Plan Review Details - Permit 18060681
Plan Review Stops For Permit 18060681
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-11-29 Cont ID  
Sent By jgomez Date 2018-11-29 Time 12:22 Rev Time 0.00
Received By jgomez Date 2018-11-29 Time 12:17 Sent To  
Notes
2018-11-29 12:17:18BUILDING REVIEW APPROVED WITH PROVISO:
 IF MORE THAN 100 CHILDREN LESS THAN 2 1/2 YRS, THEN
 SPRINKLERS ARE REQUIRED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-11-08 Cont ID  
Sent By jgomez Date 2018-11-08 Time 14:19 Rev Time 0.00
Received By jgomez Date 2018-11-08 Time 12:33 Sent To  
Notes
2018-11-08 14:20:16BUILDING REVIEW APPROVED WITH PROVISO:
 IF MORE THAN 100 CHILDREN LESS THAN 2 1/2 YRS, THEN
 SPRINKLERS ARE REQUIRED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-28 Cont ID  
Sent By jgomez Date 2018-09-28 Time 17:32 Rev Time 0.00
Received By jgomez Date 2018-09-26 Time 15:40 Sent To  
Notes
2018-09-26 18:39:25 
  
 09/28/18 TALKED TO RICHARD ELLIOT (OWNER). TOLD HIM TO
 READ COMMENTS AND BUILDING REVIEW COULD BE APPROVED
 WITH PROVISO (FEES MAY APPLY).
  
  
 TENANT BUILD OUT AND CHANGE OF OCCUPANCY SECOND
 BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
 1-IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 2- SHEET A0.01-COVER SHEET:
 A) OK
  
 B) A NEW CERTIFICATE OF OCCUPANCY WILL BE REQUIRED.
 SEC. 1001.3 FBC EXISTING BUILDING. (PROVISO)
  
 C)OK
  
 D) OK
  
 E) OK
  
 3- SHEET A1.01-PLAYGROUND/SITE PLAN:
 A)SPECIFY SIZE OF ALL EXIT GATES FROM FENCED PLAYGROUND
 AREAS AS REQUIRED BY SEC. 1006.2.2.4 FBC.
  
 B) OK.
  
 PROVISO: PROVIDE COMPLETE INFORMATION FOR PLAY AREAS
 EQUIPMENT UNDER A SEPARATE PERMIT SHOWING COMPLIANCE
 WITH SEC. 240 FBC- ACCESSIBILITY FOR THE ITEMS THAT
 APPLY IN THIS PROJECT.
 C) PLAY AREAS: SHOW COMPLIANCE WITH SEC. 240 AND 1008
 FBC- ACCESSIBILITY FOR THE ITEMS THAT APPLY IN THIS
 PROJECT.
  
  
 4- SHEET A2.00- LIFE SAFETY PLAN:
 A) OK.
  
 B) OK.
  
 C) OK
  
 (2)SHOW COMPLIANCE WITH CONSTRUCTION AND OPENINGS SEC.
 1028.4.2 FBC. THE WIDTH OF THE EGRESS COURT IS LESS
 THAN 10FEET.
 NOTE: NEED NOT LESS THAN 3/4 HOUR FIRE RATING. (NOT 20
 MIN.)
  
 (3)SHOW COMPLIANCE WITH THE ACCESS TO A PUBLIC WAY.
 SEC. 1028.5 FBC. NOTE: THE EGRESS ACCESS NEED TO BE
 ACCESSIBLE. SEC.
 207.1 FBC ACCESSIBLE. SHOW ON PLANS FLOOR/GROUND
 SURFACES LEADING TO ALL GATES (NORTH, SOUTH AND EAST).
 THIS INFORMATION MAY BE PROVIDED ON SITE PLAN SHEET
 A1.01.
  
 (4) OK.
  
 D) OK.
  
 E) OK.
  
 F) OK.
  
 5- SHEET A2.01 - FLOOR PLAN:
 A) TENANT SEPARATION WALL "P2". REVISE DETAIL 2/A8.01.
 THERE IS INFORMATION FOR UL # U419 AND FOR UL # U465 ON
 THE SAME DETAIL. DON'T MISMATCH BOTH ASSEMBLIES.
 ALSO ON SHEET A8.01 THERE ARE TWO DETAILS #1 AND THERE
 IS NOT DETAIL #6. COORDINATE WITH DETAILS ON WALL
 LEGEND ON SHEET A2.01.
  
 B) OK
  
 C)SPECIFY DIMENSION FOR OPENING IN THE HALF HEIGHT
 PARTITION LOCATED BETWEEN THE INFANTS CLASSROOMS.
  
 D)OK.
  
 E)OK.
  
 F) OK.
  
 6- SHEET A4.00-SCHEDULES/DETAILS:
 A) OK.
  
 B)OK.
  
 7- OK.
  
