Plan Review Stops For Permit 18060517 |
Review Stop |
AD |
ADDRESSING |
Rev No |
3 |
Status |
N |
Date |
2019-01-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2019-01-08 |
Time |
12:50 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2019-01-08 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
F |
Date |
2018-10-29 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-10-29 |
Time |
07:05 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-10-29 |
Time |
07:05 |
Sent To |
|
|
Notes |
2018-10-29 07:06:26 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | CLARIFY; IS UNIT 101 (LABCORP) AN EXISTING SPACE? | | | | FOR ADDRESSING FOR NEW UNITS, CONTACT [email protected] | | | | NOTE THAT, IF APPLICANT HAS ALREADY CONTACTED MIKE | | ORIO, PERMIT ISSUANCE WILL NOT BE DELAYED FOR ADDRESS | | ISSUES/ASSIGNMENTS. PLEASE SEND AN EMAIL TO ME WITH THE | | ADDRESSING INFORMATION, CC [email protected], AND THE NEW | | SUITE NUMBER WILL BE ASSIGNED, IF APPLICABLE. | | | | |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2018-07-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-02 |
Time |
07:37 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-02 |
Time |
07:37 |
Sent To |
|
|
Notes |
2018-07-02 07:38:08 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | CLARIFY; IS UNIT 101 (LABCORP) AN EXISTING SPACE? | | | | FOR ADDRESSING FOR NEW UNITS, CONTACT [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2019-02-05 |
|
|
Cont ID |
|
Sent By |
jduprey |
Date |
2019-02-05 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
jduprey |
Date |
2019-02-05 |
Time |
10:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2019-01-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2019-01-08 |
Time |
11:57 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2019-01-08 |
Time |
10:51 |
Sent To |
|
|
Notes |
2019-01-08 11:57:07 | 2017 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 18060517 | | ADD: 770 NORTHPOINT PKWY SUITE: 100 | | CONT: LEIGHTON MCGINN | | TEL: 561-308-2729 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 3RD REVIEW | | DATE: TUES. JAN. 08/2019 | | ACTION: DENIED | | | | 1-3) COMPLIED. | | | | NOTICE. 4X FEE / NOTICE!!!!! FLORIDA STATUTE | | 553.80(2)(B). WITH RESPECT TO EVALUATION OF DESIGN | | PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS | | IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE | | FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT | | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE | | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION | | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, | | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, | | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, | | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS | | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF | | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO | | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH | | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED | | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT | | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS | | REVIEW. | | | | 4) 3RD REQUEST. THE PLANS SHEET A2 SHOWS THERE IS A LAB | | IN THIS TENANT SPACE. RESPONSE INDICATES WILL SUBMIT | | LATER UNDER A SEPARATE PERMIT. TO DO THIS YOU WILL NEED | | TO REMOVE THE LAB FROM THE SCOPE OF WORK. PLEASE BE | | AWARE UNDER THE BUILDING REVIEW AND MECHANICAL REVIEW | | THE REQUIREMENTS FOR A LAB WILL REQUIRE RATED WALLS | | VENTILATION REQUIREMENTS OTHER THAN A OFFICE (BUSINESS | | OCCUPANCY) AND THE REQUIREMENTS UNDER 307 HAZARDOUS | | MATERIAL, TABLE 307.1(1) MAXIMUM ALLOWABLE QUANTITIES | | OF MATERIALS PER CONTROL AREAS. CONTROL AREAS SEE 2017 | | FBC-B SECTION 414.2 CONTROL AREAS. CONTROL AREAS SHALL | | COMPLY WITH SECTIONS 414.2.1 THROUGH414.2.5 AND THE | | FLORIDA FIRE PREVENTION CODE. | | | | 5-6) COMPLIED. | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-10-24 |
