Plan Review Details - Permit 18060904
Plan Review Stops For Permit 18060904
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-22 Cont ID  
Sent By lcrespo Date 2018-06-22 Time 15:37 Rev Time 0.00
Received By lcrespo Date 2018-06-21 Time 14:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-20 Cont ID  
Sent By lcrespo Date 2018-06-20 Time 15:18 Rev Time 0.00
Received By lcrespo Date 2018-06-20 Time 15:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-22 Cont ID  
Sent By lcrespo Date 2018-06-22 Time 15:37 Rev Time 0.00
Received By lcrespo Date 2018-06-21 Time 14:17 Sent To  
Notes
2018-06-22 15:37:5806/22/18 APPROVED BY UTILITIES SENT TO PROCESSING, LAC
  
2018-06-21 14:17:4706/21/18 APPROVED BY PLUMBING AND SENT TO UTILITIES,
 LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-20 Cont ID  
Sent By lcrespo Date 2018-06-20 Time 15:18 Rev Time 0.00
Received By lcrespo Date 2018-06-20 Time 15:15 Sent To  
Notes
2018-06-20 15:18:3306/20/2018 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ALL BACKFLOW DEVICES MUST BE LEAD FREE. P2906.2.1
 LEAD CONTENT OF DRINKING WATER PIPE AND FITTINGS.
  
 2. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS
 ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT DEPARTMENT
 OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT
 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE
 PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY
 REQUIREMENTS.
  
 THIS BACKFLOW IS NOT A LEAD-FREE DEVICE WHICH IS
 REQUIRED BY THE CITY OF WEST PALM BEACH UTILITY
 DEPARTMENT. YOU CAN REFER TO THEIR CROSS CONNECTION
 MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/
 PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CONN
 ECTION-CONTROL-MANUAL FOR MORE INFORMATION. THE 975XL
 WATKINS MODEL IS NOT LEAD-FREE AS THE 975XL2 IS SO
 PLEASE RESUBMIT SPECS FOR IT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  