Plan Review Stops For Permit 18060384 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2018-08-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-14 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-14 |
Time |
12:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2018-08-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-04 |
Time |
13:16 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-04 |
Time |
13:16 |
Sent To |
|
|
Notes |
2018-08-04 13:17:16 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | COMMENTS FROM PREVIOUS LIST: | | | | 1. FBC 109, VALUE IS TO INCLUDE ALL LABOR, MATERIALS, | | OVERHEAD, PROFIT, INCLUDING MATERIALS PROVIDED BY | | OTHERS. | | | | 2ND REVIEW, PROVIDE A COPY OF THE CONTRACT AND COST | | BREAKDOWN. NO INFORMATION WAS PROVIDED, VALUE NOT | | CHANGED. | | | | THIS MAY BE PROVIDED VIA EMAIL. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-07-30 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-30 |
Time |
18:20 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-30 |
Time |
18:20 |
Sent To |
|
|
Notes |
2018-07-30 18:20:49 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | COMMENTS FROM PREVIOUS LIST: | | | | 1. FBC 109, VALUE IS TO INCLUDE ALL LABOR, MATERIALS, | | OVERHEAD, PROFIT, INCLUDING MATERIALS PROVIDED BY | | OTHERS. | | | | 2ND REVIEW, PROVIDE A COPY OF THE CONTRACT AND COST | | BREAKDOWN. NO INFORMATION WAS PROVIDED, VALUE NOT | | CHANGED. | | | | 2. PROFLEX MSC SPEC SHEET WAS PROVIDED. WE DO NOT HAVE | | TEST REPORTS ON FILE FOR THIS PRODUCT, BUT WE DO FOR | | PROFLEX RCU250, SUPERSIM90. EITHER SELECT AN ALTERNATE | | PRODUCT OR PROVIDE THE FOLLOWING TEST REPORTS FOR | | PROFLEX MSC: | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. | | | | 2ND REVIEW, THE STC AND IIC TEST REPORTS INCLUDE A | | DROPPED GYPSUM CEILING. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-06-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-16 |
Time |
18:34 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-06-16 |
Time |
18:34 |
Sent To |
|
|
Notes |
2018-06-16 18:37:10 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC 109, VALUE IS TO INCLUDE ALL LABOR, MATERIALS, | | OVERHEAD, PROFIT, INCLUDING MATERIALS PROVIDED BY | | OTHERS. | | | | 2. PROFLEX MSC SPEC SHEET WAS PROVIDED. WE DO NOT HAVE | | TEST REPORTS ON FILE FOR THIS PRODUCT, BUT WE DO FOR | | PROFLEX RCU250, SUPERSIM90. EITHER SELECT AN ALTERNATE | | PRODUCT OR PROVIDE THE FOLLOWING TEST REPORTS FOR | | PROFLEX MSC: | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2018-08-10 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-08-10 |
Time |
07:37 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-08-10 |
Time |
07:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2018-08-03 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-08-03 |
Time |
10:18 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-08-03 |
Time |
10:17 |
Sent To |
B |
|
Notes |
2018-08-03 10:18:38 | SEE PREVIOUS REVIEWS FOR PLANS. SIGNED AND SEALED BY | | RESPONSIBLE PARRTY. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2018-07-09 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-07-09 |
Time |
16:28 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-07-09 |
Time |
16:28 |
Sent To |
B |
|
Notes |
2018-07-09 16:28:05 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE | | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | 471.025; WPB FBC 107.2.1, 107.3.5 (PLAN SUBMITTED WAS | | NOT SIGNED BY THE ELECTRICAL CONTRACTOR QUALIFIER.) | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-06-22 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-06-22 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-06-22 |
Time |
12:47 |
Sent To |
|
|
Notes |
2018-06-22 13:19:08 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE | | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | 471.025; WPB FBC 107.2.1, 107.3.5 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2018-06-12 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-06-12 |
Time |
09:28 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-06-12 |
Time |
09:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2018-08-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-14 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-06 |
Time |
13:47 |
Sent To |
|
|
Notes |
2018-08-07 13:47:19 | RESUB ROUTED TO JLEAHY |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-08-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-04 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-31 |
Time |
14:22 |
Sent To |
|
|
Notes |
2018-08-01 14:22:28 | RESUB ROUTED TO JPEARSON |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-07-30 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-30 |
Time |
18:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-05 |
Time |
14:36 |
Sent To |
|
|
Notes |
2018-07-06 14:36:57 | RESUB ROUTED TO JPEARSON |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-06-25 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-06-25 |
Time |
17:48 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-06-08 |
Time |
12:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2018-06-25 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-06-25 |
Time |
17:40 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-06-25 |
Time |
17:40 |
Sent To |
|
|
Notes |
|
|