2018-07-20 12:38:51 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18061057 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. [FBC 107.3.5.3]ADD THE CONSTRUCTION TYPE TO PROJECT |
| DATA. |
| |
| 2. [FBC ENERGY R401.2]THE ENERGY CALCULATIONS PROVIDED |
| DIDN'T ACCOUNT FOR FLOOR INSULATION AT UNDER FLOOR |
| CRAWL SPACE. PLEASE UPDATE AND SUPPLY R-VALUE. PAGE 2 |
| OF 4 CHANGE FLOOR TYPE FROM SLAB ON GRADE, AND CHECK |
| ATTIC IT SAYS BLOWN IN INSULATION. |
| [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES |
| REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH |
| THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD |
| INDEX AND SMOKE DEVELOPED INDEX. |
| |
| 3. [FBC R107.2.5]PROVIDE DEMOLITION NOTES TO REMOVE THE |
| EXISTING FOUNDATION AND OTHER STRUCTURAL ELEMENTS. |
| PROVIDE SHORING/JACKING NOTES IF APPLICABLE TO EXPLAIN |
| HOW TO THE EXISTING STRUCTURE WILL BE SUPPORTED WHILE |
| THE NEW FOUNDATION IS BEING CONSTRUCTED. |
| SEPARATE PERMIT FOR DEMO WILL BE NEEDED. |
| |
| [FBC 107.3.4.1]DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR |
| REVIEW, AND THEN FORWARED TO THE BUILDING |
| OFFICIAL INDICATING THAT THE DEFERRED SUBMITTAL |
| DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| CONFORMANCE TO THE DESIGN. THE DEFERRED SUBMITTAL ITEMS |
| SHALL NOT BE INSTALLED UNTIL THE DEFERRED SUBMITTAL |
| DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING OFFICIAL. |
| |
| 4. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR |
| WINDOWS, WINDOW MULL, DOORS, TRANSOMS, SLIDERS AND |
| SOLAR TUBES, OR INDICATE THAT YOU WOULD LIKE THEM |
| DEFFERED. |
| |
| 5. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR |
| ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED. |
| |
| 6. [FBC R408.4]PROVIDE ACCESS TO THE UNDER FLOOR SPACE |
| 18X24 MINIMUM. |
| |
| 7. [FBC 107.3.5.3]PROVIDE DETAIL OF HOW UNDER FLOOR |
| VENTS WORK WITH THE FOUNDATION. |
| |
| 08. [FBC R408.2]SUPPLY CALCULATION TO SHOW HOW MUCH |
| VENTILATION IS NEEDED UNDER FLOOR SPACE AND HOW MUCH IS |
| SUPPLIED. |
| |
| 09. [FBC R507]WHAT CONNECTORS ARE BEING USED TO CONNECT |
| THE REAR WOOD DECK TO THE EXISTING STRUCTURE? |
| |
| 10. [FBC 107.3.5.3]UPDATE CODE REFERENCE TO CURRENT |
| CODE ON SHEET S-200 WIND LOAD SCHEDULE. |
| |
| 11. [FBC 107.3.5.3]ADJUST DETAILS ON S-300 TO REFLECT |
| THAT THE STRUCTURE IS CURRENTLY STUCCO(NOT WOOD |
| SIDING). SHOW STUCCO DETAILS AT FOUNDATION AND OTHER |
| AREAS OF ALTERATION. |
| |
| 12. [FBC R302.11]VERIFY AND UPDATE FIREBLOCKING IF |
| APPLICABLE TO BALLOON FRAMING. IS FIREBLOCKING BEING |
| PROVIDED BETWEEN FLOORS (SHEET 1/A200)? |
| |
| 13. [FBC 107.3.5.3]ARE OUTLOOKERS GOING AT SHEAR WALL |
| AND OTHER AREAS? PLEASE SHOW HOW THESE WILL LOOK ON THE |
| ELEVATIONS. |
| |
| 14. [FBC R3-1.2(6)]PROVIDE WIND DIAGRAM THAT MATCHES |
| THE ROOF CONDITION OF THIS HOUSE(FLAT ROOF WITH |
| PARAPET). |
| |
| 15. [FBC R803.2.3.1]UPDATE SHEATHING FASTENING ON S-300 |
| & S-301. |
| SHEATHING NAILS TO BE RING SHANK RSRS01(2 3/8 X 0.113) |
| |
| 16. [FBC R903.4]ROOF DRAINAGE AND SCUPPERS. PROVIDE |
| ROOF DRAINAGE CALCULATION AND SHOE SCUPPER LOCATIONS |
| AND SIZING. IF SCUPPERS ARE TO BE ON EAST SIDE PARAPET, |
| SHOW HOW THE WATER WILL BE MANAGED ON THE SITE DRAINAGE |
| PLAN. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |