Plan Review Details - Permit 18061060
Plan Review Stops For Permit 18061060
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-25 Cont ID  
Sent By rmcdouga Date 2018-09-25 Time 10:50 Rev Time 0.00
Received By rmcdouga Date 2018-09-25 Time 08:43 Sent To  
Notes
2018-09-25 10:49:42BUILDING PROVISO - APPROVED WITH EXCEPTIONS
  
 1) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS AND WINDOWS THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. FBC
 107.3.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-18 Cont ID  
Sent By rmcdouga Date 2018-07-18 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2018-07-18 Time 06:53 Sent To  
Notes
2018-07-18 09:12:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORMS THAT WERE SUBMITTED CONTAIN
 NUMEROUS ERRORS. THE BUILDING TYPE HAS USER. THE FORM
 SPECIFIES THIS AS NEW AND IT IS EXISTING. THIS DWELLING
 HAS A CRAWL SPACE AND THE FORM LISTS SLAB ON GRADE. THE
 PLANS SPECIFY AN UNVENTED ATTIC WITH SPRAY FOAM
 INSULATION AND THE FORM HAS A VENTED ATTIC WITH BLOWN
 INSULATION. THE PLANS SPECIFY A WHITE ASPHALT SHINGLE
 ROOF AND THE FORM LISTS A GRAVEL ROOF. PLEASE CORRELATE
 THE FORMS WITH THE PLANS. FBC 107.2.1
  
 2) SHOW COMPLIANCE WITH FBC-R408.1 VENTILATION. THE
 UNDER-FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR
 JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE
 OCCUPIED BY A BASEMENT) SHALL HAVE VENTILATION OPENINGS
 THROUGH FOUNDATION WALLS OR EXTERIOR WALLS. THE MINIMUM
 NET AREA OF VENTILATION OPENINGS SHALL BE NOT LESS THAN
 1 SQUARE FOOT FOR EACH 150 SQUARE FEET OF UNDER-FLOOR
 SPACE AREA, UNLESS THE GROUND SURFACE IS COVERED BY A
 CLASS 1 VAPOR RETARDER MATERIAL. WHERE A CLASS 1 VAPOR
 RETARDER MATERIAL IS USED, THE MINIMUM NET AREA OF
 VENTILATION OPENINGS SHALL BE NOT LESS THAN 1 SQUARE
 FOOT FOR EACH 1,500 SQUARE FEET OF UNDER-FLOOR SPACE
 AREA. ONE SUCH VENTILATING OPENING SHALL BE WITHIN 3
 FEET OF EACH CORNER OF THE BUILDING.
  
 3) SHOW COMPLIANCE WITH FBC-R408.4 ACCESS. ACCESS SHALL
 BE PROVIDED TO ALL UNDER-FLOOR SPACES. ACCESS OPENINGS
 THROUGH THE FLOOR SHALL BE A MINIMUM OF 18 INCHES BY 24
 INCHES. OPENINGS THROUGH A PERIMETER WALL SHALL BE NOT
 LESS THAN 16 INCHES BY 24 INCHES. WHERE ANY PORTION OF
 THE THROUGH-WALL ACCESS IS BELOW GRADE, AN AREAWAY NOT
 LESS THAN 16 INCHES BY 24 INCHES SHALL BE PROVIDED. THE
 BOTTOM OF THE AREAWAY SHALL BE BELOW THE THRESHOLD OF
 THE ACCESS OPENING. THROUGH WALL ACCESS OPENINGS SHALL
 NOT BE LOCATED UNDER A DOOR TO THE RESIDENCE. SEE
 SECTION M1305.1.4 FOR ACCESS REQUIREMENTS WHERE
 MECHANICAL EQUIPMENT IS LOCATED UNDER FLOORS.
  
 4) SHOW COMPLIANCE WITH FBC-R318.7 INSPECTION FOR
 TERMITES. IN ORDER TO PROVIDE FOR INSPECTION FOR
 TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES.
  
