Plan Review Details - Permit 18060761
Plan Review Stops For Permit 18060761
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-08 Cont ID  
Sent By fgiaquin Date 2018-07-08 Time 08:31 Rev Time 0.00
Received By fgiaquin Date 2018-07-08 Time 08:13 Sent To I
Notes
2018-07-08 08:31:11VALUE ADJUSTED TO 2400$

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-25 Cont ID  
Sent By fgiaquin Date 2018-06-25 Time 06:01 Rev Time 0.00
Received By fgiaquin Date 2018-06-25 Time 05:51 Sent To M
Notes
2018-06-25 06:00:35ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. VALUE TOO LOW, RAISE VALUE. FBC 109.3
  
 3. PROVIDE UPDATED FIRE ALARM RISER TO SHOW ADDITION OF
 NEW DEVICES. PROVIDE WRITTEN SCOPE OF WORK. PLAN
 SUBMITTED IS LACKING INFORMATION AND IS INSUFFICIENT.
  
 FBC107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-19 Cont ID  
Sent By pleduc Date 2018-06-19 Time   Rev Time 0.00
Received By pleduc Date 2018-06-19 Time 12:55 Sent To E
Notes
2018-06-19 15:20:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THERE ARE NO INDICATIONS THAT THE FIRE SUPPRESSION
 SYSTEM IS TIED INTO THE FIRE ALARM.
  
 PER NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS, 2014
 EDITION
  
 10.6 SYSTEM ANNUNCIATION.
 10.6.1 UPON ACTIVATION OF AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM,
 AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE PROVIDED
 TO
 SHOW THAT THE SYSTEM HAS ACTIVATED.
  
  
 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING
 THE OCCUPANCY
 WHERE THE EXTINGUISHING SYSTEM IS LOCATED, THE
 ACTIVATION
 OF THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL
 ACTIVATE
 THE FIRE ALARM SIGNALING SYSTEM.
  
  
 PLEASE PROVIDE FOR THE TIE IN AND SUBMITT REVISIONS TO
 ACCURATLEY SHOW ON THE DRAWING.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-08 Cont ID  
Sent By fgiaquin Date 2018-07-08 Time 08:31 Rev Time 0.00
Received By fgiaquin Date 2018-07-02 Time 14:42 Sent To  
Notes
2018-07-03 14:42:14RESUB ROUTED TO FGIAQUIN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-06-29 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-15 Time 09:37 Sent To  
Notes
2018-06-18 09:37:38ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-06-29 Cont ID  
Sent By ccole Date 2018-06-29 Time 10:57 Rev Time 0.00
Received By ccole Date 2018-06-29 Time 10:57 Sent To I
Notes
***NONE***