 8- OK.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
 A) NEW EXTERIOR EXIT DOOR S SHOWN ON PLANS.
 NOTE: NOA 14-1021.03 SUBMITTED NEED TO BE COORDINATED
 WITH REQUIRED 3/4 HOUR FIRE RATED DOOR. SEE ITEM
 #4(C)(2) ABOVE. PROVIDE FIRE RATING FOR THIS DOOR.
  
 B) PRECAST LINTELS A SPECIFIED ON PLANS FOR NEW ENTRY
 DOOR OPENING.
 NOTE: PROVIDE ACTUAL NOA OR FLORIDA PRODUCT APPROVAL
 NOT THE MANUFACTURER'S LITERATURE.
  
 10-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 11-PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 12-PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 ****PROVISO: IF MORE THAN 100 CHILDREN LESS THAN 2 1/2
 YRS THEN SPRINKLERS ARE REQUIRED
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-12 Cont ID  
Sent By jgomez Date 2018-07-12 Time 18:47 Rev Time 0.00
Received By jgomez Date 2018-07-09 Time 13:43 Sent To  
Notes
2018-07-10 16:03:24TENANT BUILD OUT AND CHANGE OF OCCUPANCY-BUILDING
 REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
 1-IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 2- SHEET A0.01-COVER SHEET:
 A) REVISE PROPOSED OCCUPANCY CLASSIFICATION. GROUP "E"
 DAY CARE FACILITIES IS FOR CHILDREN OLDER THAN 2-1/2
 YEARS OLD. SEC. 305.2 FBC. ACCORDING TO SEC. 308.6 FBC
 THE OCCUPANCY CLASSIFICATION FOR THE PROPOSED OCCUPANCY
 IS "I-4" DAY CARE FACILITIES NOT "E" (MORE THAN 100
 CHILDREN). REVISE THE PREVIOUS TENANT NOTES, BUILDING
 AND CONSTRUCTION DATA AND INTERIOR FINISHES INFORMATION
 AS REQUIRED. PLANS NEED TO BE REVIEWED AS INSTITUTIONAL
 I-4.
  
 B) A NEW CERTIFICATE OF OCCUPANCY WILL BE REQUIRED.
 SEC. 1001.3 FBC EXISTING BUILDING.
 SEC. 1001.3 CERTIFICATE OF OCCUPANCY REQUIRED.
 A CERTIFICATE OF OCCUPANCY SHALL BE ISSUED WHERE A
 CHANGE OF OCCUPANCY OCCURS THAT RESULTS IN A DIFFERENT
 OCCUPANCY CLASSIFICATION AS DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING.
  
 C)\REVISE EXISTING BUILDING CONSTRUCTION TYPE.
 ACCORDING TO NEW BUILDING CITY RECORDS PERMIT #13060228
 THIS BUILDING IS CONSTRUCTION TYPE VB NOT TYPE IIIB.
 NOTE: EXISTING BUILDING IS NON-SPRINKLERED. REVISE AS
 REQUIRED. SEC. 601.1 FBC.
  
 D) REVISE TOTAL OCCUPANT LOAD. THE TOTAL OCCUPANT LOAD
 OF 35S.F. NET FOR DAY CARE IS FOR ALL OCCUPANTS
 INCLUDING STAFF, NOT JUST THE CHILDREN. NEED TO DELETE
 THE 30 STAFF. ON THE OTHER HAND NEED TO ADD THE NUMBER
 OF PEOPLE FOR OTHER AREAS LIKE KITCHEN, RECEPTION AND
 JANITOR/LAUNDRY. REVISE AS REQUIRED USING TABLE
 1004.1.2 FBC.
  
 E) REVISE INTERIOR FINISHES INFORMATION. THERE IS NOT
 TABLE 803.9. THE CORRECT TABLE IS IS TABLE 803.11 FBC.
  
 3- SHEET A1.01-PLAYGROUND/SITE PLAN:
 A)SHOW COMPLIANCE WITH THE TWO EXITS FROM FENCED
 PLAYGROUND AREAS AS REQUIRED BY SEC. 1006.2.2.4 FBC.
  
 B) PLAY AREAS: SHOW COMPLIANCE WITH ACCESSIBLE ROUTES
 SEC. 206.2.17. FBC- ACCESSIBILITY
  
 C) PLAY AREAS: SHOW COMPLIANCE WITH SEC. 240 FBC-
 ACCESSIBILITY FOR THE ITEMS THAT APPLY IN THIS PROJECT.
  
 D) PLAY AREAS: SHOW COMPLIANCE WITH SEC. 1008 FBC-
 ACCESSIBILITY FOR THE ITEMS THAT APPLY IN THIS PROJECT.
  
