Plan Review Stops For Permit 18060308 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-12-12 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-12-12 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-12-12 |
Time |
11:09 |
Sent To |
|
|
Notes |
2018-12-12 11:09:14 | PROVISOS: | | ANY WORK INVOLVING POST TENSION SYSTEM MODIFICATIONS, | | OR IF TENDONS ARE DAMAGED WILL REQUIRE SPECIAL | | INPECTOR. THE SPECIAL INSPECTOR WILL NEED TO BE | | APPROVED ANDUTILIZED FOR NEW WORK OR REPAIRS. | | | | PROVIDE SUBMITTAL FOR FLOORING TO INCLUDE: | | 1.IMPACT INSULATION CLASS (IIC) NOT LESS THAN 50, OR | | NOT LESS THAN 45 IF FIELD TESTED | | 2. SOUND TRANSMISSION CLASS (STC) NOT LESS THAN 50, OR | | NOT LESS THAN 45 IF FIELD TESTED | | 3. FLAME SPREAD INDEX AND SMOKE DEVELOPED INDEX | | | | SEPARATE PERMIT FOR FIRE ALARM WORK. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2018-10-22 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-10-22 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-10-16 |
Time |
16:37 |
Sent To |
|
|
Notes |
2018-10-22 11:04:37 | PROVISOS: | | ANY WORK INVOLVING POST TENSION SYSTEM MODIFICATIONS, | | OR IF TENDONS ARE DAMAGED WILL REQUIRE SPECIAL | | INPECTOR. THE SPECIAL INSPECTOR WILL NEED TO BE | | APPROVED ANDUTILIZED FOR NEW WORK OR REPAIRS. | | | | COMMENT REVIEW NUMBER ONE SUGGESTED THAT SEPARATE | | PERMIT BE APPLIED FOR EACH UNIT. THIS WAS NOT DONE, SO | | ALL UNITS WILL BE UNDER ONE PERMIT. WORK WILL NEED TO | | BE DONE AS ONE PROJECT. | | | | PROVIDE SUBMITTAL FOR FLOORING TO INCLUDE: | | 1.IMPACT INSULATION CLASS (IIC) NOT LESS THAN 50, OR | | NOT LESS THAN 45 IF FIELD TESTED | | 2. SOUND TRANSMISSION CLASS (STC) NOT LESS THAN 50, OR | | NOT LESS THAN 45 IF FIELD TESTED | | 3. FLAME SPREAD INDEX AND SMOKE DEVELOPED INDEX | | | | SEPARATE PERMIT FOR FIRE ALARM WORK. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-07-30 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-07-26 |
Time |
16:43 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-07-24 |
Time |
14:54 |
Sent To |
|
|
Notes |
2018-07-26 16:43:24 | BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS | | | | 1- THE PROPOSED WORK INVOLVES 3 SEPARATE FLOORS. | | PROVIDE A SEPARATE PERMIT APPLICATION FOR EACH FLOOR. | | CLEARLY IDENTIFY THE UNIT OF EACH WHERE ALTERATION IS | | GOING TO TAKE PLACE. NOTE: SAME PLANS MAY BE USED, BUT | | NEED A SEPARATE PERMIT APPLICATION FOR EACH UNIT FOR | | PROPER INSPECTIONS. SEC. 105.1 CITY AMENDMENTS. | | | | 2- THIS IS A THRESHOLD BUILDING. SPECIAL INSPECTOR MAY | | BE REQUIRED FOR NEW FLOOR PENETRATIONS INTO EXISTING | | POST TENSIONED SLAB. LOCATION OF PT TENDONS AND | | REINFORCEMENT IN SLAB IS REQUIRED BEFORE CORE DRILLING. | | COORDINATE WITH KEN CONRAD (CHIEF BUILDING INSPECTOR) | | PRIOR TO ANY WORK. SEE CONTACT INFORMATION BELOW. | | | | KEN CONRAD | | CHIEF BUILDING INSPECTOR | | PHONE: 805-6666 EXT: 6666 | | E-MAIL: [email protected] | | | | 3- -SHEET A-121-NEW PLAN: | | A)IT LOOKS LIKE THE SLIDING DOORS FOR CLOSET IN | | SECONDARY BEDROOM DON'T COMPLY WITH THE 32" USABLE | | DOORS REQUIREMENT #3 OF FAIR HOUSING ACT. SEE PAGE 3.9 | | AND PAGE 3.14 OF FAIR HOUSING ACT MANUAL. REVISE AS | | REQUIRED. | | | | B)PURPLE DASHED LINES SHOWN ON KITCHEN AND BATHROOMS | | USED TO ILLUSTRATE THE CLEAR FLOOR SPACE BY THE | | APPLIANCES ARE NOT CLEAR. CLEARLY SHOW THE CLEAR FLOOR | | SPACE IN FRONT OF EACH APPLIANCE. NOTE: CLEARLY SPECIFY | | IF THERE ARE CABINETS BELOW PLUMBING FIXTURES. | | COORDINATE