Plan Review Details - Permit 18061057
Plan Review Stops For Permit 18061057
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-25 Cont ID  
Sent By dbattles Date 2018-09-25 Time 09:11 Rev Time 0.00
Received By dbattles Date 2018-09-25 Time 09:11 Sent To  
Notes
2018-09-25 09:15:58PROVISO:
 RESPONSE LETTER STATED WINDOW AND DOOR PRODUCT
 APPROVALS REVIEWED AND ACCEPTED, BUT THE PRODUCT
 APPROVALS WERE NOT INCLUDED IN THE RE-SUBMITTAL.
 THESE PRODUCT APPROVALS ARE DEFERED.
 PROVIDE THE PRODUCT APPROVAL TO INSPECTOR PRIOR TO
 INSTALLATION OF WINDOWS AND DOORS.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-20 Cont ID  
Sent By dbattles Date 2018-07-20 Time 12:38 Rev Time 0.00
Received By dbattles Date 2018-07-20 Time 12:38 Sent To  
Notes
2018-07-20 12:38:51****CORRECTIONS****
 W.P.B. PERMIT: 18061057
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.3.5.3]ADD THE CONSTRUCTION TYPE TO PROJECT
 DATA.
  
 2. [FBC ENERGY R401.2]THE ENERGY CALCULATIONS PROVIDED
 DIDN'T ACCOUNT FOR FLOOR INSULATION AT UNDER FLOOR
 CRAWL SPACE. PLEASE UPDATE AND SUPPLY R-VALUE. PAGE 2
 OF 4 CHANGE FLOOR TYPE FROM SLAB ON GRADE, AND CHECK
 ATTIC IT SAYS BLOWN IN INSULATION.
 [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
  
 3. [FBC R107.2.5]PROVIDE DEMOLITION NOTES TO REMOVE THE
 EXISTING FOUNDATION AND OTHER STRUCTURAL ELEMENTS.
 PROVIDE SHORING/JACKING NOTES IF APPLICABLE TO EXPLAIN
 HOW TO THE EXISTING STRUCTURE WILL BE SUPPORTED WHILE
 THE NEW FOUNDATION IS BEING CONSTRUCTED.
 SEPARATE PERMIT FOR DEMO WILL BE NEEDED.
  
 [FBC 107.3.4.1]DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR
 REVIEW, AND THEN FORWARED TO THE BUILDING
 OFFICIAL INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN. THE DEFERRED SUBMITTAL ITEMS
 SHALL NOT BE INSTALLED UNTIL THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 4. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL, DOORS, TRANSOMS, SLIDERS AND
 SOLAR TUBES, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFFERED.
  
 5. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED.
  
 6. [FBC R408.4]PROVIDE ACCESS TO THE UNDER FLOOR SPACE
 18X24 MINIMUM.
  
 7. [FBC 107.3.5.3]PROVIDE DETAIL OF HOW UNDER FLOOR
 VENTS WORK WITH THE FOUNDATION.
  
 08. [FBC R408.2]SUPPLY CALCULATION TO SHOW HOW MUCH
 VENTILATION IS NEEDED UNDER FLOOR SPACE AND HOW MUCH IS
 SUPPLIED.
  
 09. [FBC R507]WHAT CONNECTORS ARE BEING USED TO CONNECT
 THE REAR WOOD DECK TO THE EXISTING STRUCTURE?
  
 10. [FBC 107.3.5.3]UPDATE CODE REFERENCE TO CURRENT
 CODE ON SHEET S-200 WIND LOAD SCHEDULE.
  
 11. [FBC 107.3.5.3]ADJUST DETAILS ON S-300 TO REFLECT
 THAT THE STRUCTURE IS CURRENTLY STUCCO(NOT WOOD
 SIDING). SHOW STUCCO DETAILS AT FOUNDATION AND OTHER
 AREAS OF ALTERATION.
  
 12. [FBC R302.11]VERIFY AND UPDATE FIREBLOCKING IF
 APPLICABLE TO BALLOON FRAMING. IS FIREBLOCKING BEING
 PROVIDED BETWEEN FLOORS (SHEET 1/A200)?
  
 13. [FBC 107.3.5.3]ARE OUTLOOKERS GOING AT SHEAR WALL
 AND OTHER AREAS? PLEASE SHOW HOW THESE WILL LOOK ON THE
 ELEVATIONS.
  
 14. [FBC R3-1.2(6)]PROVIDE WIND DIAGRAM THAT MATCHES
 THE ROOF CONDITION OF THIS HOUSE(FLAT ROOF WITH
 PARAPET).
  