|
|
Cont ID |
|
Sent By |
|
Date |
2018-10-24 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
|
Date |
2018-10-24 |
Time |
07:28 |
Sent To |
|
|
Notes |
2018-10-24 10:35:12 | 2017 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 18060517 | | ADD: 770 NORTHPOINT PKWY SUITE: 100 | | CONT: LEIGHTON MCGINN | | TEL: 561-308-2729 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 2ND REVIEW | | DATE: WED. OCT. 24/ 2018 | | ACTION: DENIED | | | | 1) COMPLIED, 2 NEW SETS OF PLANS. COLLATED. VOIDED | | SHEETS REMOVED FROM THE SETS OF PLANS AND NEW SHEETS | | INSERTED. | | | | 2) 2ND REQUEST. THE 1ST ROUND OF COMMENTS INDICATED | | SEPARATE PERMITS REQUIRED FOR BOTH SIDES OF THE TENANT | | SEPARATION WALL AND NEW FILE ROOM TO BE USED FOR TENANT | | 100. WHEREAS SHEET A2 ALSO SHOWS THE SAME AREA IS BEING | | PREPPED FOR A FUTURE RESTROOM. IT IS NOT CLEAR AS TO | | HOW MANY SQUARE FEET ARE GOING TO BE PART OF THE TENANT | | SPACE # 100. THE CODE SUMMARY ON SHEET A1 INDICATES A | | TOTAL OF 8448 SQUARE FEET IN TENANT SPACE # 100. PLEASE | | NOTE WITH THE ADDITIONAL SQUARE FOOTAGE OF THE STORAGE | | ROOM THE OCCUPANT LOAD WOULD ALSO INCREASE ABOVE THE | | OCCUPANT LOAD INDICATED 85. WHEREAS SHEET A2 INDICATES | | 8924 SQ. FT.? DISCREPANCY IN PLANS. ADDITIONAL | | INFORMATION IS REQUIRED. 107.2.1. | | | | 3) 2ND REQUEST. THE RESPONSE INDICATED THE CONTRACTOR | | WILL SUPPLY VALUE FOR THE PROJECT. ORIGINAL COMMENT, | | THE VALUE APPEARS LOW WEST PALM BEACH AMENDMENT 109. | | | | 4) THE PLANS SHEET A2 SHOWS THERE IS A LAB IN THIS | | TENANT SPACE. RESPONSE INDICATES WILL SUBMIT LATER | | UNDER A SEPARATE PERMIT. TO DO THIS YOU WILL NEED TO | | REMOVE THE LAB FROM THE SCOPE OF WORK. PLEASE BE AWARE | | UNDER THE BUILDING REVIEW AND MECHANICAL REVIEW THE | | REQUIREMENTS FOR A LAB WILL REQUIRE RATED WALLS | | VENTILATION REQUIREMENTS OTHER THAN A OFFICE (BUSINESS | | OCCUPANCY) AND THE REQUIREMENTS UNDER 307 HAZARDOUS | | MATERIAL, TABLE 307.1(1) MAXIMUM ALLOWABLE QUANTITIES | | OF MATERIALS PER CONTROL AREAS. CONTROL AREAS SEE 2017 | | FBC-B SECTION 414.2 CONTROL AREAS. CONTROL AREAS SHALL | | COMPLY WITH SECTIONS 414.2.1 THROUGH414.2.5 AND THE | | FLORIDA FIRE PREVENTION CODE. | | | | 5) 2ND REQUEST. PLEASE INDICATE UNDER THE 2017 | | FBC-EXISTING BUILDING CODE SECTION 301.1 REVISE PLANS | | TO INDICATE WHICH COMPLIANCE METHOD WAS USED IN | | DEVELOPING THE PLANS. THE RESPONSE LETTER STATES THIS | | ALTERATION IS A LEVEL 2. PLEASE NOTE THIS NOTE DOES NOT | | APPEAR ON SHEET A1 UNDER THE HEADING CODE SUMMARY. | | 107.2.1 ADDITIONAL INFORMATION IS REQUIRED. | | | | 6) 2ND REQUEST. CODE ANALYSIS, SEMI COMPLIED. . PLEASE | | NOTE THIS NOTE DOES NOT APPEAR ON SHEET A1 UNDER THE | | HEADING CODE SUMMARY. 107.2.1 ADDITIONAL INFORMATION IS | | REQUIRED. WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | DEVELOPMENT SERVICES HOME PAGE | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-07-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-02 |
Time |
07:47 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-02 |
Time |
07:47 |
Sent To |
|
|
Notes |
