASS PROVISO
 1) REFER TO SECTION R403.3.6 AIR HANDLING UNITS
 2017 FLORIDA ENERGY CODE.
 2) REFER TO SECTION R1602.3 BALANCED RETURN AIR
 NOTE # 1 RESIDENTIAL CODE 2017
 3) PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS
 ON KITCHEN HOOD M1503.4 MAKE UP AIR REQUIRED.
 2017 RESIDENTIAL CODE AT FIRST INSPECTION.
 4) PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS
 ON GAS GRILL AT FIRST INSPECTION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-04 Cont ID  
Sent By hmoser Date 2018-08-04 Time 08:26 Rev Time 0.00
Received By hmoser Date 2018-08-04 Time 07:56 Sent To  
Notes
2018-08-04 08:25:55DENIED
 NO AIR CONDITIONING PLAN SUBMITTED HM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-27 Cont ID  
Sent By thunt Date 2019-03-27 Time 17:10 Rev Time 0.00
Received By thunt Date 2019-03-27 Time 17:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-15 Cont ID  
Sent By lcrespo Date 2018-08-15 Time 17:44 Rev Time 0.00
Received By lcrespo Date 2018-08-15 Time 17:44 Sent To  
Notes
2018-08-15 17:45:0908/15/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON ISOMETRIC DRAWING WATER CLOSET IS NOT VENTED NEXT
 TO LAUNDRY ROOM IN PAGE S-1, IT MAY BE VENTED BY
 LAUNDRY ROOM. IN MASTER NEEDS TO BE VENTED BETWEEN
 WATER CLOSET AND SHOWER. 2017 FBC R3101.2.1 VENTING
 REQUIRED. EVERY TRAP AND TRAPPED FIXTURE SHALL BE
 VENTED IN ACCORDANCE WITH ONE OF THE VENTING METHODS.
 2. CLEAN OUT ARE NOT REQUIRED ON VERTICAL PIPE BUT ONLY
 IN HORIZONTAL BUILDING DRAIN.
  
 3. ROMAN TUB FAUCET WILL REQUIRE A THERMOSTATIC VALVE
 IN A REMOTE LOCATION OR A VALVE THAT HAS A BUILT IN
 DEVICE. 2017 FBC R2713.3 BATHTUB AND WHIRLPOOL BATHTUB
 VALVES.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-03-23 Cont ID  
Sent By dbattles Date 2019-03-23 Time 08:31 Rev Time 0.00
Received By dbattles Date 2019-03-23 Time 08:31 Sent To  
Notes
2019-03-23 08:37:11NOA 17-0822.13 REVIEWED FOR TILE ROOF.
 PROVISO:
 PROVIDE ROOF TILE ATTACHMENT TO MEET NOA 17-0822.13
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-08-03 Cont ID  
Sent By dbattles Date 2018-08-03 Time 08:08 Rev Time 0.00
Received By dbattles Date 2018-08-03 Time 08:08 Sent To  
Notes
2018-08-03 08:10:23NEED PRODUCT APPROVAL FOR CEMENT TILE ATTACHMENT FOR
 THE CEMENT TILE SUBMITTED.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-04-11 Cont ID  
Sent By awooten Date 2019-04-11 Time   Rev Time 0.00
Received By awooten Date 2019-04-11 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-04-05 Cont ID  
Sent By awooten Date 2019-04-05 Time   Rev Time 0.00
Received By awooten Date 2019-04-05 Time   Sent To  
Notes
2019-04-05 13:24:20PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT.
  
 SHOWING THE FOLLOWING:
  
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 -GROSS LOT SQUARE FOOTAGE MINUS
 -BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 -OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 -ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 -ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-09 Cont ID  
Sent By AW Date 2018-07-09 Time 15:13 Rev Time 0.00
Received By awooten Date 2018-07-09 Time 12:28 Sent To  
Notes
2018-07-09 15:13:20**********************ZONING REVIEW
 FAILED****************************
  
 DRIVEWAYS, FENCES/WALLS AND POOLS REQUIRE A SEPARATE
 PERMIT.
  
 DIMENSION THE SETBACKS FOR ALL MECHANICAL EQUIPMENT.
 MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK. WINDOW
 AIR-CONDITIONING UNITS MAY NOT PROJECT MORE THAN 18
 INCHES INTO A REQUIRED SIDE SETBACK.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT.
  
 SHOWING THE FOLLOWING:
  
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 -GROSS LOT SQUARE FOOTAGE MINUS
 -BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 -OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 -ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 -ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  