 5) SHOW THAT THE NEW SLAB ON GRADE FOUNDATION FOR THE
 SHED COMPLIES WITH FBC-R404.1.6 HEIGHT ABOVE FINISHED
 GRADE. CONCRETE AND MASONRY FOUNDATION WALLS SHALL
 EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE
 FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM)
 WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES
 (152 MM) ELSEWHERE.
  
 6) SHOW COMPLIANCE WITH FBC-R803.2.3.1 SHEATHING
 FASTENINGS. WOOD STRUCTURAL PANEL SHEATHING SHALL BE
 FASTENED TO ROOF FRAMING WITH RSRS-01 (2 3/8" X 0.113")
 NAILS AT 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON
 CENTER AT INTERMEDIATE FRAMING, UNLESS ROOF DIAPHRAGM
 DESIGN REQUIRES A CLOSER SPACING. RSRS-01 IS RING SHANK
 ROOF SHEATHING NAIL MEETING THE SPECIFICATIONS IN ASTM
 F1667.
 WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, 0.42 < OR =
 G < 0.49 IS USED, SPACING OF RING-SHANK FASTENERS SHALL
 BE 4 INCHES ON CENTER IN NAILING ZONE 3 IN ACCORDANCE
 WITH FIGURE R803.2.3.1 WHERE VULT IS 165 MPH OR
 GREATER.
  
 7) UPDATE THE IMPACT GLAZING NOTES ON SHEET S-200 FROM
 THE 2014 TO THE 2017 FBC.
  
 8) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORT
 AND INSTALLATION INSTRUCTIONS FOR THE SPRAY FOAM
 INSULATION. FBC-R316
  
 9) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW(GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES.
  
 10) THE PERMIT VALUATION OF $167,000.00 ON THE
 APPLICATION IS LOW BASED ON THE SCOPE OF WORK AND HAS
 BEEN ADJUSTED TO $202,606.00. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-24 Cont ID  
Sent By jpearson Date 2018-09-24 Time 13:08 Rev Time 0.00
Received By jpearson Date 2018-09-24 Time 12:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-17 Cont ID  
Sent By jpearson Date 2018-07-17 Time 11:27 Rev Time 0.00
Received By jpearson Date 2018-07-17 Time 05:52 Sent To  
Notes
2018-07-17 11:27:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 2. NOTE 1 DETAILING AFCI PROTECTION IS NOT CODE
 COMPLIANT. PER CODE, ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. SOME AREAS REQUIRE GFCI AND AFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902.16
 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 5. ROOM 107 BATHROOM DOES NOT SHOW THE REQUIRED GFCI
 PROTECTED RECEPTACLE OUTLET WITHIN 3 FEET OF THE BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
 6. SHEET M-2 STATES THAT CU-3 REQUIRES A MINIMUM
 CIRCUIT AMPACITY OF 32 AMPS. PLAN SHOWS #10 WIRE
 FEEDING THIS UNIT. THE #10 ROMEX IS ONLY RATED FOR 30
 AMPS. PROVIDE CORRECTION. NEC 334.80; FBC RE E3705.4.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-09-25 Cont ID  
Sent By skennedy Date 2018-09-25 Time 16:10 Rev Time 0.00
Received By skennedy Date 2018-09-25 Time 16:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-08-06 Cont ID  
Sent By lcrespo Date 2018-08-06 Time 14:17 Rev Time 0.00
Received By lcrespo Date 2018-08-06 Time 14:17 Sent To  
Notes
2018-08-06 14:48:1608/06/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT TWO COPIES MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT
 (FIREPLACE) TO VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS
 RES. SEC. G2408.1.
 2. SUBMIT TWO COPIES OF DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE
 ROOF AND ANCHORING DETAILS OF THE GAS VENT FOR
 FIREPLACE PER 2017 FBC FUEL GAS SECS. 502 THRU 505 OR
 2017 FBC FUEL GAS RES. SECS. G2426 THRU G2429.1
 3. FIRE PLACE MANUFACTURES INSTALLATION INSTRUCTION
 SHALL BE ON SITE AT TIME OF INSTALLATION.
 4. KEY NOTES 7 AND 8 ON PAGE P-1 AT FIRE PLACE DO NOT
 HAVE ANY VERBIAGE FOR PLAN KEY NOTES, PLEASE ADD NOTES
 OR DELETE NUMBER ON PLANS. WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 5. THERE APPEARS TO BE A CARPORT WHERE THE TANKLESS GAS
 WATER HEATER IS GOING TO BE LOCATED THIS REQUIRES
 SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 6. PAGE P-1 HAS THE CARPORT LABEL AS A BEDROOM PLEASE
 CHANGE TO CARPORT, WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 7. SUBMIT TWO COPIES MANUFACTURER?S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION, WHERE APPLICABLE AND SHALL BE ON SITE,
 2017 FBC FUEL GAS RES. SEC. G2421.1.
 8. A ELECTRICAL OUT MAY BE REQUIRED FOR SOURCE OF
 IGNITION, WPB AMENDMENTS TO THE FBC SEC 105.1
 9. A SEPARATE GAS PERMIT SHALL BE REQUIRED, FBC WPB A
 107.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-09-24 Cont ID  
Sent By fmittner Date 2018-09-24 Time 11:02 Rev Time 0.00
Received By fmittner Date 2018-09-24 Time 11:02 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-07-19 Cont ID  
Sent By fmittner Date 2018-07-19 Time 10:50 Rev Time 0.00
Received By fmittner Date 2018-07-19 Time 10:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-25 Cont ID  
Sent By skennedy Date 2018-09-25 Time 16:10 Rev Time 0.00
Received By skennedy Date 2018-08-24 Time 13:59 Sent To  
Notes
2018-08-27 13:59:11R14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-06 Cont ID  
Sent By lcrespo Date 2018-08-06 Time 14:17 Rev Time 0.00
Received By lcrespo Date 2018-06-21 Time 16:01 Sent To  
Notes
2018-06-22 16:01:30R16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-07-18 Cont ID  
Sent By rmcdouga Date 2018-07-18 Time 06:53 Rev Time 0.00
Received By rmcdouga Date 2018-07-18 Time 06:53 Sent To  
Notes
2018-07-18 06:54:09NO ADDITIONAL HABITABLE SPACE IS BEING ADDED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-07-30 Cont ID  
Sent By cmontell Date 2018-07-30 Time 15:20 Rev Time 0.00
Received By cmontell Date 2018-07-30 Time 14:15 Sent To  
Notes
2018-07-30 15:20:59MAKEUP AIR MAY BE REQUIRED FOR KITCHEN EXHAUST HOOD

