Plan Review Details - Permit 18060517
Plan Review Stops For Permit 18060517
Review Stop AD ADDRESSING
Rev No 3 Status N Date 2019-01-08 Cont ID  
Sent By jwitmer Date 2019-01-08 Time 12:50 Rev Time 0.00
Received By jwitmer Date 2019-01-08 Time   Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2018-10-29 Cont ID  
Sent By shill Date 2018-10-29 Time 07:05 Rev Time 0.00
Received By shill Date 2018-10-29 Time 07:05 Sent To  
Notes
2018-10-29 07:06:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 CLARIFY; IS UNIT 101 (LABCORP) AN EXISTING SPACE?
  
 FOR ADDRESSING FOR NEW UNITS, CONTACT [email protected]
  
 NOTE THAT, IF APPLICANT HAS ALREADY CONTACTED MIKE
 ORIO, PERMIT ISSUANCE WILL NOT BE DELAYED FOR ADDRESS
 ISSUES/ASSIGNMENTS. PLEASE SEND AN EMAIL TO ME WITH THE
 ADDRESSING INFORMATION, CC [email protected], AND THE NEW
 SUITE NUMBER WILL BE ASSIGNED, IF APPLICABLE.
  
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-07-02 Cont ID  
Sent By shill Date 2018-07-02 Time 07:37 Rev Time 0.00
Received By shill Date 2018-07-02 Time 07:37 Sent To  
Notes
2018-07-02 07:38:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 CLARIFY; IS UNIT 101 (LABCORP) AN EXISTING SPACE?
  
 FOR ADDRESSING FOR NEW UNITS, CONTACT [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-02-05 Cont ID  
Sent By jduprey Date 2019-02-05 Time 10:39 Rev Time 0.00
Received By jduprey Date 2019-02-05 Time 10:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-01-08 Cont ID  
Sent By jwitmer Date 2019-01-08 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2019-01-08 Time 10:51 Sent To  
Notes
2019-01-08 11:57:072017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18060517
 ADD: 770 NORTHPOINT PKWY SUITE: 100
 CONT: LEIGHTON MCGINN
 TEL: 561-308-2729
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JAN. 08/2019
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 NOTICE. 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B). WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
 4) 3RD REQUEST. THE PLANS SHEET A2 SHOWS THERE IS A LAB
 IN THIS TENANT SPACE. RESPONSE INDICATES WILL SUBMIT
 LATER UNDER A SEPARATE PERMIT. TO DO THIS YOU WILL NEED
 TO REMOVE THE LAB FROM THE SCOPE OF WORK. PLEASE BE
 AWARE UNDER THE BUILDING REVIEW AND MECHANICAL REVIEW
 THE REQUIREMENTS FOR A LAB WILL REQUIRE RATED WALLS
 VENTILATION REQUIREMENTS OTHER THAN A OFFICE (BUSINESS
 OCCUPANCY) AND THE REQUIREMENTS UNDER 307 HAZARDOUS
 MATERIAL, TABLE 307.1(1) MAXIMUM ALLOWABLE QUANTITIES
 OF MATERIALS PER CONTROL AREAS. CONTROL AREAS SEE 2017
 FBC-B SECTION 414.2 CONTROL AREAS. CONTROL AREAS SHALL
 COMPLY WITH SECTIONS 414.2.1 THROUGH414.2.5 AND THE
 FLORIDA FIRE PREVENTION CODE.
  
 5-6) COMPLIED.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-24 Cont ID  
Sent By   Date 2018-10-24 Time 10:45 Rev Time 0.00
Received By   Date 2018-10-24 Time 07:28 Sent To  
Notes
2018-10-24 10:35:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18060517
 ADD: 770 NORTHPOINT PKWY SUITE: 100
 CONT: LEIGHTON MCGINN
 TEL: 561-308-2729
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. OCT. 24/ 2018
 ACTION: DENIED
  
 1) COMPLIED, 2 NEW SETS OF PLANS. COLLATED. VOIDED
 SHEETS REMOVED FROM THE SETS OF PLANS AND NEW SHEETS
 INSERTED.
  
