Plan Review Details - Permit 18060981
Plan Review Stops For Permit 18060981
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date   Cont ID  
Sent By sathomas Date 2018-08-27 Time 00:00 Rev Time 0.00
Received By   Date 2018-08-27 Time 00:00 Sent To I
Notes
2018-08-27 13:50:38SUBJECT TO FIELD INSPECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-06-28 Cont ID  
Sent By sathomas Date 2018-06-28 Time 00:00 Rev Time 0.00
Received By sathomas Date 2018-06-28 Time 00:00 Sent To  
Notes
2018-06-28 09:12:551. ENSURE HYDRAULIC CALCULATIONS MATCH AREA INDICATED
 ON THE PLANS.
 2. ENSURE SIDEWALL SPRAY PATTERNS ARE NOT OBSTRUCTED BY
 CEILING FAN INSTALLATION IN MAIN LIVING AREAS.
 3. REVIEW HYDRAULIC CALCULATIONS INFORMATION TO ENSURE
 ADEQUATE PRESSURE REQUIREMENTS.
 4. PROVIDE DATA SHEET FOR TYCO SPRINKLER HEAD 3331
 5. REVIEW UNITS B2-A ON ALL FLOORS AS IT APPEARS TO BE
 LACKING COVERAGE UNDER SOFFIT. TO BE VERIFIED IN THE
 FIELD.
  
 S. THOMAS
 561-8044728

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-27 Cont ID  
Sent By cpuell Date 2018-08-27 Time 16:59 Rev Time 0.00
Received By cpuell Date 2018-08-21 Time 15:38 Sent To  
Notes
2018-08-22 15:38:21RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-28 Cont ID  
Sent By cpuell Date 2018-06-28 Time 15:30 Rev Time 0.00
Received By cpuell Date 2018-06-20 Time 14:23 Sent To  
Notes
2018-06-21 14:23:15ROUTED TO FIRE INBOX