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-09-25 Cont ID  
Sent By skennedy Date 2018-09-25 Time 16:10 Rev Time 0.00
Received By skennedy Date 2018-09-25 Time 16:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-06 Cont ID  
Sent By lcrespo Date 2018-08-06 Time 14:17 Rev Time 0.00
Received By lcrespo Date 2018-08-06 Time 12:06 Sent To  
Notes
2018-08-06 14:49:2708/06/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS, PLEASE ADD TO PLAN
 KEY NET AS AN ITEM NUMBER. 2017 FBC SEC R2903.9.3
 FIXTURE VALVES AND ACCESS. ACCESSIBLE, SIGNIFIES ACCESS
 THAT REQUIRES THE REMOVAL OF AN ACCESS PANEL OR SIMILAR
 REMOVABLE OBSTRUCTION.
 2. SHOW HAMMER ARRESTORS ON ISOMETRIC. WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status N Date 2018-09-25 Cont ID  
Sent By skennedy Date 2018-09-25 Time 16:11 Rev Time 0.00
Received By skennedy Date 2018-09-25 Time 16:11 Sent To  
Notes
2018-09-25 16:11:42A RESIDENT INSPECTOR AGREEMENT WAS SUBMITTED BUT IS NOT
 REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-09-24 Cont ID  
Sent By fmittner Date 2018-09-24 Time 11:02 Rev Time 0.00
Received By fmittner Date 2018-09-24 Time 11:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-19 Cont ID  
Sent By fmittner Date 2018-07-19 Time 10:50 Rev Time 0.00
Received By fmittner Date 2018-07-19 Time 10:50 Sent To  
Notes
***NONE***