 2) 2ND REQUEST. THE 1ST ROUND OF COMMENTS INDICATED
 SEPARATE PERMITS REQUIRED FOR BOTH SIDES OF THE TENANT
 SEPARATION WALL AND NEW FILE ROOM TO BE USED FOR TENANT
 100. WHEREAS SHEET A2 ALSO SHOWS THE SAME AREA IS BEING
 PREPPED FOR A FUTURE RESTROOM. IT IS NOT CLEAR AS TO
 HOW MANY SQUARE FEET ARE GOING TO BE PART OF THE TENANT
 SPACE # 100. THE CODE SUMMARY ON SHEET A1 INDICATES A
 TOTAL OF 8448 SQUARE FEET IN TENANT SPACE # 100. PLEASE
 NOTE WITH THE ADDITIONAL SQUARE FOOTAGE OF THE STORAGE
 ROOM THE OCCUPANT LOAD WOULD ALSO INCREASE ABOVE THE
 OCCUPANT LOAD INDICATED 85. WHEREAS SHEET A2 INDICATES
 8924 SQ. FT.? DISCREPANCY IN PLANS. ADDITIONAL
 INFORMATION IS REQUIRED. 107.2.1.
  
 3) 2ND REQUEST. THE RESPONSE INDICATED THE CONTRACTOR
 WILL SUPPLY VALUE FOR THE PROJECT. ORIGINAL COMMENT,
 THE VALUE APPEARS LOW WEST PALM BEACH AMENDMENT 109.
  
 4) THE PLANS SHEET A2 SHOWS THERE IS A LAB IN THIS
 TENANT SPACE. RESPONSE INDICATES WILL SUBMIT LATER
 UNDER A SEPARATE PERMIT. TO DO THIS YOU WILL NEED TO
 REMOVE THE LAB FROM THE SCOPE OF WORK. PLEASE BE AWARE
 UNDER THE BUILDING REVIEW AND MECHANICAL REVIEW THE
 REQUIREMENTS FOR A LAB WILL REQUIRE RATED WALLS
 VENTILATION REQUIREMENTS OTHER THAN A OFFICE (BUSINESS
 OCCUPANCY) AND THE REQUIREMENTS UNDER 307 HAZARDOUS
 MATERIAL, TABLE 307.1(1) MAXIMUM ALLOWABLE QUANTITIES
 OF MATERIALS PER CONTROL AREAS. CONTROL AREAS SEE 2017
 FBC-B SECTION 414.2 CONTROL AREAS. CONTROL AREAS SHALL
 COMPLY WITH SECTIONS 414.2.1 THROUGH414.2.5 AND THE
 FLORIDA FIRE PREVENTION CODE.
  
 5) 2ND REQUEST. PLEASE INDICATE UNDER THE 2017
 FBC-EXISTING BUILDING CODE SECTION 301.1 REVISE PLANS
 TO INDICATE WHICH COMPLIANCE METHOD WAS USED IN
 DEVELOPING THE PLANS. THE RESPONSE LETTER STATES THIS
 ALTERATION IS A LEVEL 2. PLEASE NOTE THIS NOTE DOES NOT
 APPEAR ON SHEET A1 UNDER THE HEADING CODE SUMMARY.
 107.2.1 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) 2ND REQUEST. CODE ANALYSIS, SEMI COMPLIED. . PLEASE
 NOTE THIS NOTE DOES NOT APPEAR ON SHEET A1 UNDER THE
 HEADING CODE SUMMARY. 107.2.1 ADDITIONAL INFORMATION IS
 REQUIRED. WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-02 Cont ID  
Sent By shill Date 2018-07-02 Time 07:47 Rev Time 0.00
Received By shill Date 2018-07-02 Time 07:47 Sent To  
Notes
2018-07-02 07:48:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. SEPARATE PERMITS ARE REQUIRED FOR EACH SUITE, FBC
 107. PROVIDE VALUE FOR EACH UNIT.
  