WITH SHEET A-460. THE KITCHEN ISLAND HAVE | | CABINETS BELOW, THEREFORE,THERE IS NO KNEE SPACE BELOW | | THE COUNTER. CLEARLY SHOW THE CLEAR DIMENSION BETWEEN | | THE REFRIGERATOR AND THE KITCHEN ISLAND. SEE PAGE 7.6 | | AND 7.7 OF FAIR HOUSING ACT MANUAL. | | | | C) CLEARLY IDENTIFY WHICH TYPE OF BATHROOMS TO BE USED. | | "A" OR "B". SEE PAGE 7.34 OF FAIR HOUSING ACT MANUAL | | FOR PROPER REVIEW COMPLIANCE. NOTE: IT LOOKS LIKE THERE | | MAY BE AN ISSUE WITH THE DOOR IN WATER CLOSET | | COMPARTMENT OF BATHROOM LOCATED IN THE MIDDLE OF THE | | APARTMENT. IT LOOKS LIKE THERE MAY BE CONFLICT WITH THE | | REQUIRED CLEAR FLOOR SPACE OUTSIDE THE SWING OF THE | | DOOR. | | | | | | D) IT LOOKS LIKE THE SHOWERS DON'T COMPLY WITH THE | | CLEAR FLOOR SPACE THAT NEEDS TO BE PARALLEL AND FLUSHED | | WITH THE CONTROL WALL. SEE PAGE 7.56 OF FAIR HOUSING | | ACT MANUAL. REVISE AS REQUIRED. | | | | 4--SHEET G-100: | | A)REVISE PROJECT CODE ANALYSIS (SEC. 107.2.1 CITY | | AMENDMENTS): | | (1)PROVIDE CORRECT FLOORS TO MATCH PERMIT APPLICATION | | AND PLANS. WORK IS ON FLOORS 10 THRU 12 NOT 8 THRU 10. | | (NOTE: ALSO NEED A PERMIT APPLICATION FOR EACH FLOOR | | UNIT) | | (2)REVISE JURISDICTION CONTACT INFORMATION. CURRENT | | BUILDING OFFICIAL IS ROBERT BROWN NOT DOUG WISE. REVISE | | PHONE NUMBER AND E-MAIL AS WELL. NOTE: THIS IS NOT PALM | | BEACH COUNTY JURISDICTION. THIS IS THE CITY OF WEST | | PALM BEACH. PHONE NUMBER AND E-MAIL ADDRESS IS NOT | | REQUIRED. | | | | B) THE CURRENT CODE IS THE FBC, 6TH EDITION (2017) | | UPDATE ALL THE INFORMATION ON SHEET G-100 THAT IS | | REFERENCING THE 2014 CODE. | | CHAPTER 553 F.S. | | | | C) REVISE/CLARIFY BUILDING DATA. ACCORDING TO CITY | | RECORDS (PERMIT #95009927) 3RD AND 4TH FLOORS HAVE HAVE | | NURSING UNITS, 5TH AND 6TH FLOORS HAVE ASSISTED LIVING | | UNITS AND 8TH THRU 11TH FLOOR AND PENTHOUSE HAVE | | INDEPENDENT UNITS. FOR CLARIFICATION THE OCCUPANCY OF | | THIS BUILDING IS A MIXED USE OF NURSING HOME, ASSISTED | | LIVING FACILITY AND INDEPENDENT LIVING FACILITY FOR THE | | ELDERLY. UNITS ON FLOORS 10 THRU 12 ARE RESIDENTIAL | | (R2). | | SEC. 301.1 FBC. | | | | 5- FLOORING UNDERLAYMENT SOUND INSULATION MATERIAL TO | | BE USED FOR CERAMIC TILE AND WOOD FLOORING(NOTE: THIS | | MAY BE SUBMITTED LATER AS A DEFERRED SUBMITTAL. | | DESIGNER OF RECORD TO APPROVE THEM BEFORE SUBMITTAL): | | A) PROVIDE COPIES OF THE FLAME SPREAD INDEX AND SMOKE | | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 | | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION | | (2017). | | NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. | | | | B) PROVIDE COPIES OF THE SOUND TRANSMISSION CLASS (STC) | | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY | | SEC. 1207.2 OF FBC 6TH EDITION (2017). | | NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE | | ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT | | ACOUSTICAL CEILING. | | | | C) PROVIDE COPIES OF THE IMPACT INSULATION CLASS (IIC) | | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY | | SEC. 1207.3 OF FBC 6TH EDITION (2017). | | NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE | | ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT | | ACOUSTICAL CEILING. | | | | 6- SHEET A-460-FINISH PLAN + ELEVATIONS + DETAILS: | | PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | REINFORCEMENT AT ALL THE GRAB BARS AS REQUIRED BY | | REQUIREMENT #6 OF FAIR HOUSING ACT. NOTE: REMEMBER TYPE | | OF CONSTRUCTION. COMBUSTIBLE MATERIALS ARE NOT ALLOWED. | | SEE SEC. 