Plan Review Details - Permit 18061244
Plan Review Stops For Permit 18061244
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-07-02 Cont ID  
Sent By scaldero Date 2018-07-02 Time 11:52 Rev Time 0.00
Received By scaldero Date 2018-07-02 Time 11:52 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-08-13 Time   Rev Time 0.00
Received By cpuell Date 2018-08-03 Time 11:54 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-07-19 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-26 Time 14:29 Sent To  
Notes
2018-06-27 14:30:06ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-08-15 Cont ID  
Sent By ccole Date 2018-08-15 Time 10:08 Rev Time 0.00
Received By ccole Date 2018-08-15 Time 10:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-08-13 Cont ID  
Sent By ccole Date 2018-08-13 Time 12:25 Rev Time 0.00
Received By ccole Date 2018-08-13 Time 12:25 Sent To I
Notes
2018-08-13 12:33:441ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18061244
 8/13/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REQUESTED NOA'S FOR THE FANS WERE NOT SUBMITTED-
 PLEASE PROVIDE.
  
 2) THE SUBMITTED AC SIZING CALCULATIONS DO NOT PROVIDE
 THE BTUH HEAT LOAD FROM THE MAKEUP AIR TO VERIFY
 COMPLIANCE WITH SECTION 508.1.1 (SEE REPRINTED COMMENT
 #3 BELOW), BUT THE CALCULATIONS DO INDICATE THAT 1794
 CFMS OF COOLING IS REQUIRED FOR THE KITCHEN. PLEASE
 NOTE THAT THE MAIN SET OF PLANS FOR THE PROJECT
 SUBMITTED UNDER PERMIT #18010561 SHOW ONLY 1000 CFMS OF
 COOLING PROVIDED IN THE KITCHEN, WHICH IS INADEQUATE
 PER THE CALCULATIONS.
  
 3) REFER TO SECTION 508.1.1 FBC M MAKEUP AIR
 TEMPERATURE, AND INDICATE HOW COMPLIANCE IS BEING MET.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-18 Cont ID  
Sent By ccole Date 2018-07-18 Time 17:32 Rev Time 0.00
Received By ccole Date 2018-07-18 Time 17:32 Sent To I
Notes
2018-07-19 08:44:071ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18061244
 7/19/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET #2: PLEASE INDICATE WHICH UL LISTED GREASE
 DUCT WILL BE USED IN COMPLIANCE WITH SECTIONS 506.3.1.1
 EXCEPTION, AND 506.3.11.3 FBC M.
  
 2) SUBMIT THE NOA'S FOR THE ROOF FANS, AND PROVIDE
 ENGINEERED DETAILS ON THE PLAN- SECTION 301.15 FBC M.
  
 3) REFER TO SECTION 508.1.1 FBC M MAKEUP AIR
 TEMPERATURE, AND INDICATE HOW COMPLIANCE IS BEING MET.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  