 3. VALUE APPEARS LOW; PROVIDE CONTRACT AND COST
 BREAKDOWN FBC 109.
  
 4. FBC B 307, REVISE PLAN TO INDICATE PRODUCTS USED IN
 LAB, AMOUNTS.
  
 5. FBC EB 301.1, REVISE PLAN TO INDICATE METHOD
 SELECTED.
  
 6. NO FIRE RATED WALLS ARE SHOWN. INFORMATION ABOUT THE
 BUILDING, TYPICALLY CALLED A "CODE SUMMARY", WAS NOT
 PROVIDED - SPRINKLERED OR NOT, FIRE ALARM, BUILDING
 TYPE, AREA, ETC. NOT PROVIDED. FBC EB 803.6, THIS
 BUILDING WAS CONSTRUCTED WHEN TENANT SEPARATION AND
 OCCUPANCY SEPARATIONS WERE REQUIRED. COMPLIANCE WITH
 FLORIDA BUILDING CODE 2017, BUILDING NOT CLEAR; EITHER
 PROVIDE TENANT SEPARATION OR REVISE PLAN TO SHOW THAT
 THIS IS NOT REQUIRED.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-02-13 Cont ID  
Sent By jpearson Date 2019-02-13 Time 09:59 Rev Time 0.00
Received By jpearson Date 2019-02-13 Time 09:59 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-01-29 Cont ID  
Sent By jpearson Date 2019-01-29 Time 12:42 Rev Time 0.00
Received By jpearson Date 2019-01-29 Time 12:42 Sent To  
Notes
2019-01-29 12:41:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E0.1 MISSING FROM BOTH SETS, SO NOW MISSING
 ALL NOTES AND CODE DATA. PROVIDE CORRECTION. WPB FBC
 107.1, 107.2.1
 2. PROVIDE NOTE THAT ALL PATIENT CARE AREAS WILL BE
 WIRED PER NEC 517.13. IDENTIFY THOSE AREAS ON PLAN. NEC
 517.13; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-29 Cont ID  
Sent By jpearson Date 2018-07-25 Time 15:35 Rev Time 0.00
Received By jpearson Date 2018-07-25 Time 15:00 Sent To  
Notes
2019-01-29 12:42:33CHANGED STATUS TO FAIL ON SECOND REVIEW.

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-04-16 Cont ID  
Sent By jpearson Date 2019-04-16 Time 12:41 Rev Time 0.00
Received By jpearson Date 2019-04-16 Time 12:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-01-22 Cont ID  
Sent By pleduc Date 2019-01-22 Time   Rev Time 0.00
Received By pleduc Date 2019-01-22 Time 13:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-14 Cont ID  
Sent By pleduc Date 2018-09-14 Time   Rev Time 0.00
Received By pleduc Date 2018-09-13 Time 15:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By pleduc Date 2018-06-15 Time   Rev Time 0.00
Received By pleduc Date 2018-06-15 Time 13:27 Sent To  
Notes
2018-06-15 16:08:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO INDICATIONS THAT THE PROPOSED PROJECT
 WAS REVIEWED OR WILL BE BUILT IN COMPLIANCE WITH ANY
 FIRE CODE
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
  
 PLEASE PROVIDE AN APPLICABLE REVIEW AND NOTE INDICATING
 ACKNOWLEDGEMENT OF THE ABOVE.
  
  
  
 2) THERE IS NO INDICATION OF ANY WORK ON THE LIFE
 SAFETY SYSTEMS.
  
 IS THERE EXISTING FIRE ALARM AND/OR FIRE SPRINKLER
 SYSTEM?
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
 3) ANY WORK ON THE FIRE ALARM OF FIRE SPRINKLER SYSTEM
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED
 LIFE SAFETY CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2019-02-13 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-08 Time 14:24 Sent To  
Notes
2019-02-12 10:31:46ROUTED TO JPEARSON
2019-02-11 14:24:33RESUB ROUTED TO JESMITH

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-02-05 Cont ID  
Sent By jesmith Date 2019-02-05 Time 12:11 Rev Time 0.00
Received By jesmith Date 2019-02-05 Time 12:11 Sent To  
Notes
2019-01-18 14:36:26B22