  
 4- SHEET A2.00- LIFE SAFETY PLAN:
 A) TOTAL OCCUPANT LOAD ON DOOR REQUIREMENTS NOTE C IS
 INCORRECT. COORDINATE WITH ITEM #2D ABOVE AND REVISE AS
 REQUIRED. SEC. 1004.1 FBC.
  
 B) THE CORRIDOR CONTINUITY IS INTERRUPTED BY AN
 INTERVENING ROOM (DRAMATIC PLAY CLASSROOM). REVISE FBC.
 AS REQUIRED. SEC. 1020.6 FBC.
  
 C) SHOW COMPLIANCE WITH THE EXIT DISCHARGE REQUIREMENTS
 AT THE FENCED AREAS:
 1)SHOW COMPLIANCE WITH THE WIDTH SEC. 1028.4.1 FBC.
 NOTE: I LOOKS LIKE THE WIDTH OF THE "EGRESS COURT" ON
 BY THE TWO
 CLASSROOMS ON THE NORTH EAST CORNER OF THE BUILDING
 DOESN'T COMPLY WITH SEC. 1005.7.1 FBC. THE DOOR REDUCES
 THE WIDTH BY MORE THAN ONE-HALF. REVISE AS REQUIRED TO
 COMPLY.
  
 (2)SHOW COMPLIANCE WITH CONSTRUCTION AND OPENINGS SEC.
 1028.4.2 FBC. THE WIDTH OF THE EGRESS COURT IS LESS
 THAN 10FEET.
  
 (3)SHOW COMPLIANCE WITH THE ACCESS TO A PUBLIC WAY.
 SEC. 1028.5 FBC. NOTE: THE EGRESS ACCESS NEED TO BE
 ACCESSIBLE. SEC.
 207.1 FBC ACCESSIBLE. SHOW ON PLANS FLOOR/GROUND
 SURFACES LEADING TO ALL GATES (NORTH, SOUTH AND EAST).
 THIS INFORMATION MAY BE PROVIDED ON SITE PLAN SHEET
 A1.01.
  
 (4) SWING OF GATES ON PLAYGROUND AREA NEED TO BE IN THE
 DIRECTION OF TRAVEL FOR AREAS WITH MORE THAN 50 PEOPLE.
 THERE IS
 A CONFLICT WITH THE GATE LOCATED BETWEEN THE OLDER KIDS
 AND INFANTS/TODDLERS. REVISE AS REQUIRED. SEC.
 1010.1.2.1 FBC.
 THIS INFORMATION MAY BE PROVIDED ON SITE PLAN SHEET
 A1.01.
  
 D) THE NUMBER OF EXITS SHOWN ON THE EXIT REQUIREMENTS
 TABLE IN THE MIDDLE OF THE SHEET IS NOT CLEAR. THERE
 ARE 8 EXITS SHOWN ON PLAN NOT 11. NOTE: EXIT AND EXIT
 ACCESS DOORWAY ARE NOT THE SAME THING. SEE DEFINITIONS
 ON CHAPTER 2. ALSO, FOR CLARIFICATION THERE ARE ONLY 3
 EXITS LOCATED IN THE CORRIDOR. THE OTHER 5 EXITS ARE
 THE REQUIRED 2ND EXITS FOR THE INDIVIDUAL ROOMS. SEC.
 1006.2.2.4 FBC.
  
 E) EXIT SIGN IS MISSING ON BOTH SIDES OF EXIT ACCESS
 DOOR BETWEEN THE TWO INFANT CLASSROOMS. SEC. 1013.1
 FBC. REVISE ELECTRICAL PLANS AS REQUIRED.
  
 F) THERE ARE NOT EXIT SIGNS IN THE CORRIDOR INDICATING
 THE DIRECTION OF EGRESS TRAVEL. SEC. 1013.1 FBC. REVISE
 ELECTRICAL PLANS AS REQUIRED. NOTE:CHECK REQUIRED
 DISTANCES ALSO.
  
 5- SHEET A2.01 - FLOOR PLAN:
 A) TWO HOUR TENANT SEPARATION WALL "P2". ASSEMBLY
 UL-U465 SPECIFIED ON DETAIL 2/A8.01 DOESN'T CORRESPOND
 TO 2 HOUR FIRE RATED WALL ASSEMBLY AND IT DOESN'T MATCH
 THE UL-U465 ASSEMBLY EITHER. REVISE AS REQUIRED.
 PROVIDE 2 HR FIRE RATED ASSEMBLY THAT PROVIDE FIRE
 RESISTANCE FROM BOTH SIDES. TABLE 508.4 FBC
  
 B) TWO HOUR TENANT SEPARATION WALL "P2". HEAD/WALL
 JOINT TERMINATION SYSTEM NO HW-D-0020 SPECIFIED ON
 DETAIL 6/A8.01 DOESN'T MATCH WALL AND CEILING
 ASSEMBLIES IN THIS PROJECT. REVISE AS REQUIRED. TABLE
 508.4 FBC. NOTE: ACCORDING TO CITY RECORDS FOR THE
 CONSTRUCTION OF THE SHELL, THERE IS NOT CONCRETE IN THE
 ROOF ASSEMBLY.
  