603.1 FBC FOR PERMITTED MATERIALS. | | | | 7- SHEET G-201 -EXISTING LIFE SAFETY PLANS: | | A) REVISE THE EXIT ACCESS TRAVEL DISTANCE. THE DISTANCE | | IS MEASURE FORM THE MOST REMOTE POINT TO THE EXIT NOT | | TO THE ENTRY DOOR. SEE SEC. 1017.3 FBC AND REVISE AS | | REQUIRED. | | | | B)EXISTING LIFE SAFETY PLANS SHOW A FIRE EXTINGUISHER | | WHERE THE NEW CORRIDOR WALL IS BUILT FOR NEW APARTMENT. | | SPECIFY LOCATION OF RELOCATED FIRE EXTINGUISHER. SEC. | | 906.1 FBC. | | | | 8- SHEET G-500-UL ASSEMBLIES: PROVIDE SPECIFICATIONS | | FOR RATED CEILING ASSEMBLY. SEC. 420.3 FBC | | | | 9- SHEET FP-001-GENERAL INFORMATION-FIRE PROTECTION: | | REVISE INFORMATION SPECIFIED UNDER RESIDENTIAL UNITS IN | | THE FIRE PROTECTION DESIGN CRITERIA COLUMN. THIS | | BUILDING REQUIRES A NFPA 13 SPRINKLER SYSTEM. SEC. | | 903.3.2 FBC. NFPA 13R SPRINKLER SYSTEM IS NOT ALLOWED. | | NFPA 13R SYSTEM IS FOR LOW RISE RESIDENTIAL | | OCCUPANCIES. REVISE AS REQUIRED. | | SEPARATE PERMIT REQUIRED. | | | | 10- PROVIDE SPECIFICATIONS FOR FIRE ALARM AND SMOKE | | ALARMS. SEC. 907.2.9 FBC. | | SEPARATE PERMIT REQUIRED. | | | | 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | PENETRATIONS IF FIRE RATED HORIZONTAL ASSEMBLIES AND | | FIRE RATED WALLS. | | SEC. 714 FBC. | | | | 12- THIS IS A DIGITAL SUBMITTAL. ALL DRAWINGS NEED TO | | HAVE DIGITAL SIGNATURE AS REQUIRED BY CHAPTER 481 FOR | | ARCHITECTS AND CHAPTER 471 FOR ENGINEERS. | | | | 13- PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2018-12-11 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-12-11 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-12-11 |
Time |
11:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2018-10-07 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-10-07 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-10-07 |
Time |
13:54 |
Sent To |
|
|
Notes |
2018-10-07 13:54:34 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. CORRECTED. | | 2. DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE. PROVIDE | | CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 (NOT | | CORRECTED, SEE NOTES IN SIGNATURE STOP.) | | 3. CORRECTED. | | 4. CORRECTED. | | 5. CORRECTED. | | 6. CORRECTED. | | 7. CORRECTED. | | | | NEW COMMENT: | | | | 8. NO VALUE FOR WORK STATED ON PERMIT APPLICATIONS. | | PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF | | WORK, TO INCLUDE ALL MATERIALS AND LABOR. THE VALUE | | LISTED ON EACH PERMIT APPLICATION SHOULD BE FOR THE | | WORK THAT IS INCLUDED IN THAT PORTION OF THE PROJECT. | | FBC 109.3 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-07-23 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-07-23 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-07-23 |
Time |
11:00 |
Sent To |
|
|
Notes |
2018-07-23 11:00:48 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. NOTE G2 ON SHEET E-001 AND SHEET G-100 SPECIFY THE | | WRONG CODE FOR DESIGN. THESE ARE IN CONFLICT WITH OTHER | | AREAS OF THE PLAN THAT STATE THE CURRENT CODE. CORRECT | | DISCREPANCIES. WPB FBC 107.2.1; FBC PREFACE | | 2. DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE. PROVIDE | | CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 | | 3. BE ADVISED THAT FIRE ALARM IS NOT INCLUDED IN THE | | SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN | | SUBMITTALS FOR THIS. WPB FBC 105.1, 107.2.1 | | 4. SHEET E-002 HAS A NOTE FOR PATIENT CARE AREAS, BUT | | REVIEWER DOES NOT SEE ANY PATIENT CARE AREAS IDENTIFIED | | ON PLAN. PROVIDE CLARIFICATION AND/OR CORRECTION. WPB | | FBC 107.2.1 | | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL TO CONFIRM THE STATED AIC RATING OF THE PANELS IS | | ADEQUATE. NEC 110.9, 110.10 | | 6. NOTE ON PANEL SCHEDULE INDICATES THAT ALL BREAKERS | | SHALL BE AFCI TYPE. BRANCH CIRCUITS THAT FEED EQUIPMENT | | SUCH AS A RANGE OR AN AC ARE NOT TYPICALLY INSTALLED | | WITH AFCI PROTECTION. PROVIDE CLARIFICATION AS TO WHICH | | CIRCUITS ARE AFCI PROTECTED PER CODE. NEC 210.12 | | 7. PLAN SHOWS WHAT APPEARS TO BE A STANDARD RECESS | | LIGHT OVER SHOWER. LIGHTING IN BATHTUB OR SHOWER AREAS | | SHALL BE SUITABLE FOR DAMP LOCATIONS. PROVIDE | | CORRECTION. NEC 410.10(D) | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2018-11-20 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-11-20 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-11-20 |
Time |
14:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-09-24 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-09-24 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-09-24 |
Time |
12:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2018-06-27 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-06-27 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-06-27 |
Time |
08:39 |
Sent To |
|
|
Notes |
2018-06-27 09:25:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) THE SUBMITTED PLAN INDICATES ONE ADDRESS - 315 S | | FLAGLER DR., HOWEVER, THEY INDICATE WORK ON FLOORS 10 - | | 11 & 12, WHICH APPEARS TO BE INDIVIDUAL UNITS. | | | | THERE IS NO INDICATIONS OF INTERNAL STAIRS CONNECTING | | THE FLOORS. | | | | THESE INDIVIDUAL UNITS ARE NOT INDICATED WITH THEIR | | CORRESPONDING NUMBERS. | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY IN ADDITION TO # 2 | | BELOW | | | | | | | | 2) EACH OF THESE INDIVIDUAL UNITS WITH THE PROPOSED | | WORK SHOULD BE SUBMITTED UNDER INDIVIDUAL PERMITS WITH | | THE CORRESPONDING UNIT NUMBERS AS NOTED IN # 1 ABOVE. | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | 3) A FIRE SPRINKLER SHEET WAS PROVIDED; HOWEVER, THERE | | IS NO INDICATION THAT THE WORK SHALL BE DONE UNDER | | SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY | | CONTRACTORS. | | | | THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED AND | | OPERATIONAL DURING ALL CONSTRUCTION PERIODS. | | | | IF THE SYSTEM IS DOWN FOR MORE THAN 4 HOURS, YOU ARE | | REQUIRED TO NOTIFY THE AHJ AND CONDUCT A FIRE WATCH. | | | | PLEASE REVIEW AND CORRECT FOR EACH INDIVIDUAL UNIT. | | | | | | | | | | 4) THERE IS NO INDICATION OF WORK ON THE FIRE ALARM | | SYSTEM AND THAT ANY WORK ON THE FIRE ALARM SYSTEM SHALL | | BE DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE | | SAFETY CONTRACTORS. | | | | THE FIRE ALARM SYSTEM SHALL BE MAINTAINED AND | | OPERATIONAL DURING ALL CONSTRUCTION PERIODS. | | | | IF THE SYSTEM IS DOWN FOR MORE THAN 4 HOURS, YOU ARE | | REQUIRED TO NOTIFY THE AHJ AND CONDUCT A FIRE WATCH. | | | | PLEASE REVIEW AND CORRECT FOR EACH INDIVIDUAL UNIT. | | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2019-02-13 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2019-02-13 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-01-14 |
Time |
14:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-01-04 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-04 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-11-19 |
Time |
16:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-10-30 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-10-30 |
Time |