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-10 Cont ID  
Sent By cpuell Date 2019-01-10 Time 12:58 Rev Time 0.00
Received By cpuell Date 2018-12-07 Time 11:23 Sent To  
Notes
2018-12-10 11:25:02B22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-24 Cont ID  
Sent By cpuell Date 2018-10-24 Time 11:41 Rev Time 0.00
Received By cpuell Date 2018-09-07 Time 15:28 Sent To  
Notes
2018-09-11 15:28:52B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-07 Cont ID  
Sent By gjohnson Date 2018-08-07 Time 07:19 Rev Time 0.00
Received By gjohnson Date 2018-06-12 Time 15:22 Sent To  
Notes
2018-06-13 15:22:20B22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-08-09 Cont ID  
Sent By shill Date 2018-08-09 Time 18:55 Rev Time 0.00
Received By shill Date 2018-08-09 Time 18:55 Sent To  
Notes
2018-08-09 18:56:16NOT REQUIRED PER EMAIL FROM WILLIE SWOOPE
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-01-28 Cont ID  
Sent By ccole Date 2019-01-28 Time 13:59 Rev Time 0.00
Received By ccole Date 2019-01-28 Time 13:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-01-03 Cont ID  
Sent By ccole Date 2019-01-03 Time 08:07 Rev Time 0.00
Received By ccole Date 2019-01-03 Time 07:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-10 Cont ID  
Sent By ccole Date 2018-10-10 Time 11:32 Rev Time 0.00
Received By ccole Date 2018-10-10 Time 11:32 Sent To  
Notes
2018-10-10 11:42:062ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18060517
 10/10/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO COMMENT #2 FRO THE 1ST REVIEW WHICH
 IS PRINTED BELOW, THE EOR IS STATING IN RESPONSE THAT A
 LETTER FROM THE OWNERSHIP IS TO BE PROVIDED TO ADDRESS
 THE USE OF THE LAB ROOM. THE LETTER WAS NOT SUBMITTED.
 PLEASE NOTE RHAT A LAB ROOM SHALL BE PROVIDED WITH AN
 EXHAUST VENTILATION SYSTEM, AND AIR RECIRCULATED FROM
 THE ROOM SHALL BE LIMITED TO 10%- SEE TABLE 403.3.1.1
 AND FOOTNOTE G
  
 2) THE PLANS SHOW A LAB ROOM. REFER TO SECTION 510.1
 FBC M AND CLARIFY WHAT PROCESSES ARE TO TAKE PLACE IN
 THE ROOM, AND WHAT CHEMICALS, IF ANY, ARE STORED IN THE
 ROOM AND THEIR QUANTITIES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-25 Cont ID  
Sent By ccole Date 2018-06-25 Time 17:53 Rev Time 0.00
Received By ccole Date 2018-06-25 Time 17:03 Sent To  
Notes
2018-06-25 17:55:451ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18060517
 6/25/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL NEW
 ROOMS AND SPACES- SECTION 809.2 FBC EX, AND TABLE
 403.3.1.1 FBC M.
  
 2) THE PLANS SHOW A LAB ROOM. REFER TO SECTION 510.1
 FBC M AND CLARIFY WHAT PROCESSES ARE TO TAKE PLACE IN
 THE ROOM, AND WHAT CHEMICALS, IF ANY, ARE STORED IN THE
 ROOM AND THEIR QUANTITIES.
  
 3) THERE ARE TWO EXISTING AC TRUNK LINES ON THE EAST
 AND WEST SIDE OF THE SPACE THAT DO NOT SHOW ANY
 CONTINUATIONS TO AIR HANDLER UNITS. PLEASE PROVIDE
 NOTES TO CLARIFY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2019-02-12 Cont ID  
Sent By jesmith Date 2019-02-12 Time 10:29 Rev Time 0.00
Received By jesmith Date 2019-02-12 Time 10:26 Sent To  
Notes
2019-02-12 10:29:17APPROVED
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2019-02-05 Cont ID  
Sent By jesmith Date 2019-02-05 Time 12:05 Rev Time 0.00
Received By jesmith Date 2019-02-05 Time 12:05 Sent To  
Notes
2019-02-05 12:05:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 4TH REVIEW; DENIED
  