 C)CLARIFY/REVISE INFORMATION FOR DOOR IN THE HALF
 HEIGHT PARTITION LOCATED BETWEEN THE INFANTS
 CLASSROOMS. CLARIFY SIZE OF DOOR. COORDINATE WITH EXIT
 SIGN REQUESTED ON ITEM #4E ABOVE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 D)PROVIDE ALL DIMENSIONS FOR ALL BATHROOMS SHOWN ON THE
 FLOOR PLAN. SEC. 604 FBC-ACCESSIBILITY.
  
 E)REVISE INFORMATION ON DETAIL 4/A4.00 FOR WINDOW W1
 SPECIFIED ON FLOR PLAN. THE DISTANCE OF GLAZING FROM
 THE DOOR IS WITHIN 24" NOT 12". REVISE AS REQUIRED.
 SEC. 2406.4 FBC.
  
 F) REVISE FINISH NOTES AT THE BOTTOM OF ROOM FINISH
 SCHEDULE. INFORMATION DOESN'T MATCH INFORMATION SHOWN
 ON SHEET A0.01. REVISE CLASS OF FINISHES TO MATCH AND
 PROVIDE CORRECT TABLE NUMBER. COORDINATE WITH ITEM #2E
 ABOVE. TABLE 803.11 FBC.
  
 6- SHEET A4.00-SCHEDULES/DETAILS:
 A) REVISE NOTE AT THE BOTTOM OF DOOR SCHEDULE "ALL
 DOORS TO COMPLY W/ FBC 1008.1.9". THERE IS NOT SUCH
 SECTION. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B)REVISE INFORMATION ON DETAIL 4/A4.00 FOR WINDOW W1
 SPECIFIED ON FLOR PLAN. THE DISTANCE OF GLAZING FROM
 THE DOOR IS WITHIN 24" NOT 12". REVISE AS REQUIRED.
 SEC. 2406.4 FBC.
  
 7- PROVIDE FIRE SPRINKLERS INFORMATION AS REQUIRED BY
 SEC. 107.3.5.1 CITY AMENDMENTS.
  
 8- THE PROPOSED SCOPE OF WORK INCLUDES THE SHELL AREA
 THAT WAS NOT AIR CONDITIONED AND A CHANGE OF
 OCCUPANCY/USE. PROVIDE COMPLETE ENERGY CALCULATIONS (2
 COPIES), NOT JUST THE PRESCRIPTIVE FORM. SEE MECHANICAL
 COMMENTS. SEC. C503.2 AND SEC. C505 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE ENERGY CALCULATIONS ARE PROPERLY
 SIGNED AND SEALED BY THE REQUIRED DESIGN PROFESSIONALS
 AND ALL THE INFORMATION IS PROVIDED.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
 A) NEW EXTERIOR EXIT DOOR S SHOWN ON PLANS.
  
 B) PRECAST LINTELS A SPECIFIED ON PLANS FOR NEW ENTRY
 DOOR OPENING.
  
 10-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 11-PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 12-PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-30 Cont ID  
Sent By jpearson Date 2018-10-30 Time 10:55 Rev Time 0.00
Received By jpearson Date 2018-10-30 Time 09:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-02 Cont ID  
Sent By jpearson Date 2018-09-02 Time 09:19 Rev Time 0.00
Received By jpearson Date 2018-09-02 Time 09:19 Sent To  
Notes
2018-09-02 09:19:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE AIC RATING OF PANELS. NEC 110.3, 110.9 (NOT
 ADDRESSED.)
 2. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS
 ADEQUATE. NEC 110.10 (NOT ADDRESSED.)
 3. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24. (NOT ADDRESSED.)
 4. PROVIDE NOTE THAT GFCI PROTECTION FOR DRINKING
 FOUNTAIN MUST BE READILY ACCESSIBLE. NEC 422.5, 422.52
 (NOT ADDRESSED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
 NOTE: PROPOSED USE IS INSTITUTIONAL "I-4" NOT
 EDUCATIONAL "E". SEE NUMBER OF CHILDREN AND AGES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-16 Cont ID  
Sent By jpearson Date 2018-07-16 Time 13:58 Rev Time 0.00
Received By jpearson Date 2018-07-16 Time 10:13 Sent To  
Notes
2018-07-16 13:58:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AIC RATING OF PANELS. NEC 110.3, 110.9
 2. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS
 ADEQUATE. NEC 110.10
 3. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.
 4. PROVIDE NOTE THAT GFCI PROTECTION FOR DRINKING
 FOUNTAIN MUST BE READILY ACCESSIBLE. NEC 422.5, 422.52
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
2018-07-11 08:05:13NOTE: PROPOSED USE IS INSTITUTIONAL "I-4" NOT
 EDUCATIONAL "E". SEE NUMBER OF CHILDREN AND AGES.

