Plan Review Details - Permit 18060764
Plan Review Stops For Permit 18060764
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-07-18 Cont ID  
Sent By shill Date 2018-07-18 Time 15:14 Rev Time 0.00
Received By shill Date 2018-07-18 Time 15:14 Sent To  
Notes
2018-07-18 16:05:27****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 2017 BUILDING 1604.5, FBC EXISTING BUILDING 1103,
 THE ADDITION IS TO BE DESIGNED TO RISK CATEGORY III,
 180MPH. PER CONVERSATION WITH SEOR, THIS DOES NOT
 AFFECT THE FOUNDATION DESIGN; THIS WILL BE REVISED WITH
 BUILDING PERMIT SUBMITTAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-07-16 Cont ID  
Sent By shill Date 2018-07-16 Time 17:52 Rev Time 0.00
Received By shill Date 2018-07-16 Time 17:52 Sent To  
Notes
2018-07-16 17:59:10COURTESY REVIEW
  
 ****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. MEP STRUCTURAL LETTER OK [FBC 105.13, AS DISCUSSED,
 PLEASE ADVISE WHEN THE BUILDING PERMIT APPLICATION HAS
 BEEN SUBMITTED. A FOUNDATION PERMIT WILL NOT BE ISSUED
 UNTIL THE BUILDING PERMIT IS SUBMITTED.]
  
 2. PROVISO - STRUCTURAL TO INCLUDE CERTIFICATE OF
 AUTHORIZATION ON EACH PAGE (FUTURE SUBMITTALS)
  
 3. OK
  
 4. PROVIDE UPDATED REVIEW BY PRIVATE PROVIDER (PLAN
 COMPLIANT AFFIDAVIT).
  
 CHANGES TO THE PLAN WERE MADE; I WAS UNABLE TO LOCATE
 THE PLAN COMPLIANT AFFIDAVIT FOR THE NEW PAGES.
  
 5. PENDING REVIEW BY RICHARD GATHRIGHT, ABO - PROVIDE
 PRIVATE PROVIDER NOTICE TO BUILDING OFFICIAL. PLEASE
 NOTE THAT THE LANGUAGE IN THE NOTICE SUBMITTED WITH THE
 DEMO PERMIT WAS SPECIFIC TO THE "ATTACHED PLANS". IT IS
 RECOMMENDED TO INCLUDE LANGUAGE WHICH COVERS ALL SCOPE
 OF WORK FOR THIS PROJECT TO AVOID THE NEED FOR MULTIPLE
 LETTERS.
  
 6. PENDING REVIEW BY RICHARD GATHRIGHT, ABO - PROVIDE
 UPDATED INSURANCE CERTIFICATE FOR PRIVATE PROVIDER.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-08 Cont ID  
Sent By shill Date 2018-07-08 Time 13:15 Rev Time 0.00
Received By shill Date 2018-07-08 Time 13:15 Sent To  
Notes
2018-07-08 13:17:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 105.13, AS DISCUSSED, PLEASE ADVISE WHEN THE
 BUILDING PERMIT APPLICATION HAS BEEN SUBMITTED. A
 FOUNDATION PERMIT WILL NOT BE ISSUED UNTIL THE BUILDING
 PERMIT IS SUBMITTED.
  
 PER BUILDING OFFICIAL - PROVIDE THE COMMENT LIST OR
 STAMPED PLAN FROM THE PRIVATE PROVIDER.
  
 2. PROVISO - STRUCTURAL TO INCLUDE CERTIFICATE OF
 AUTHORIZATION ON EACH PAGE (FUTURE SUBMITTALS)
  
 3. OK
  
 NEW COMMENTS:
  
 4. PROVIDE UPDATED REVIEW BY PRIVATE PROVIDER (PLAN
 COMPLIANT AFFIDAVIT).
  
 5. PROVIDE PRIVATE PROVIDER NOTICE TO BUILDING
 OFFICIAL. PLEASE NOTE THAT THE LANGUAGE IN THE NOTICE
 SUBMITTED WITH THE DEMO PERMIT WAS SPECIFIC TO THE
 "ATTACHED PLANS". IT IS RECOMMENDED TO INCLUDE LANGUAGE
 WHICH COVERS ALL SCOPE OF WORK FOR THIS PROJECT TO
 AVOID THE NEED FOR MULTIPLE LETTERS.
  
