Plan Review Details - Permit 18061189
Plan Review Stops For Permit 18061189
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By shill Date 2018-08-21 Time 11:36 Rev Time 0.00
Received By shill Date 2018-08-21 Time 11:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 19:03 Rev Time 0.00
Received By shill Date 2018-08-11 Time 19:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-01 Cont ID  
Sent By skennedy Date 2018-09-01 Time 14:18 Rev Time 0.00
Received By skennedy Date 2018-09-01 Time 14:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-06 Cont ID  
Sent By jpearson Date 2018-08-06 Time 08:43 Rev Time 0.00
Received By jpearson Date 2018-08-06 Time 08:43 Sent To  
Notes
2018-08-06 08:43:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. WPB FBC
 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-07-11 Cont ID  
Sent By scaldero Date 2018-07-11 Time 11:02 Rev Time 0.00
Received By scaldero Date 2018-07-11 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-01 Cont ID  
Sent By skennedy Date 2018-09-01 Time 14:25 Rev Time 0.00
Received By skennedy Date 2018-08-20 Time 09:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-13 Cont ID  
Sent By gjohnson Date 2018-08-13 Time 16:18 Rev Time 0.00
Received By gjohnson Date 2018-07-06 Time 08:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-29 Cont ID  
Sent By hmoser Date 2018-08-29 Time 11:37 Rev Time 0.00
Received By hmoser Date 2018-08-29 Time 11:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-26 Cont ID  
Sent By ccole Date 2018-07-26 Time 12:30 Rev Time 0.00
Received By ccole Date 2018-07-26 Time 12:30 Sent To  
Notes
2018-07-26 12:35:521ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18061189
 7/26/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1: SHOW THE LOCATIONS OF KEY NOTES #2 & 4
 ON THE FLOOR PLAN DRAWING.
  
 2) THE MECHANICAL PLANS SHALL BE ELECTRONICALLY SIGNED
 AND SEALED BY THE ENGINEER OF RECORD- SECTION
 61G15-23.005 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-09-01 Cont ID  
Sent By skennedy Date 2018-09-01 Time 14:25 Rev Time 0.00
Received By skennedy Date 2018-09-01 Time 14:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-13 Cont ID  
Sent By gjohnson Date 2018-08-13 Time 15:31 Rev Time 0.00
Received By gjohnson Date 2018-08-13 Time 14:42 Sent To  
Notes
2018-08-13 16:18:091ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE DIGITAL SIGNATURES ARE MISSING ON PLUMBING PAGES
 THEY SHALL COMPLY WITH FAC 61G15-23.003
  
 2. THE INSIDE WIDTH OF THE SHOWER IS SHOWN AT 3'-2" THE
 CODE REQUIRES 36" EXACT. PER FBC ACC 608.2.3
  
 3. IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB
 BARS SHALL BE PROVIDED ON THE BACK WALL AND THE SIDE
 WALL FARTHEST FROM THE COMPARTMENT ENTRY. GRAB BARS
 SHALL NOT BE PROVIDED ABOVE THE SEAT. GRAB BARS SHALL
 BE INSTALLED 6 INCHES (150 MM) MAXIMUM FROM ADJACENT
 WALLS. FBC ACC 608.3.3
  
 4. THE CLEAR FLOOR SPACE FOR LAV SHALL COMPLY WITH FBC
 ACC 606.2
  
 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. FBC ACC 604.7
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By shill Date 2018-08-21 Time 11:35 Rev Time 0.00
Received By shill Date 2018-08-21 Time 11:35 Sent To  
Notes
2018-08-21 11:36:14A, MEP SHEETS OK
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-08-06 Cont ID  
Sent By jpearson Date 2018-08-06 Time 13:08 Rev Time 0.00
Received By jpearson Date 2018-08-06 Time 13:08 Sent To  
Notes
2018-08-11 18:55:25SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 A SHEETS ARE OK
 MEP SHEETS ARE NOT DIGITALLY SIGNED & SEALED, FS471.
  
  
2018-08-06 13:08:58SEE ELECTRICAL REVIEW.