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-10-30 Cont ID  
Sent By jpearson Date 2018-10-30 Time 15:19 Rev Time 0.00
Received By jpearson Date 2018-10-30 Time 15:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-10-25 Cont ID  
Sent By scaldero Date 2018-10-25 Time 10:12 Rev Time 0.00
Received By scaldero Date 2018-10-25 Time 10:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-05 Cont ID  
Sent By scaldero Date 2018-09-05 Time 12:13 Rev Time 0.00
Received By scaldero Date 2018-09-05 Time 11:53 Sent To  
Notes
2018-09-05 12:17:14DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-17 Cont ID  
Sent By scaldero Date 2018-07-17 Time 10:48 Rev Time  
Received By scaldero Date 2018-06-27 Time 11:48 Sent To  
Notes
2018-07-17 10:48:27PERMIT # 18060681
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. (THIS SAME NOTE APPEARS ON
 SHEET A2.00, BUT THE ENGINEERED DOCUMENTS ARE NOT
 PROVIDED.)
  
 2) PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 4) SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS, AS APPLICABLE
 TO THIS PROJECT.
  
 5) PLEASE REVIEW AND RESPOND TO BUILDING PLAN REVIEWER
 COMMENTS.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-11-29 Cont ID  
Sent By jgomez Date 2018-11-29 Time 12:22 Rev Time 0.00
Received By jgomez Date 2018-11-29 Time 12:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-14 Cont ID  
Sent By gjohnson Date 2018-11-14 Time 13:15 Rev Time 0.00
Received By gjohnson Date 2018-10-22 Time 15:54 Sent To  
Notes
2018-10-23 15:54:21C22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-28 Cont ID  
Sent By jgomez Date 2018-09-28 Time 17:52 Rev Time 0.00
Received By jgomez Date 2018-08-29 Time 10:32 Sent To I
Notes
2018-08-31 10:32:16C21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-31 Cont ID  
Sent By gjohnson Date 2018-07-31 Time 14:50 Rev Time 0.00
Received By gjohnson Date 2018-06-14 Time 15:21 Sent To  
Notes
2018-06-14 15:22:00C21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2018-11-29 Cont ID  
Sent By jgomez Date 2018-11-29 Time 12:22 Rev Time 0.00
Received By jgomez Date 2018-11-29 Time 12:15 Sent To  
Notes
2018-11-29 12:23:42$33,239.07 PAID. MU-2018-039360.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-11-08 Cont ID  
Sent By jgomez Date 2018-11-08 Time 14:20 Rev Time 0.00
Received By jgomez Date 2018-11-08 Time 14:20 Sent To  
Notes
2018-11-08 14:20:49IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-09-28 Cont ID  
Sent By jgomez Date 2018-09-28 Time 17:52 Rev Time 0.00
Received By jgomez Date 2018-09-28 Time 17:52 Sent To  
Notes
2018-09-28 17:52:48IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-07-12 Cont ID  
Sent By jgomez Date 2018-07-12 Time 08:23 Rev Time 0.00
Received By jgomez Date 2018-07-12 Time 08:23 Sent To  
Notes
2018-07-12 08:23:38IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-09-13 Cont ID  
Sent By ccole Date 2018-09-13 Time 17:19 Rev Time 0.00
Received By ccole Date 2018-09-13 Time 17:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-03 Cont ID  
Sent By ccole Date 2018-07-03 Time 14:13 Rev Time 0.00
Received By ccole Date 2018-07-03 Time 13:03 Sent To  
Notes
2018-07-03 14:48:071ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18060681
 7/3/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PROPOSED PROJECT IS CLASSIFIED AS A CHANGE OF
 OCCUPANCY PER SECTION 202 FBC EX, AND THEREFORE SHALL
 BE IN COMPLIANCE WITH SECTIONS C503.2 AND C505.1 FBC
 EC. THE SUBMITTED ENERGY FORM C402-2017 IS VALID FOR
 ALTERATIONS, RENOVATIONS, AND BUILDING SYSTEMS. IN
 ACCORDANCE WITH SECTION C101.5.1 APPROVED SOFTWARE SUCH
 AS ENERGYGAUGE OR COMCHECK SHALL BE USED TO SHOW
 COMPLIANCE.
  
 2) SHEET M1: EXHAUST AT A RATE OF .75 CFM PER SQ. FT.
 IS REQUIRED FOR THE KITCHEN, AND RECIRCULATION OF AIR
 FROM THE KITCHEN IS PROHIBITED- PLEASE REMOVE THE
 RETURN DUCTS AND GRILLS FROM THE KITCHEN AND ADJOINING
 STORAGE/LAUNDRY ROOM.
  
