Plan Review Details - Permit 18061114
Plan Review Stops For Permit 18061114
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-07-20 Cont ID  
Sent By shill Date 2018-07-20 Time 12:00 Rev Time 0.00
Received By shill Date 2018-07-20 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-07-19 Cont ID  
Sent By shill Date 2018-07-19 Time 17:08 Rev Time 0.00
Received By shill Date 2018-07-19 Time 07:48 Sent To  
Notes
2018-07-19 17:09:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FBC B 1609
  
 1. THE PRODUCT APPROVAL DOES NOT HAVE PROVISION FOR
 ENHANCED FASTENING
 2. THE ENHANCED FASTENING LETTER FROM THE ENGINEER DOES
 NOT ADDRESS THE PANEL SEAM REQUIREMENT, WHICH AFFECTS
 UPLIFT
 3. ENHANCED FASTENING ENGINEERING IS FOR ZONES 2 AND 3
 PRESSURES (-64, -94.6); -74.9 AND -125.9 ARE REQUIRED
 4. IF THE BUILDING OFFICIAL ELECTS TO ALLOW FOR YOU TO
 UTILIZE ENHANCED FASTENING, HOW WILL YOU DESIGNATE THE
 DIFFERENT ZONES FOR THE INSPECTOR? THIS METHOD OF
 INSTALLATION IS TYPICALLY DONE ON FLAT DECKS BASE
 SHEET; THE BASE SHEET CAN BE MARKED/CHALK LINED. HOW
 WILL YOU ACCOMPLISH THIS ON THE METAL ROOF?
 5. ENGINEERING IS TO BE SIGNED, SEALED, DATED
 ORIGINALS. WE SUGGEST THAT, IF YOU USE AN ENGINEER WHO
 HAS A DIGITAL SEAL, YOU SUBMIT THE APPLICATION
 DIGITALLY. FOR THIS ONE PERMIT, IF IT IS DETERMINED
 THAT ENGINEERING IS ACCEPTABLE (BY B.O.), YOU MAY EMAIL
 THE ORIGINAL TO ME AFTER THE BUILDING REVIEW IS PASSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-07 Cont ID  
Sent By shill Date 2018-07-07 Time 14:21 Rev Time 0.00
Received By shill Date 2018-07-07 Time 14:20 Sent To  
Notes
2018-07-07 14:37:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. SEE SHEET S4.00; THE ASSEMBLY SELECTED DOES NOT
 APPEARS TO MEET THE DESIGN PRESSURE REQUIREMENTS
 SPECIFIED BY THE ENGINEER, FBC B 1609.
  
 2. FBC 107, PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 2ND REVIEW, COMMENTS NOT ADDRESSED.
  
 SEE SHEET S4.00. ENGINEER SPECIFIES PRESSURES AS
 FOLLOWS:
  
 ZONE 1 -30.6
 ZONE 2 -64.0
 ZONE 3 -94.6
  
 THE METAL ROOF ASSEMBLY SELECTED HAS A DP LIMITATION OF
 -60 PSF.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-27 Cont ID  
Sent By shill Date 2018-06-27 Time 17:48 Rev Time 0.00
Received By shill Date 2018-06-27 Time 17:48 Sent To  
Notes
2018-06-27 17:50:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SEE SHEET S4.00; THE ASSEMBLY SELECTED DOES NOT
 APPEARS TO MEET THE DESIGN PRESSURE REQUIREMENTS
 SPECIFIED BY THE ENGINEER, FBC B 1609.
  
 2. FBC 107, PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-19 Cont ID  
Sent By shill Date 2018-07-19 Time 17:09 Rev Time 0.00
Received By shill Date 2018-07-17 Time 13:34 Sent To  
Notes
2018-07-18 13:34:38RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-07 Cont ID  
Sent By shill Date 2018-07-07 Time 14:37 Rev Time 0.00
Received By shill Date 2018-07-03 Time 15:52 Sent To  
Notes
2018-07-05 15:53:02RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-27 Cont ID  
Sent By shill Date 2018-06-27 Time 17:50 Rev Time 0.00
Received By shill Date 2018-06-22 Time 09:56 Sent To  
Notes
2018-06-26 09:56:41SHILL