08:54 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-09-18 |
Time |
12:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-08-15 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-08-15 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-06-25 |
Time |
15:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2019-02-05 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-02-05 |
Time |
12:00 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-02-05 |
Time |
11:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2018-12-14 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-12-14 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-12-14 |
Time |
07:58 |
Sent To |
|
|
Notes |
2018-12-14 10:07:02 | 3RD REVIEW FBC-2017 MECHANICAL | | PERMIT #18060308 | | 12/14/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M-121: THE EXHAUST DUCT HAS BEEN REMOVED FOM | | THE KITCHEN. PLEASE SUBMIT MANUFACTURER'S | | SPECIFICATIONS FOR THE RANGE HOOD SHOWING COMPLIANCE | | WITH TABLE 403.3.1.1 AND SECTION 505.1 EXCEPTION 1. | | | | 2) SUBMIT MANUFACTURER'S FOR THE NEW O/A DAMPERS- | | SECTION C403.2.4.3 FBC M. | | | | 3) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW HEAT | | PUMPS- SECTION 307.2 FBC M. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2018-10-18 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-10-18 |
Time |
08:06 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-10-17 |
Time |
16:53 |
Sent To |
|
|
Notes |
2018-10-18 08:14:35 | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT #18060308 | | 10/18/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE 16X8 TRANSFER GRILL FOR THE LARGE BEDROOM IS | | UNDERSIZED PER SECTION 601.6 FBC M (2)- 50 SQ. INCHES | | PER 100 CFMS REQUIRED FOR BALANCED AIR. IN ADDITION, IT | | APPEARS THAT THE AIR FROM THE BEDROOM THAT IS SUPPLIED | | BY HP-A WILL BE TRANSFERRED DIRECTLY INTO THE MAIN | | RETURN GRILL OF HP-B WHICH WILL CAUSE AN IMBALNCE IN | | THE SYSTEMS. A BETTER OPTION MAY BE TO DUCT THE RETURN | | DIRECTLY TO HP-B. | | | | 2) THE NEW KITCHEN EXHAUST SHALL BE RUN INDEPENDENTLY | | OF THE TOILET ROOM EXHAUST, AND MUST MEET ALL THE | | COMPLIANCES LISTED UNDER SECTION 505.3 FBC M- SEE | | BELOW. | | | | 505.3 COMMON EXHAUST SYSTEMS FOR DOMESTIC KITCHENS | | LOCATED IN MULTISTORY STRUCTURES. | | | | WHERE A COMMON MULTISTORY DUCT SYSTEM IS DESIGNED AND | | INSTALLED TO CONVEY EXHAUST FROM MULTIPLE DOMESTIC | | KITCHEN EXHAUST SYSTEMS, THE CONSTRUCTION OF THE SYSTEM | | SHALL BE IN ACCORDANCE WITH ALL OF THE FOLLOWING: | | | | 1.THE SHAFT IN WHICH THE DUCT IS INSTALLED SHALL BE | | CONSTRUCTED AND FIRE-RESISTANCE RATED AS REQUIRED BY | | THE FLORIDA BUILDING CODE, BUILDING. | | | | 2.DAMPERS SHALL BE PROHIBITED IN THE EXHAUST DUCT, | | EXCEPT AS SPECIFIED IN SECTION 505.1. PENETRATIONS OF | | THE SHAFT AND DUCTWORK SHALL BE PROTECTED IN ACCORDANCE | | WITH SECTION 607.5.5, EXCEPTION 2. | | | | 3.RIGID METAL DUCTWORK SHALL BE INSTALLED WITHIN THE | | SHAFT TO CONVEY THE EXHAUST. THE DUCTWORK SHALL BE | | CONSTRUCTED OF SHEET STEEL HAVING A MINIMUM THICKNESS | | OF 0.0187 INCH (0.4712 MM) (NO. 26 GAGE) AND IN | | ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS. | | | | 4.THE DUCTWORK WITHIN THE SHAFT SHALL BE DESIGNED AND | | INSTALLED WITHOUT OFFSETS. | | | | 5.THE EXHAUST FAN MOTOR DESIGN SHALL BE IN ACCORDANCE | | WITH SECTION 503.2. | | | | 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF | | THE AIRSTREAM. | | | | 7.THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE | | CONNECTED