 COMMENTS NOTED BELOW ARE A RESTATEMENT OF PREVIOUS
 COMMENTS WHICH HAVE NOT BEEN ADDRESSED.
 1. RE: PLAN SHEET P0.1; PLUMBING FIXTURE SCHEDULE,
 HLAV. SPECIFY IN THE FIXTURE DESCRIPTION AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. TO COMPLY WITH FBC PL 416.5 PER WPB
 FPC 107.2.1.
 2. PROVIDE A DETAIL OF THE WATER HEATER AND HOT WATER
 RECIRC PUMP SHOWING THE FOLLOWING IN ACCORDANCE WITH
 WPB FBC 107.2.1:
 A) COLD AND COLD WATER PIPING ARRANGEMENT INCLUDING ALL
 VALVES IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL
 CHAPTER 6
 B) THERMAL EXPANSION DEVICE REQUIRED ON COLD WATER
 SUPPLY TO WATER HEATER IN ACCORDANCE WITH FBC PL 607.3
 C) T&P RELIEF VALVE AND DISCHARGE INCLUDING TERMINATION
 IN ACCORDANCE WITH FBC PL 504.1, 504.4, 504.4.1, 504.5
 AND 504.6 504.7, 504.7.1 AND 504.7.2.
 D) WATER HEATER PAN AND DRAIN INCLUDING TERMINATION IN
 ACCORDANCE WITH FBC PL 504.7, 504.7.1 AND 504.7.2.
  
 PLEASE NOTE THAT SUBMITTED PLAN PAGE P0.1 IS REV 1
 DATED 8/30/18 AND IT WAS NOTED ON THE LAST REVIEW THAT
 THERE WERE TWO (2) PLAN PAGES P0.1 ONE OF WHICH WAS REV
 1 AND THE OTHER WHICH WAS REV 2. IT IS POSSIBLE THAT
 THE WRONG P0.1 WAS SUBMITTED AND THAT THE P0.1 REV 2
 HAS THE REQUIRED INFORMATION.
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING,
 IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-01-09 Cont ID  
Sent By jwitmer Date 2019-01-09 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2019-01-08 Time 11:58 Sent To  
Notes
2019-01-09 08:14:322017 FBC- PLUMBING PLAN REVIEW
 W. P. B. PERMIT: 18060517
 ADD: 770 NORTHPOINT PKWY SUITE: 100
 CONT: LEIGHTON MCGINN
 TEL: 561-308-2729
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JAN. 08/2019
 ACTION: DENIED
  
 1A) 3RD REVIEW/ SEMI-COMPLIED. SHEET A2 DOES SHOW A
 NOTE THAT EXAM ROOM # 4 IS AN ACCESSIBLE EXAM ROOM.
 PLEASE NOTE THERE IS NO CLEAR FLOOR SPACE INDICATED ON
 THE FLOOR PLAN SHOWING COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTION606.2 CLEAR FLOOR SPACE.
 SHEET A3 DETAIL: 6 DOES INDICATE THIS IS THE ACCESSIBLE
 EXAM ROOM, BUT THE SINK IS SHOWN AT 36 INCHES ABOVE THE
 FINISH FLOOR, NOT IN COMPLIANCE WITH ACCESS. CODE
 SECTION 606.3 HEIGHT OF NO MORE THAN 34 INCHES ABOVE
 GRADE. THE PLANS WILL ALSO NEED TO SHOW COMPLIANCE WITH
 606.4 FAUCET AND 606.5 EXPOSED PIPES AND SURFACES.
  
 1B) NEW COMMENT. THERE ARE 2 P0.1 PLANS IN THE PLANS.
 ONE SHEET SHOW REVISION # 1 AND THE OTHER REVISION # 1
 & 2. WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY.
  