2018-07-02 07:48:09 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED | | SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | 2. SEPARATE PERMITS ARE REQUIRED FOR EACH SUITE, FBC | | 107. PROVIDE VALUE FOR EACH UNIT. | | | | 3. VALUE APPEARS LOW; PROVIDE CONTRACT AND COST | | BREAKDOWN FBC 109. | | | | 4. FBC B 307, REVISE PLAN TO INDICATE PRODUCTS USED IN | | LAB, AMOUNTS. | | | | 5. FBC EB 301.1, REVISE PLAN TO INDICATE METHOD | | SELECTED. | | | | 6. NO FIRE RATED WALLS ARE SHOWN. INFORMATION ABOUT THE | | BUILDING, TYPICALLY CALLED A "CODE SUMMARY", WAS NOT | | PROVIDED - SPRINKLERED OR NOT, FIRE ALARM, BUILDING | | TYPE, AREA, ETC. NOT PROVIDED. FBC EB 803.6, THIS | | BUILDING WAS CONSTRUCTED WHEN TENANT SEPARATION AND | | OCCUPANCY SEPARATIONS WERE REQUIRED. COMPLIANCE WITH | | FLORIDA BUILDING CODE 2017, BUILDING NOT CLEAR; EITHER | | PROVIDE TENANT SEPARATION OR REVISE PLAN TO SHOW THAT | | THIS IS NOT REQUIRED. | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2019-02-13 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-02-13 |
Time |
09:59 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-02-13 |
Time |
09:59 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2019-01-29 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-01-29 |
Time |
12:42 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-01-29 |
Time |
12:42 |
Sent To |
|
|
Notes |
2019-01-29 12:41:59 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. SHEET E0.1 MISSING FROM BOTH SETS, SO NOW MISSING | | ALL NOTES AND CODE DATA. PROVIDE CORRECTION. WPB FBC | | 107.1, 107.2.1 | | 2. PROVIDE NOTE THAT ALL PATIENT CARE AREAS WILL BE | | WIRED PER NEC 517.13. IDENTIFY THOSE AREAS ON PLAN. NEC | | 517.13; WPB FBC 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-01-29 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-07-25 |
Time |
15:35 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-07-25 |
Time |
15:00 |
Sent To |
|
|
Notes |
2019-01-29 12:42:33 | CHANGED STATUS TO FAIL ON SECOND REVIEW. |
|
|
Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
Rev No |
1 |
Status |
P |
Date |
2019-04-16 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-04-16 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-04-16 |
Time |
12:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2019-01-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-01-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-01-22 |
Time |
13:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-09-14 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-09-14 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-09-13 |
Time |
15:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2018-06-15 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-06-15 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-06-15 |
Time |
13:27 |
Sent To |
|
|
Notes |
2018-06-15 16:08:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) THERE ARE NO INDICATIONS THAT THE PROPOSED PROJECT | | WAS REVIEWED OR WILL BE BUILT IN COMPLIANCE WITH ANY | | FIRE CODE | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | APPLICABLE CODES OR STANDARDS. | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | OF NFPA 13, 2013 EDITION. | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | NFPA 72, 2013 EDITION. | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | NFPA 241, 2013 EDITION. | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | OF NFPA 10, 2013 EDITION. | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. | | | | PLEASE PROVIDE AN APPLICABLE REVIEW AND NOTE INDICATING | | ACKNOWLEDGEMENT OF THE ABOVE. | | | | | | | | 2) THERE IS NO INDICATION OF ANY WORK ON THE LIFE | | SAFETY SYSTEMS. | | | | IS THERE EXISTING FIRE ALARM AND/OR FIRE SPRINKLER | | SYSTEM? | | | | PLEASE PROVIDE AN APPLICABLE NOTE. | | | | | | | | 3) ANY WORK ON THE FIRE ALARM OF FIRE SPRINKLER SYSTEM | | SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED | | LIFE SAFETY CONTRACTORS. | | | | PLEASE PROVIDE AN APPLICABLE NOTE. | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2019-02-13 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-02-08 |
