Plan Review Details - Permit 18060742
Plan Review Stops For Permit 18060742
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-05 Cont ID  
Sent By skennedy Date 2018-07-05 Time 10:21 Rev Time 0.00
Received By skennedy Date 2018-07-05 Time 10:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By fgiaquin Date 2018-06-29 Time 07:30 Rev Time 0.00
Received By fgiaquin Date 2018-06-29 Time 07:09 Sent To I
Notes
2018-06-29 07:30:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PRINTED COPIES OF DIGITALLY SIGNED PLANS ARE NOT
 CONSIDERED TO BE SIGNED. ELECTRICAL PLAN IS REQUIRED TO
 BE DESIGNED AND SIGNED/SEALED BY A DESIGN PROFESSIONAL
 OR THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-29 Cont ID  
Sent By cpuell Date 2018-06-29 Time 10:04 Rev Time 0.00
Received By cpuell Date 2018-06-15 Time 10:42 Sent To  
Notes
2018-06-18 10:42:38MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-05 Cont ID  
Sent By skennedy Date 2018-07-05 Time 10:21 Rev Time 0.00
Received By skennedy Date 2018-07-05 Time 10:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-27 Cont ID  
Sent By ccole Date 2018-06-27 Time 17:45 Rev Time 0.00
Received By ccole Date 2018-06-27 Time 17:45 Sent To  
Notes
2018-06-27 17:45:341ST REVIEW FBC-2017 RESIDENTIAL MECHANICAL
 PERMIT #18060742
 6/27/18
  
 CODES IN EFFECT:
  
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC SYSTEM CHOSEN FOR THE GARAGE IS AN AHRI
 CERTIFIED HEAT PUMP SYSTEM. IT IS NOT CERTIFIIED,
 TESTED, OR RATED AS A DEHUMIDIFER. DEHUMIDIFIERS FALL
 UNDER A SEPARATE CERTIFICATION CATEGORY AND ARE NOT
 DESIGNED FOR COMFORT CONDITIONING. IF CHOOSING TO USE
 THIS SYSTEM, PLEASE PROVIDE AC LOAD CALCULATIONS PER
 SECTION R403.7.1 FBC EC, AND ENERGY CALCULATIONS FOR
 THE GARAGE PER THE FOLLOWING ENERGY CODE SECTIONS:
 R502.1, R503.2, R202 , AND R101.2- R101.5.1.2 FBC EC.
  
 2) PROVIDE AN ELECTRICAL PLAN- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  