 6. PROVIDE UPDATED INSURANCE CERTIFICATE FOR PRIVATE
 PROVIDER. THIS MAY BE SENT VIA EMAIL:
  
 [email protected]
 [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 13:23 Rev Time 0.00
Received By shill Date 2018-06-30 Time 13:23 Sent To  
Notes
2018-06-30 13:27:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 105.13, AS DISCUSSED, PLEASE ADVISE WHEN THE
 BUILDING PERMIT APPLICATION HAS BEEN SUBMITTED. A
 FOUNDATION PERMIT WILL NOT BE ISSUED UNTIL THE BUILDING
 PERMIT IS SUBMITTED.
  
 IF YOU NEED TO APPEAL THIS DECISION, PLEASE SEND A
 LETTER FROM THE QUALIFIER ADDRESSED TO THE BUILDING
 OFFICIAL OUTLINING WHY ISSUANCE OF A FOUNDATION PERMIT
 WITHOUT BUILDING PERMIT SUBMITTAL WILL NOT CREATE A
 FUTURE URGENCY AND WILL NOT BE DETRIMENTAL TO THE JOB
 (INSTALLED FOUNDATION ELEMENTS WILL NOT BE SUBJECT TO
 WASHOUT WHILE IF THE BUILDING PERMIT IS NOT ISSUED IN
 THE EXPECTED TIME FRAME). THE LETTER CAN BE SENT VIA
 EMAIL.
  
 2. THE ENGINEER'S TITLE BLOCK LACKS THE CERTIFICATE OF
 AUTHORIZATION REQUIRED BY FS471, FAC61G15-23.002.
  
 PLEASE REVISE ALL SHEETS TO INCLUDE BUT ***DO NOT***
 RESUBMIT. THIS IS TO BE ON ALL FUTURE SUBMITTALS
 (BUILDING PERMIT, REVISIONS).
  
 3. AS IT APPEARS THAT THE OWNER DID NOT SIGN THE PERMIT
 APPLICATION, PLEASE PROVIDE A COPY OF A SIGNED CONTRACT
 FOR THIS JOB. OR, YOU MAY PROVIDE A PERMIT APPLICATION
 WITH THE OWNER'S NOTARIZED SIGNATURE, OR PROVIDE OTHER
 LEGAL AUTHORIZATION FOR SIGNER TO SIGN ON BEHALF OF
 OWNER.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2018-06-28 Cont ID  
Sent By jpearson Date 2018-06-28 Time 10:35 Rev Time 0.00
Received By jpearson Date 2018-06-28 Time 10:35 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-07-08 Cont ID  
Sent By shill Date 2018-07-08 Time 13:14 Rev Time 0.00
Received By shill Date 2018-07-08 Time 13:14 Sent To  
Notes
2018-07-08 13:15:07CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
 WHEN ALL OTHER REVIEWS HAVE PASSED, MANNY GONZALEZ WILL
 BE CONTACTED TO SEE IF THIS REVIEW CAN BE PASSED.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2018-06-30 Cont ID  
Sent By shill Date 2018-07-30 Time 12:40 Rev Time 0.00
Received By shill Date 2018-06-30 Time 12:40 Sent To  
Notes
2018-07-11 16:55:27APPLIED THUR ENGINEERING DEPT, - PASSED
2018-06-30 12:40:37CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-10 Cont ID  
Sent By pleduc Date 2018-07-10 Time   Rev Time 0.00
Received By pleduc Date 2018-07-10 Time 13:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-06-22 Cont ID  
Sent By pleduc Date 2018-06-22 Time   Rev Time 0.00
Received By pleduc Date 2018-06-21 Time 14:44 Sent To  
Notes
2018-06-21 15:30:24THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF HOW THE MECHANICAL
 VENTILATION/MAKE UP AIR FOR THE SMOKE CONTROL SYSTEM
 WILL BE MAINTAINED AND CONTROLLED THROUGHOUT THIS
 CONSTRUCTION PROJECT.
  