 3) SHEET M1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE OVENS AND ANY OTHER COOKING APPLIANCES IN THE
 KITCHEN. REFER TO SECTIONS 507.2 AND 507.3 FBC M AND
 PROVIDE EITHER A TYPE I OR TYPE II EXHAUST HOOD. PLEASE
 NOTE THE MAIN PLANS SHALL SHOW THE HOOD AND
 SPECIFICATIONS BUT THE INSTALLATION SHALL BE DONE UNDER
 SEPARATE PERMIT- SECTION 107.2.1.3 WPB.
  
 4) PROVIDE AIR BALANCE CALCULATIONS- SECTION 508.1 FBC
 M.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER
 PER SECTION 504.1 FBC M, AND INDICATE HOW MAKEUP AIR IS
 BEING PROVIDED- SECTION 504.6 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-11-14 Cont ID  
Sent By gjohnson Date 2018-11-14 Time 13:15 Rev Time 0.00
Received By gjohnson Date 2018-11-14 Time 13:15 Sent To  
Notes
2018-11-08 14:22:57REVISED DRAWINGS WERE SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-09-26 Cont ID  
Sent By gjohnson Date 2018-09-26 Time 10:40 Rev Time 0.00
Received By gjohnson Date 2018-09-26 Time 09:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-31 Cont ID  
Sent By gjohnson Date 2018-07-31 Time 14:23 Rev Time 0.00
Received By gjohnson Date 2018-07-31 Time 10:23 Sent To  
Notes
2018-07-31 14:50:201ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. AT LEAST 1 SINK IN EACH ROOM SHALL COMPLY WITH FBC
 ACC 212.3, 606
  
 2. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE, PER FBC ACC 609.4
  
 3. ALL WATER FOUNTAINS SHALL COMPLY WITH FBC ACC 211
  
 4. SHOW THE AGES OF THE CHILDREN ON THE FLOOR PLAN PER
 ROOM. WPB AMEND TO FBC 107.2.1
  
 5. PROVIDE SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR. WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
2018-07-11 08:05:32NOTE: PROPOSED USE IS INSTITUTIONAL "I-4" NOT
 EDUCATIONAL "E". SEE NUMBER OF CHILDREN AND AGES

Review Stop Z ZONING
Rev No 3 Status P Date 2018-11-02 Cont ID  
Sent By eschneid Date 2018-11-02 Time 16:31 Rev Time 0.50
Received By eschneid Date 2018-11-02 Time 09:45 Sent To  
Notes
2018-11-02 16:45:15PASSED W/PROVISOS
  
 1) PRIOR TO THE CERTIFICATE OF COMPLETION/OCCUPANCY FOR
 THE DAY CARE:
  
 A. SUBMIT A TREE ALTERATION PERMIT TO THE PLANNING
 DIVISION FOR TREES AND SHRUBS THAT ARE PROPOSED FOR
 RELOCATION. THIS MAY ALSO REQUIRE THE SUBMITTAL OF A
 LANDSCAPE PERMIT.
  
 B. SUBMIT PERMITS FOR THE PLAYGROUND EQUIPMENT AND
 UMBRELLAS. THE PERMIT FOR THESE FEATURES MUST INCLUDE
 APPROVAL FROM ALL THE EASEMENT HOLDERS THAT THEY WILL
 PERMIT THE EQUIPMENT WITHIN THE EASEMENT.
  
 C. SUBMIT A BICYCLE RACK/PAD PERMIT. THIS PERMIT MUST
 SHOW THE CORRECT NUMBER AND TYPE OF BICYCLE RACKS AND
 THE ACCURATE DIMENSIONS FOR THE PADS AND THE RACKS ON
 THE PADS.
  
 D. A HARDSCAPE PERMIT. THIS PERMIT MUST INCLUDE THE
 DETAILS OF THE PLAY SURFACE. PLEASE REMEMBER THAT NONE
 OF THE EXISTING LANDSCAPE ADJACENT TO THE BUILDING MAY
 BE REMOVED AS PART OF THIS APPLICATION. THIS PERMIT
 MUST INCLUDE CALCULATIONS TO VERIFY THAT THE SOD BEING
 REMOVED FOR THE PLAY AREA DOES NOT REDUCE THE AMOUNT OF
 LANDSCAPE ON THE SITE BELOW THE MINIMUM 15%
 REQUIREMENT.
  
 E. SUBMIT A FENCE PERMIT ALL THE FENCES AND GATES.
  
 F. SUBMIT A PARKING LOT STRIPING PERMIT IS REQUIRED FOR
 THE INSTALLATION OF THE DROP OFF SPACES.
  
 G. SUBMIT A MINOR AMENDMENT MUST BE SUBMITTED TO AND
 APPROVED BY THE PLANNING DIVISION FOR THE CHANGES TO
 THE EXTERIOR OF THE SITE (FENCES, RELOCATED BICYCLE
 RACK, RELOCATED DROP OFF SPACES, ETC.).
  
