Plan Review Details - Permit 18060927
Plan Review Stops For Permit 18060927
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2018-08-20 Cont ID  
Sent By lcrespo Date 2018-08-20 Time 07:35 Rev Time 0.00
Received By lcrespo Date 2018-08-20 Time 07:35 Sent To  
Notes
2018-08-20 07:36:0508/20/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-07-28 Cont ID  
Sent By tklarge Date 2018-07-28 Time 08:06 Rev Time 0.00
Received By tklarge Date 2018-07-28 Time 07:43 Sent To I
Notes
2018-07-28 07:59:341) THIS RESUBMITTAL IS A CONVOLUTED MESS AND IN
 DISSARAY. THERE ARE TWO DIFFERENT GAS DRWAINGS,
 MULTIPLE COPIES OF ONE GAS DRAWING,ONLY ONE COPY OF
 ANOTHER, MULTIPLE COPIES OF RINNAI SPECS AND REGULATOR
 SPECS. NOTHING IS IN ORDER. THERE ARE MULTIPLE COPIES
 OF PERMIT APPLICATIONS, ETC. SOMEONE FROM THE
 CONTRACTOR'S OFFICE SHALL COME TO THE BUILDING DIVISION
 AND REMOVE ALL THE OLD PLANS AND ARRANGE THESE
 DOCUMENTS INTO TWO COMPLETE SETS OF PLANS FOR REVIEW.
 WPB AMEND. TO FBC SEC. 107.2.1, 107.1. I WILL NOT DO A
 REVIEW UNTIL THIS IS DONE.
 2) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 FOR THE LOW PRESSURE SYSTEM USED TO SIZE THE GAS SYSTEM
 OR PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND
 TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
 3) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
 4) ) SUBMIT LEGIBLE COPIES OF THE MANUFACTURER?S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. IDENTIFY ON THE SPECIFICATION SHEETS
 WHICH MODEL REGULATOR IS BEING INSTALLED AND THE
 ORIFICE SIZE TO ENSURE THE REGULATOR CAN ACCOMMODATE
 THE BTU LOAD THROUGH THE REGULATOR.2017 FGC SEC.410.1,
 2017 FBC-RES. SEC. G2421.1.
 5) THE ABANDONED POOL HEATER AND FIREPLACE LINES SHALL
 BE EQUIPPED WITH A SHUTOFF VALVE, PRESSURE REGULATOR, A
 NIPPLE AND A CAP. 2017 FBC-FUEL GAS SEC.404.15. THIS IS
 REQUIRED TO ENSURE THE GAS SYSTEM IS LEFT IN A SAFE
 CONDITION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-07-19 Cont ID  
Sent By thunt Date 2018-07-19 Time 15:21 Rev Time 0.00
Received By thunt Date 2018-07-19 Time 15:21 Sent To  
Notes
2018-07-19 15:30:5707/19/2018 2ND GAS REVIEW**DENIED**
  
 1) PLAN SUBMITTED SHALL NOT BE IN PENCIL AND SHALL BE
 OF PERMANENT SOURCE.107.3.5MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS
  
 2) EVEN WITH THE POOL HEATER AND FIRE PLACING BEING
 CAPPED THE GAS SUPPLY TO THEM COULD AT SOME TIME BE
 RECONNECTED AND SHALL BE INCLUDED ON YOUR PLAN AND SHOW
 AS A BTU LOAD. FBC FUEL AND GAS 401.8, 402.1
  
 3) SHOW WHERE EXISTING HEATER IS LOCATED ON FLOOR PLAN.
 FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By thunt Date 2018-06-29 Time 14:23 Rev Time 0.00
Received By thunt Date 2018-06-29 Time 14:23 Sent To  
Notes
2018-06-29 14:30:1106/29/2018 1ST GAS REVIEW**DENIED**
  
 1) CITY RECORDS SHOW A POOL HEATER INSTALLED UNDER
 PERMIT # 99120567 AND A RANGE AND FIREPLACE INSTALLED
 UNDER PERMIT # 05091464. NOT ALL OF THESE ARE SHOWN ON
 YOUR PLAN. LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4
 AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). . THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. . FGC SECS. 401.4,
 401.8, 402.1, 402.2, 402.3 OR FBCR SECS.G2412.4,
 G2412.8, G2413.1, G2413.2, G2413.3.
  
 2) YOU ARE SHOWING THE SYSTEM AS A 2 PSI SYSTEM BUT DID
 NOT INCLUDE ANY INSTALLATION MANUALS FOR THE PRESSURE
 REGULATORS.SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 3) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT
 REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT
 BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE
 ON THE APPLICATION IN THE DESCRIPTION OF WORK.
  
 4) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-08-20 Cont ID  
Sent By lcrespo Date 2018-08-20 Time 07:35 Rev Time 0.00
Received By lcrespo Date 2018-08-15 Time 14:51 Sent To  
Notes
2018-08-16 14:51:23RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-28 Cont ID  
Sent By tklarge Date 2018-07-28 Time 08:06 Rev Time 0.00
Received By tklarge Date 2018-07-24 Time 13:48 Sent To  
Notes
2018-07-25 13:49:18RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-19 Cont ID  
Sent By thunt Date 2018-07-19 Time 15:31 Rev Time 0.00
Received By thunt Date 2018-07-16 Time 14:05 Sent To I
Notes
2018-07-17 14:05:22RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-29 Cont ID  
Sent By thunt Date 2018-06-29 Time 14:30 Rev Time 0.00
Received By thunt Date 2018-06-20 Time 11:04 Sent To  
Notes
2018-06-21 11:05:08PLUMB <5K

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-06-29 Cont ID  
Sent By thunt Date 2018-06-29 Time 14:23 Rev Time 0.00
Received By thunt Date 2018-06-29 Time 14:23 Sent To  
Notes
***NONE***