Time |
14:24 |
Sent To |
|
|
Notes |
2019-02-12 10:31:46 | ROUTED TO JPEARSON | 2019-02-11 14:24:33 | RESUB ROUTED TO JESMITH |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2019-02-05 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2019-02-05 |
Time |
12:11 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2019-02-05 |
Time |
12:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-01-10 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2019-01-10 |
Time |
12:58 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-12-07 |
Time |
11:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-10-24 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-10-24 |
Time |
11:41 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-09-07 |
Time |
15:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-08-07 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-08-07 |
Time |
07:19 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-06-12 |
Time |
15:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2018-08-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-09 |
Time |
18:55 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-09 |
Time |
18:55 |
Sent To |
|
|
Notes |
2018-08-09 18:56:16 | NOT REQUIRED PER EMAIL FROM WILLIE SWOOPE | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2019-01-28 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-01-28 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-01-28 |
Time |
13:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2019-01-03 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-01-03 |
Time |
08:07 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-01-03 |
Time |
07:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2018-10-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-10-10 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-10-10 |
Time |
11:32 |
Sent To |
|
|
Notes |
2018-10-10 11:42:06 | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT #18060517 | | 10/10/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) IN RESPONSE TO COMMENT #2 FRO THE 1ST REVIEW WHICH | | IS PRINTED BELOW, THE EOR IS STATING IN RESPONSE THAT A | | LETTER FROM THE OWNERSHIP IS TO BE PROVIDED TO ADDRESS | | THE USE OF THE LAB ROOM. THE LETTER WAS NOT SUBMITTED. | | PLEASE NOTE RHAT A LAB ROOM SHALL BE PROVIDED WITH AN | | EXHAUST VENTILATION SYSTEM, AND AIR RECIRCULATED FROM | | THE ROOM SHALL BE LIMITED TO 10%- SEE TABLE 403.3.1.1 | | AND FOOTNOTE G | | | | 2) THE PLANS SHOW A LAB ROOM. REFER TO SECTION 510.1 | | FBC M AND CLARIFY WHAT PROCESSES ARE TO TAKE PLACE IN | | THE ROOM, AND WHAT CHEMICALS, IF ANY, ARE STORED IN THE | | ROOM AND THEIR QUANTITIES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-06-25 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-06-25 |
Time |
17:53 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-06-25 |
Time |
17:03 |
Sent To |
|
|
Notes |
2018-06-25 17:55:45 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18060517 | | 6/25/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL NEW | | ROOMS AND SPACES- SECTION 809.2 FBC EX, AND TABLE | | 403.3.1.1 FBC M. | | | | 2) THE PLANS SHOW A LAB ROOM. REFER TO SECTION 510.1 | | FBC M AND CLARIFY WHAT PROCESSES ARE TO TAKE PLACE IN | | THE ROOM, AND WHAT CHEMICALS, IF ANY, ARE STORED IN THE | | ROOM AND THEIR QUANTITIES. | | | | 3) THERE ARE TWO EXISTING AC TRUNK LINES ON THE EAST | | AND WEST SIDE OF THE SPACE THAT DO NOT SHOW ANY | | CONTINUATIONS TO AIR HANDLER UNITS. PLEASE PROVIDE | | NOTES TO CLARIFY. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO | | NSERVICES | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2019-02-12 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2019-02-12 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2019-02-12 |
