2018-06-29 14:30:11 | 06/29/2018 1ST GAS REVIEW**DENIED** |
| |
| 1) CITY RECORDS SHOW A POOL HEATER INSTALLED UNDER |
| PERMIT # 99120567 AND A RANGE AND FIREPLACE INSTALLED |
| UNDER PERMIT # 05091464. NOT ALL OF THESE ARE SHOWN ON |
| YOUR PLAN. LIST THE BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 |
| FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4 |
| AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). . THE BTU |
| LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. . FGC SECS. 401.4, |
| 401.8, 402.1, 402.2, 402.3 OR FBCR SECS.G2412.4, |
| G2412.8, G2413.1, G2413.2, G2413.3. |
| |
| 2) YOU ARE SHOWING THE SYSTEM AS A 2 PSI SYSTEM BUT DID |
| NOT INCLUDE ANY INSTALLATION MANUALS FOR THE PRESSURE |
| REGULATORS.SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| G2421.1. |
| |
| 3) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT |
| REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT |
| BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE |
| ON THE APPLICATION IN THE DESCRIPTION OF WORK. |
| |
| 4) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. |
| G2413.4.1, G2413.4.2. |
| |
| |
| TIM HUNT |
| PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| 561-805-6695 |
| [email protected] |
| |
| |
| |
| |