 15. [FBC R803.2.3.1]UPDATE SHEATHING FASTENING ON S-300
 & S-301.
 SHEATHING NAILS TO BE RING SHANK RSRS01(2 3/8 X 0.113)
  
 16. [FBC R903.4]ROOF DRAINAGE AND SCUPPERS. PROVIDE
 ROOF DRAINAGE CALCULATION AND SHOE SCUPPER LOCATIONS
 AND SIZING. IF SCUPPERS ARE TO BE ON EAST SIDE PARAPET,
 SHOW HOW THE WATER WILL BE MANAGED ON THE SITE DRAINAGE
 PLAN.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-24 Cont ID  
Sent By jpearson Date 2018-09-24 Time 13:28 Rev Time 0.00
Received By jpearson Date 2018-09-24 Time 13:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By jpearson Date 2018-07-23 Time 09:04 Rev Time 0.00
Received By jpearson Date 2018-07-23 Time 07:36 Sent To  
Notes
2018-07-23 09:04:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 2. NOTE 1 DETAILING AFCI PROTECTION IS NOT CODE
 COMPLIANT. PER CODE, ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. SOME AREAS REQUIRE GFCI AND AFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902.16
 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 5. A GFCI PROTECTED RECEPTACLE OUTLET IS REQUIRED ON
 THE KITCHEN PENINSULA. PROVIDE CORRECTION. NEC
 210.52(C)(3); FBC RE E3901.4.3
 6. DINING ROOM LIGHT IS SHOWN ON THE SAME CIRCUIT AS
 THE DINING ROOM RECEPTACLE OUTLETS, WHICH IS A CODE
 VIOLATION. PROVIDE CORRECTION. NEC 210.52(B)(2); FBC RE
 E3703.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-09-25 Cont ID  
Sent By skennedy Date 2018-09-25 Time 15:02 Rev Time 0.00
Received By skennedy Date 2018-09-25 Time 15:02 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-08-02 Cont ID  
Sent By lcrespo Date 2018-08-02 Time 17:58 Rev Time 0.00
Received By lcrespo Date 2018-08-02 Time 17:58 Sent To  
Notes
2018-08-02 18:20:0008/02/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT(TANKLESS) TO VERIFY COMPLIANCE WITH 2017 FBC
 FUEL GAS SEC.305.1 OR 2017 FBC FUEL GAS RES. SEC.
 G2408.1.
 2. PLEASE SHOW THE LOCATION OF THE TANKLESS WATER
 HEATER AND THE LOCATION AND DISTANCE OF ANY OPERABLE
 DOORS OR WINDOWS IN RELATION TO THE WATER HEATER. THE
 LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 3. SUBMIT TWO COPIES MANUFACTURER'S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
 4. A ELECTRICAL OUT MAY BE REQUIRED FOR SOURCE OF
 IGNITION, WPB AMENDMENTS TO THE FBC SEC 105.1
 5. A SEPARATE GAS PERMIT SHALL BE REQUIRED, FBC WPB A
 107.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-09-24 Cont ID  
Sent By fmittner Date 2018-09-24 Time 10:45 Rev Time 0.00
Received By fmittner Date 2018-09-24 Time 10:45 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-07-05 Cont ID  
Sent By fmittner Date 2018-07-05 Time 11:35 Rev Time 0.00
Received By fmittner Date 2018-07-05 Time 11:35 Sent To  
Notes
2018-07-05 11:35:52DOES NOT REFLECT BOARD CONDITION FOR WINDOWS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-25 Cont ID  
Sent By skennedy Date 2018-09-25 Time 15:02 Rev Time 0.00
Received By skennedy Date 2018-08-24 Time 13:31 Sent To  
Notes
2018-08-27 13:31:52R09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-02 Cont ID  
Sent By lcrespo Date 2018-08-02 Time 17:58 Rev Time 0.00
Received By lcrespo Date 2018-06-21 Time 15:47 Sent To  
Notes
2018-06-22 15:48:00R08

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-07-30 Cont ID  
Sent By cmontell Date 2018-07-30 Time 14:06 Rev Time 0.00
Received By cmontell Date 2018-07-30 Time 13:36 Sent To  
Notes
2018-07-30 14:05:54MAKEUP AIR MAY BE REQUIRED FOR KITCHEN EXHAUST HOOD

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-09-25 Cont ID  
Sent By skennedy Date 2018-09-25 Time 15:03 Rev Time 0.00
Received By skennedy Date 2018-09-25 Time 15:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-08-02 Cont ID  
Sent By lcrespo Date 2018-08-02 Time 17:57 Rev Time 0.00
Received By lcrespo Date 2018-08-02 Time 17:57 Sent To  
Notes
2018-08-02 18:00:2908/02/18 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/BACKFLOW)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-09-25 Cont ID  
Sent By dbattles Date 2018-09-25 Time 09:10 Rev Time 0.00
Received By dbattles Date 2018-09-25 Time 09:10 Sent To  
Notes
2018-09-25 09:11:20[RAS 117]PROVIDE ENGINEERING FOR ENHANCED NAILING AS
 STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS
 #5.7
  
 PRODUCT APPROVAL FOR SHINGLES WAS SUBMITTED, BUT THIS
 IS ALL FLAT ROOF.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status N Date 2018-09-25 Cont ID  
Sent By skennedy Date 2018-09-25 Time 15:22 Rev Time 0.00
Received By skennedy Date 2018-09-25 Time 15:22 Sent To  
Notes
2018-09-25 15:30:29A RESIDENT INSPECTOR AGREEMENT HAS BEEN SUPPLIED. I
 HAVE DISCUSSED THE INTENT WITH A REPRESENTATIVE OF THE
 APPLICANT AND I AM AWAITING A REPLY, HOWEVER IT IS NOT
 REQUIRED. .

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-05 Cont ID  
Sent By fmittner Date 2018-07-05 Time 11:36 Rev Time 0.00
Received By fmittner Date 2018-07-05 Time 11:36 Sent To  
Notes
***NONE***