Time |
10:26 |
Sent To |
|
|
Notes |
2019-02-12 10:29:17 | APPROVED | | ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S | | APPROVAL | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2019-02-05 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2019-02-05 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2019-02-05 |
Time |
12:05 |
Sent To |
|
|
Notes |
2019-02-05 12:05:52 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | FAC= FLORIDA ADMINISTRATIVE CODE | | FS = FLORIDA STATUTES | | | | 4TH REVIEW; DENIED | | | | COMMENTS NOTED BELOW ARE A RESTATEMENT OF PREVIOUS | | COMMENTS WHICH HAVE NOT BEEN ADDRESSED. | | 1. RE: PLAN SHEET P0.1; PLUMBING FIXTURE SCHEDULE, | | HLAV. SPECIFY IN THE FIXTURE DESCRIPTION AN APPROVED | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | 1070 OR CSA B125.3. TO COMPLY WITH FBC PL 416.5 PER WPB | | FPC 107.2.1. | | 2. PROVIDE A DETAIL OF THE WATER HEATER AND HOT WATER | | RECIRC PUMP SHOWING THE FOLLOWING IN ACCORDANCE WITH | | WPB FBC 107.2.1: | | A) COLD AND COLD WATER PIPING ARRANGEMENT INCLUDING ALL | | VALVES IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL | | CHAPTER 6 | | B) THERMAL EXPANSION DEVICE REQUIRED ON COLD WATER | | SUPPLY TO WATER HEATER IN ACCORDANCE WITH FBC PL 607.3 | | C) T&P RELIEF VALVE AND DISCHARGE INCLUDING TERMINATION | | IN ACCORDANCE WITH FBC PL 504.1, 504.4, 504.4.1, 504.5 | | AND 504.6 504.7, 504.7.1 AND 504.7.2. | | D) WATER HEATER PAN AND DRAIN INCLUDING TERMINATION IN | | ACCORDANCE WITH FBC PL 504.7, 504.7.1 AND 504.7.2. | | | | PLEASE NOTE THAT SUBMITTED PLAN PAGE P0.1 IS REV 1 | | DATED 8/30/18 AND IT WAS NOTED ON THE LAST REVIEW THAT | | THERE WERE TWO (2) PLAN PAGES P0.1 ONE OF WHICH WAS REV | | 1 AND THE OTHER WHICH WAS REV 2. IT IS POSSIBLE THAT | | THE WRONG P0.1 WAS SUBMITTED AND THAT THE P0.1 REV 2 | | HAS THE REQUIRED INFORMATION. | | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY | | RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING, | | IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING | | EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | REMAIN IN PACKAGE AND BE MARKED "VOID". | | | | JERALD SMITH | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | EMAIL [email protected] | | PHONE 561-805-6715 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2019-01-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2019-01-09 |
Time |
08:14 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2019-01-08 |
Time |
11:58 |
Sent To |
|
|
Notes |
2019-01-09 08:14:32 | 2017 FBC- PLUMBING PLAN REVIEW | | W. P. B. PERMIT: 18060517 | | ADD: 770 NORTHPOINT PKWY SUITE: 100 | | CONT: LEIGHTON MCGINN | | TEL: 561-308-2729 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 3RD REVIEW | | DATE: TUES. JAN. 08/2019 | | ACTION: DENIED | | | | 1A) 3RD REVIEW/ SEMI-COMPLIED. SHEET A2 DOES SHOW A | | NOTE THAT EXAM ROOM # 4 IS AN ACCESSIBLE EXAM ROOM. | | PLEASE NOTE THERE IS NO CLEAR FLOOR SPACE INDICATED ON | | THE FLOOR PLAN SHOWING COMPLIANCE WITH THE 2017 | | FBC-ACCESSIBILITY CODE SECTION606.2 CLEAR FLOOR SPACE. | | SHEET A3 DETAIL: 6 DOES INDICATE THIS IS THE ACCESSIBLE | | EXAM ROOM, BUT THE SINK IS SHOWN AT 36 INCHES ABOVE THE | | FINISH FLOOR, NOT IN COMPLIANCE WITH ACCESS. CODE | | SECTION 606.3 HEIGHT OF NO MORE THAN 34 INCHES ABOVE | | GRADE. THE PLANS WILL ALSO NEED TO SHOW COMPLIANCE WITH | | 606.4 FAUCET AND 606.5 EXPOSED PIPES AND SURFACES. | | | | 1B) NEW COMMENT. THERE ARE 2 P0.1 PLANS IN THE PLANS. | | ONE SHEET SHOW REVISION # 1 AND THE OTHER REVISION # 1 | | & 2. WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | AS NECESSARY. | | | | 2A-D) COMPLIED. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2018-10-09 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2018-10-09 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2018-10-09 |