 2. ALL PERMITS SUBMITTED TO ADDRESS ITEMS IN #1 NEED TO
 BE ISSUED, INSTALLED AND PASS INSPECTION PRIOR TO THE
 C.O.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2018-09-05 Cont ID  
Sent By eschneid Date 2018-09-05 Time 09:29 Rev Time 0.50
Received By eschneid Date 2018-09-05 Time 09:29 Sent To  
Notes
2018-09-05 10:57:38FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: THE MECHANICAL PLANS INDICATE THAT
 RTU 3-8 ARE NEW INSTALLATIONS. PLEASE PROVIDE
 VERIFICATION THAT THE NEW RTU'S (INCLUDING CURB HEIGHT)
 CONFORM TO THE FOLLOWING REQUIREMENT OF THE SEDONA
 COMMONS DEVELOPMENT ORDER - "ALL GROUND AND ROOF
 MOUNTED AIR CONDITIONING, MECHANICAL EQUIPMENT,
 SATELLITE DISHES, GENERATORS, ETC., SHALL BE SCREENED
 FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE BARRIER
 CONSISTENT WITH THE COLOR, CHARACTER AND ARCHITECTURAL
 STYLE OF THE STRUCTURES OR EQUIVALENT LANDSCAPE
 MATERIAL. THE HEIGHT OF THE OPAQUE BARRIER SHALL BE AS
 REQUIRED TO PROVIDE AMPLE SCREENING". VERIFICATION IS
 PROVIDED VIA SIGHT LINE OR SIMILAR METHODS. STATING
 THAT THE EQUIPMENT WILL BE SCREENED IS NOT SUFFICIENT.
  
 3) THE RESUBMITTED PLANS SHOW TWO DRINKING FOUNTAIN
 LOCATIONS ON THE WEST EXTERIOR OF THE BUILDING ARE
 SHOWN IN REQUIRED LANDSCAPE BEDS. YOU MAY NOT REMOVE
 THE REQUIRED LANDSCAPE ALONG THE BUILDING. ANY PROPOSED
 DRINKING FOUNTAINS MUST BE INSTALLED AS LOCATIONS THAT
 DO NOT REMOVE LANDSCAPE.
  
 4) THE RESUBMITTED PLANS SHOW PLAYGROUND EQUIPMENT AND
 PERMANENT UMBRELLAS WITHIN THE VARIUS UTILITY EASEMETS.
 THE PERMIT FOR THESE FEATURES MUST INCLUDE APPROVAL
 FROM ALL THE EASEMENT HOLDERS THAT THEY WILL PERMIT THE
 EQUIPMENT WITHIN THE EASEMENT.
  
 5) REPEAT COMMENT: THE FOLLOWING SEPARATE BUILDING
 PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR TO ZONING
 APPROVAL OF THIS PERMIT:
  
 A. A BICYCLE RACK/PAD PERMIT. THIS PERMIT MUST SHOW THE
 CORRECT NUMBER AND TYPE OF BICYCLE RACKS AND THE
 ACCURATE DIMENSIONS FOR THE PADS AND THE RACKS ON THE
 PADS. PLEASE NOT THAT THE CURRENTLY PROPOSED BICYCLE
 RACK LOCATION DIRECTLY CONFLICTS WITH AN EXISTING OAK
 TREE AND MUST BE SHOWN IN A DIFFERENT LOCATION.
  
 B. A HARDSCAPE PERMIT. THIS PERMIT MUST INCLUDE THE
 DETAILS OF AND DEMARCATE THE BOUNDARIES OF THE
 "PERMA-GRASS". PLEASE REMEMBER THAT NONE OF THE
 EXISTING LANDSCAPE ADJACENT TO THE BUILDING MAY BE
 REMOVED AS PART OF THIS APPLICATION. THE EXISTING
 LANDSCAPE MAY NOT BE REMOVED SINCE IT IS THE REQUIRED
 LANDSCAPE BUFFER AND FOUNDATION PLANTING. THIS PERMIT
 MUST INCLUDE CALCULATIONS TO VERIFY THAT THE SOD BEING
 REMOVED FOR THE PLAY AREA DOES NOT REDUCE THE AMOUNT OF
 LANDSCAPE ON THE SITE BELOW THE MINIMUM 15%
 REQUIREMENT. THE RESUBMITTED PLANS SHOW FOUNDATION
 LANDSCAPE (AND POSSIBLY A TREE) REMOVED ON THE SOUTH
 SIDE OF THE BUILDING. THE HARDSCAPE PERMIT MUST INCLUDE
 GRAPHIC VERIFICATION THAT NO LANDSCAPE ADJACENT TO THE
 BUILDING IS BEING REMOVED WITH THIS APPLICATION.
  