 2A-D) COMPLIED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-09 Cont ID  
Sent By jesmith Date 2018-10-09 Time 13:07 Rev Time 0.00
Received By jesmith Date 2018-10-09 Time 13:05 Sent To  
Notes
2018-10-09 13:07:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. THE ACCESSIBILITY CODE REQUIRES A MINIMUM OF 1 SINK
 IN EACH TYPE OF ACCESSIBLE ROOM COMPLY WITH FBC ACC 606
 PER FBC ACC 212.3. THIS IS A SECOND REQUEST. PLEASE
 NOTE THAT THE ARCHITECT HAS NOT PROVIDED THIS
 INFORMATION ON THE PLANS AND NEEDS TO DO SO BEFORE THE
 PLUMBING PERMIT APPLICATION CAN BE APPROVED. THE
 PROVIDED INFORMATION BY THE ARCHITECT NEEDS TO INCLUDE
 SUCH THINGS AS THE DESIGNATED ACCESSIBLE ROOM (IE. EXAM
 RM #4), MILL WORK PLAN AND ELEVATION VIEWS, AND
 POSSIBLY ANOTHER DESIGNATED PLUMBING FIXTURE IN THE
 PLUMBING FIXTURE SCHEDULE.
 2. RE: PLAN SHEET P0.1; PLUMBING FIXTURE SCHEDULE,
 HLAV. SPECIFY IN THE FIXTURE DESCRIPTION AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. TO COMPLY WITH FBC PL 416.5 PER WPB
 FPC 107.2.1. THIS IS A SECOND REQUEST.
 3. PROVIDE A DETAIL OF THE WATER HEATER AND HOT WATER
 RECIRC PUMP SHOWING THE FOLLOWING IN ACCORDANCE WITH
 WPB FBC 107.2.1:
 A. HOT AND COLD WATER PIPING ARRANGEMENT INCLUDING ALL
 VALVES IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL
 CHAPTER 6.
 B. THERMAL EXPANSION DEVICE REQUIRED ON COLD WATER
 SUPPLY TO WATER HEATER IN ACCORDANCE WITH FBC PL 607.3
 C. T&P RELIEF VALVE AND DISCHARGE INCLUDING TERMINATION
 IN ACCORDANCE WITH FBC PL 504.1, 504.4, 504.4.1, 504.5
 AND 504.6 504.7, 504.7.1 AND 504.7.2.
 D. WATER HEATER PAN AND DRAIN INCLUDING TERMINATION IN
 ACCORDANCE WITH FBC PL 504.7, 504.7.1 AND 504.7.2.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-07 Cont ID  
Sent By gjohnson Date 2018-08-03 Time 14:22 Rev Time 0.00
Received By gjohnson Date 2018-08-03 Time 09:11 Sent To  
Notes
2018-08-07 07:18:591ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE ACCESSIBILITY CODE REQUIRES A MINIMUM OF 1 SINK
 IN EACH TYPE OF ACCESSIBLE ROOM COMPLY WITH FBC ACC
 606. PER FBC ACC 212.3
  
 2. SHT. P0.1 THE SANITARY ISOMETRIC IS MISSING THE
 FOLLOWING PLUMBING FIXTURES, ALL THE SINKS IN THE SONO
 ROOMS, THE LAVATORY AND URINAL IN THE MENS BATHROOM
 PLEASE CLARIFY, PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. P0.1 BOTH THE SANITARY AND WATER ISOMETRIC
 DRAWING ARE TO COMPACT AND CONGESTED TO DETERMINE CODE
 COMPLIANCE PLEASE EXPAND THE SANITARY AND WATER
 ISOMETRIC DRAWINGS, PER WPB AMEND TO FBC 107.2.1
  
 4. SHT. P0.1 THE SANITARY ISOMETRIC THE SINK IN EXAM
 ROOM #4 AND LAB SHALL CONNECT TO THE BUILDING DRAIN
 SEPARATELY THE THE BATHROOM GROUP. PER FBC PL 912.1
  
 5. ALL LAVATORY'S USED BY THE PUBLIC SHALL HAVE ONLY
 TEMPERED WATER AND SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 6. SHT. P0.1 THE WATER ISOMETRIC IS MISSING THE
 FOLLOWING PLUMBING FIXTURES, THE MEN AND WOMENS
 BATHROOMS M PLEASE CLARIFY, PER WPB AMEND TO FBC
 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  