Time |
13:05 |
Sent To |
|
|
Notes |
2018-10-09 13:07:28 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | FAC= FLORIDA ADMINISTRATIVE CODE | | FS = FLORIDA STATUTES | | | | 2ND REVIEW: | | PLUMBING COMMENTS: DENIED | | | | 1. THE ACCESSIBILITY CODE REQUIRES A MINIMUM OF 1 SINK | | IN EACH TYPE OF ACCESSIBLE ROOM COMPLY WITH FBC ACC 606 | | PER FBC ACC 212.3. THIS IS A SECOND REQUEST. PLEASE | | NOTE THAT THE ARCHITECT HAS NOT PROVIDED THIS | | INFORMATION ON THE PLANS AND NEEDS TO DO SO BEFORE THE | | PLUMBING PERMIT APPLICATION CAN BE APPROVED. THE | | PROVIDED INFORMATION BY THE ARCHITECT NEEDS TO INCLUDE | | SUCH THINGS AS THE DESIGNATED ACCESSIBLE ROOM (IE. EXAM | | RM #4), MILL WORK PLAN AND ELEVATION VIEWS, AND | | POSSIBLY ANOTHER DESIGNATED PLUMBING FIXTURE IN THE | | PLUMBING FIXTURE SCHEDULE. | | 2. RE: PLAN SHEET P0.1; PLUMBING FIXTURE SCHEDULE, | | HLAV. SPECIFY IN THE FIXTURE DESCRIPTION AN APPROVED | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | 1070 OR CSA B125.3. TO COMPLY WITH FBC PL 416.5 PER WPB | | FPC 107.2.1. THIS IS A SECOND REQUEST. | | 3. PROVIDE A DETAIL OF THE WATER HEATER AND HOT WATER | | RECIRC PUMP SHOWING THE FOLLOWING IN ACCORDANCE WITH | | WPB FBC 107.2.1: | | A. HOT AND COLD WATER PIPING ARRANGEMENT INCLUDING ALL | | VALVES IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL | | CHAPTER 6. | | B. THERMAL EXPANSION DEVICE REQUIRED ON COLD WATER | | SUPPLY TO WATER HEATER IN ACCORDANCE WITH FBC PL 607.3 | | C. T&P RELIEF VALVE AND DISCHARGE INCLUDING TERMINATION | | IN ACCORDANCE WITH FBC PL 504.1, 504.4, 504.4.1, 504.5 | | AND 504.6 504.7, 504.7.1 AND 504.7.2. | | D. WATER HEATER PAN AND DRAIN INCLUDING TERMINATION IN | | ACCORDANCE WITH FBC PL 504.7, 504.7.1 AND 504.7.2. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". | | | | | | JERALD SMITH | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | EMAIL [email protected] | | PHONE 561-805-6715 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-08-07 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-08-03 |
Time |
14:22 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-08-03 |
Time |
09:11 |
Sent To |
|
|
Notes |
2018-08-07 07:18:59 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. THE ACCESSIBILITY CODE REQUIRES A MINIMUM OF 1 SINK | | IN EACH TYPE OF ACCESSIBLE ROOM COMPLY WITH FBC ACC | | 606. PER FBC ACC 212.3 | | | | 2. SHT. P0.1 THE SANITARY ISOMETRIC IS MISSING THE | | FOLLOWING PLUMBING FIXTURES, ALL THE SINKS IN THE SONO | | ROOMS, THE LAVATORY AND URINAL IN THE MENS BATHROOM | | PLEASE CLARIFY, PER WPB AMEND TO FBC 107.2.1 | | | | 3. SHT. P0.1 BOTH THE SANITARY AND WATER ISOMETRIC | | DRAWING ARE TO COMPACT AND CONGESTED TO DETERMINE CODE | | COMPLIANCE PLEASE EXPAND THE SANITARY AND WATER | | ISOMETRIC DRAWINGS, PER WPB AMEND TO FBC 107.2.1 | | | | 4. SHT. P0.1 THE SANITARY ISOMETRIC THE SINK IN EXAM | | ROOM #4 AND LAB SHALL CONNECT TO THE BUILDING DRAIN | | SEPARATELY THE THE BATHROOM GROUP. PER FBC PL 912.1 | | | | 5. ALL LAVATORY'S USED BY THE PUBLIC SHALL HAVE ONLY | | TEMPERED WATER AND SHALL BE DELIVERED THROUGH AN | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 | | | | 6. SHT. P0.1 THE WATER ISOMETRIC IS MISSING THE | | FOLLOWING PLUMBING FIXTURES, THE MEN AND WOMENS | | BATHROOMS M PLEASE CLARIFY, PER WPB AMEND TO FBC | | 107.2.1 | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|