 6) REPEAT COMMENT: PRIOR TO THE CERTIFICATE OF
 COMPLETION/OCCUPANCY FOR THE DAY CARE, A FENCE PERMIT
 IS REQUIRED FOR ALL THE FENCES AND GATES.
  
 7) REPEAT COMMENT: PRIOR TO THE CERTIFICATE OF
 COMPLETION/OCCUPANCY FOR THE DAY CARE, A PARKING LOT
 STRIPING PERMIT IS REQUIRED FOR THE INSTALLATION OF THE
 DROP OFF SPACES.
  
 5) REPEAT COMMENT: PRIOR TO THE CERTIFICATE OF
 COMPLETION/OCCUPANCY FOR THE DAY CARE, A MINOR
 AMENDMENT MUST BE SUBMITTED TO AND APPROVED BY THE
 PLANNING DIVISION FOR THE CHANGES TO THE EXTERIOR OF
 THE SITE (FENCES, RELOCATED BICYCLE RACK, RELOCATED
 DROP OFF SPACES, ETC.).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By eschneid Date 2018-06-26 Time 14:30 Rev Time 1.00
Received By eschneid Date 2018-06-26 Time 12:04 Sent To  
Notes
2018-06-26 14:28:36FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE MECHANICAL PLANS INDICATE THAT RTU 3-8 ARE NEW
 INSTALLATIONS. PLEASE PROVIDE VERIFICATION THAT THE NEW
 RTU'S (INCLUDING CURB HEIGHT) CONFORM TO THE FOLLOWING
 REQUIREMENT OF THE SEDONA COMMONS DEVELOPMENT ORDER -
 "ALL GROUND AND ROOF MOUNTED AIR CONDITIONING,
 MECHANICAL EQUIPMENT, SATELLITE DISHES, GENERATORS,
 ETC., SHALL BE SCREENED FROM VIEW ON ALL SIDES BY A
 VISUALLY OPAQUE BARRIER CONSISTENT WITH THE COLOR,
 CHARACTER AND ARCHITECTURAL STYLE OF THE STRUCTURES OR
 EQUIVALENT LANDSCAPE MATERIAL. THE HEIGHT OF THE OPAQUE
 BARRIER SHALL BE AS REQUIRED TO PROVIDE AMPLE
 SCREENING".
  
 2) THE FOLLOWING SEPARATE BUILDING PERMITS ARE REQUIRED
 TO BE SUBMITTED PRIOR TO ZONING APPROVAL OF THIS
 PERMIT:
  
 A. A BICYCLE RACK/PAD PERMIT. THIS PERMIT MUST SHOW THE
 CORRECT NUMBER AND TYPE OF BICYCLE RACKS AND THE
 ACCURATE DIMENSIONS FOR THE PADS AND THE RACKS ON THE
 PADS. PLEASE NOT THAT THE CURRENTLY PROPOSED BICYCLE
 RACK LOCATION DIRECTLY CONFLICTS WITH AN EXISTING OAK
 TREE AND MUST BE SHOWN IN A DIFFERENT LOCATION.
  
 B. A HARDSCAPE PERMIT. THIS PERMIT MUST INCLUDE THE
 DETAILS OF AND DEMARCATE THE BOUNDARIES OF THE
 "PERMA-GRASS". PLEASE REMEMBER THAT NONE OF THE
 EXISTING LANDSCAPE ADJACENT TO THE BUILDING MAY BE
 REMOVED AS PART OF THIS APPLICATION. THE EXISTING
 LANDSCAPE MAY NOT BE REMOVED SINCE IT IS THE REQUIRED
 LANDSCAPE BUFFER AND FOUNDATION PLANTING. THIS PERMIT
 MUST INCLUDE CALCULATIONS TO VERIFY THAT THE SOD BEING
 REMOVED FOR THE PLAY AREA DOES NOT REDUCE THE AMOUNT OF
 LANDSCAPE ON THE SITE BELOW THE MINIMUM 15%
 REQUIREMENT.
  
 3) A FENCE PERMIT IS REQUIRED FOR ALL THE FENCES AND
 GATES.
  
 4) A PARKING LOT STRIPING PERMIT IS REQUIRED FOR THE
 INSTALLATION OF THE DROP OFF SPACES.
  
 5) PRIOR TO THE CERTIFICATE OF COMPLETION FOR THE DAY
 CARE, A MINOR AMENDMENT MUST BE SUBMITTED TO AND
 APPROVED BY THE PLANNING DIVISION FOR THE CHANGES TO
 THE EXTERIOR OF THE SITE (FENCES, RELOCATED BICYCLE
 RACK, RELOCATED DROP OFF SPACES, ETC.).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]