 THERE ARE LARGE INTAKE OPENINGS AT THIS EXISTING SLAB
 SITE THAT ARE NOT CLEARLY IIDENTIFIED ON THE PLAN
 SHEETS.
  
 PLEASE PROVIDE DETAILS ON HOW THIS SYSTEM WILL BE
 MAINTAINED AND/OR BUILT OUT.
  
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-18 Cont ID  
Sent By shill Date 2018-07-18 Time 15:14 Rev Time 0.00
Received By shill Date 2018-07-03 Time 16:07 Sent To  
Notes
2018-07-05 16:08:00C35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 13:28 Rev Time 0.00
Received By shill Date 2018-06-15 Time 10:18 Sent To  
Notes
2018-06-19 10:18:40C35

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-07-18 Cont ID  
Sent By shill Date 2018-07-18 Time 15:07 Rev Time 0.00
Received By shill Date 2018-07-18 Time 15:07 Sent To  
Notes
2018-07-18 15:10:21MU-2018-24860
 $1,376.91 PAID
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-07-08 Cont ID  
Sent By shill Date 2018-07-08 Time 13:12 Rev Time 0.00
Received By shill Date 2018-07-08 Time 13:12 Sent To  
Notes
2018-07-08 13:14:17TO REQUEST THAT IMPACT FEES BE DEFERRED UNTIL VERTICAL
 PERMIT, SEND THE REQUEST DIRECTLY TO THE BUILDING
 OFFICIAL (ROBERT BROWN) VIA EMAIL.
  
 [email protected]
 CC: [email protected]
  
 PLEASE MAKE THE REQUEST CLEAR THAT THIS INCLUDES
 BASEMENT WALLS.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 12:39 Rev Time 0.00
Received By shill Date 2018-06-30 Time 12:39 Sent To  
Notes
2018-06-30 12:39:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2018-06-28 Cont ID  
Sent By gjohnson Date 2018-06-28 Time 15:42 Rev Time 0.00
Received By gjohnson Date 2018-06-28 Time 15:42 Sent To  
Notes
2018-06-28 15:43:24NO PLUMBING WORK APPROVED UNDER THIS PERMIT
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 13:21 Rev Time 0.00
Received By shill Date 2018-06-30 Time 12:58 Sent To  
Notes
2018-06-30 12:59:06PROVISO - PENDING APPROVAL BY KEN CONRAD, CHIEF
 BUILDING INSPECTOR
  
 ADDITION OF ANOTHER INSPECTOR IS RECOMMENDED (MAY BE
 ADDED AFTER PERMIT ISSUANCE) - PLEASE CONTACT ME IF YOU
 WISH TO DISCUSS
  
 THRESHOLD STATEMENT FOR ARCHITECT ON MOST PAGES
 (WILLIAM A HANSER, AR7110)
 THRESHOLD STATEMENT FOR ENGINEER ON EACH PAGE (DEREK A
 WASSINK, PE 55303, THORNTON THOMASETTI)
  
 THRESHOLD INSPECTION PLAN ON SHEET DS004 & DS005
  
 PRIVATE PROVIDER (MEP STRUCTURAL ENGINEERING AND
 INSPECTIONS) IS ALSO SI FOR THE PROJECT
  
 SI AGREEMENT SIGNED BY:
  
 OTTO J LETZELTER, PE, SI 54716
 MEP STRUCTURAL ENGINEERING AND INSPECTIONS
 GARY HENNINGS, CGC1509819
 KRAVIS REP
 JACK BOTHE, BN5957
  
 ROUTED 1 SET TO RICHARD GATHRIGHT
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-17 Cont ID  
Sent By eschneid Date 2018-07-17 Time 13:13 Rev Time 0.25
Received By eschneid Date 2018-07-17 Time 13:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-26 Cont ID  
Sent By eschneid Date 2018-06-26 Time 15:15 Rev Time 0.75
Received By eschneid Date 2018-06-26 Time 12:02 Sent To  
Notes
***NONE***