TO A STANDBY POWER SOURCE. | | | | 8. EXHAUST FAN OPERATION SHALL BE MONITORED IN AN | | APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR | | VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION. | | | | 9.WHERE THE EXHAUST RATE FOR AN INDIVIDUAL KITCHEN | | EXCEEDS 400 CFM (0.19 M3/S) MAKEUP AIR SHALL BE | | PROVIDED IN ACCORDANCE WITH SECTION 505.2. | | | | 10.A CLEANOUT OPENING SHALL BE LOCATED AT THE BASE OF | | THE SHAFT TO PROVIDE ACCESS TO THE DUCT TO ALLOW FOR | | CLEANOUT AND INSPECTION. THE FINISHED OPENINGS SHALL BE | | NOT LESS THAN 12 INCHES BY 12 INCHES (305 MM BY 305 | | MM). | | | | 11.SCREENS SHALL NOT BE INSTALLED AT THE TERMINATION. | | | | 12.THE COMMON MULTISTORY DUCT SYSTEM SHALL SERVE ONLY | | KITCHEN EXHAUST AND SHALL BE INDEPENDENT OF OTHER | | EXHAUST SYSTEMS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-07-11 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-07-11 |
Time |
17:53 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-07-11 |
Time |
17:53 |
Sent To |
|
|
Notes |
2018-07-11 18:06:59 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18060308 | | 7/11/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M-121: PROVIDE A MEANS OF RETURNING AIR FROM | | THE BEDROOMS- SECTION 601.6 FBC M. | | | | 2) M-121: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | NEW COOKING APPLIANCE- SECTION 917.1 FBC M. | | | | 3) M-121: EXHAUST VENTILATION IS REQUIRED FOR THE | | KITCHEN AT A RATE OF 25 CFMS CONTINUOUS, OR 100 CFMS | | INTERMITTENTLY PER TABLE 403.3.1.1 FBC M. INDICATE IF A | | NEW KITCHEN EXHAUST HOOD AND EXHAUST DUCT ARE TO BE | | INSTALLED AND: A) SUBMIT MANUFACTURER'S SPECIFICATIONS | | FOR THE SYSTEM. B) PROVIDE A DETAIL SHOWING THE EXHAUST | | DUCT RUN AND TERMINATION LOCATION- SECTION 505 FBC M | | | | 4) CLARIFY IF A NEW OR RELOCATED DRYER IS TO BE | | INSTALLED AND: A) SUBMIT MANUFACTURER'S SPECIFICATIONS. | | B) SHOW THE LOCATION OF THE DRYER AND THE EXHAUST DUCT | | RUN AND TERMINATION LOCATION.- SECTION 504 FBC M. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2019-02-13 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-02-13 |
Time |
08:30 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-02-13 |
Time |
08:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2019-01-04 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-04 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-01-04 |
Time |
16:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2018-10-30 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-10-30 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-10-30 |
Time |
08:50 |
Sent To |
|
|
Notes |
2018-10-30 08:52:20 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. SHT. A121 THE CLEAR FLOOR SPACE FOR THE SHOWER SHALL | | BE FLUSH WITH THE CONTROL WALL. PER FHA DESIGN MANUAL | | REQUIREMENT #7 PG. 7.56 | | 2. SHT. A121 IN THE CLEAR FLOOR SPACE FOR THE SHOWER | | THE LAVATORY SHALL BE ALLOWED TO OVERLAP THE CLEAR | | FLOOR SPACE ONLY 6? PLEASE CLARIFY THIS ON THE PLAN. | | PER FHA DESIGN MANUAL REQUIREMENT #7 PG. 7.57 | | 3. THE VANITY AND THE WING WALL NEXT TO THE VANITY | | SHALL HAVE A DEPTH NO MORE THAN 24?. PER FHA DESIGN | | MANUAL REQUIREMENT #7 PG. 7.44 | | 4. PLEASE LABEL ALL THE CLEAR FLOOR SPACE FOR THE | | PLUMBING FIXTURES IN THE BATHROOM WITH THE DIMENSIONS. | | PER FHA DESIGN MANUAL REQUIREMENT #7 PG. 7.43, 7.47, | | 7.52, 7.56 | | 5. ALL BATHROOMS SHALL HAVE GRAB BAR BACKING PLEASE | | PROVIDE DETAIL DRAWINGS SHOWING THE LOCATION AND HEIGHT | | DIMENSIONS FOR THE GRAB BAR BACKING. PER FHA DESIGN | | MANUAL REQUIREMENT #6 PG. 6.3-6.13 | | 6. PLEASE CLARIFY WHAT TYPE OF SHOWER ENCLOSURE IS BE | | INSTALLED, UNDER THE PLUMBING FIXTURE SCHEDULE IT | | STATES AN ACRYLIC SHOWER STALL AND UNDER THE SPECS IT | | STATES A TILED SHOWER IF IT IS A TILED SHOWER PLEASE | | PROVIDE THE MANUFACTURE SPECIFICATIONS FOR THE SHOWER | | PAN WATER PROOFING. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-08-02 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-08-02 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-08-02 |
Time |
10:36 |
Sent To |
|
|
Notes |
2018-08-02 11:02:24 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. PLEASE DEFINE THE OCCUPANCY TYPE OF THE BUILDING AND | | THE FLOORS THE UNITS ARE LOCATED THIS BEING A MIXED | | OCCUPANCY SEE BUILDINGS COMMENTS. PER WPB AMEND TO FBC | | 107.2.1 | | | | 2. PLEASE CLARIFY WHAT ACCESSIBILITY CODE YOU ARE | | COMPILING WITH. PER WPB AMEND TO FBC 107.2.1 | | | | 3. SHT P-401 DETAIL #2 PLEASE CLARIFY WHAT IS A TYPICAL | | SANITARY TRANSITION IS ALSO THE THE VENTING SHALL BE | | SHOWN. PER FBC PL 901.2.1 | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2019-02-13 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2019-02-13 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-02-13 |
Time |
08:32 |
Sent To |
|
|
Notes |
2019-02-13 08:33:18 | 2/13/19 DIG SIG ON PLUMB OK |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2018-12-11 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-12-11 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-12-11 |
Time |
11:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2018-10-07 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-10-07 |
Time |
13:34 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-10-07 |
Time |
13:34 |
Sent To |
|
|
Notes |
2018-10-07 13:34:38 | DIGITAL PLANS ARE REQUIRED TO HAVE A DIGITAL | | SIGNARTURE. WPB FBC 107.1, 107.2; FS 471, 481 | | | | THE FOLLOWING SHEETS DO NOT HAVE THE DIGITAL SIGNATURE | | REQUIRED: A-111, A-121, A-460, G-001, G-010, G-100, | | G-150, G-201, G-500, I-100, I-510, M-001, M-221, M-301, | | P-001, P-121, P-221, P-301, P-401, S-121. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2018-07-23 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-07-23 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-07-23 |
Time |
09:15 |
Sent To |
|
|
Notes |
2018-07-23 09:17:47 | DIGITAL PLANS ARE REQUIRED TO HAVE A DIGITAL | | SIGNARTURE. WPB FBC 107.1, 107.2; FS 471, 481 |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
2 |
Status |
P |
Date |
2018-10-22 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-10-22 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-10-22 |
Time |
11:05 |
Sent To |
|
|
Notes |
2018-10-22 11:05:43 | SEE PROVISO IN BUILDING COMMENT. |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
1 |
Status |
F |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-07-26 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-07-26 |
Time |
14:59 |
Sent To |
|
|
Notes |
2018-07-26 15:08:48 | THIS IS A THRESHOLD BUILDING. SPECIAL INSPECTOR MAY BE | | REQUIRED FOR NEW FLOOR PENETRATIONS INTO EXISTING POST | | TENSIONED SLAB. LOCATION OF PT TENDONS AND | | REINFORCEMENT IN SLAB IS REQUIRED BEFORE CORE DRILLING. | | COORDINATE WITH KEN CONRAD (CHIEF BUILDING INSPECTOR) | | PRIOR TO ANY WORK. SEE CONTACT INFORMATION BELOW. | | | | | | KEN CONRAD | | CHIEF BUILDING INSPECTOR | | DEVELOPMENT SERVICES | | BUILDING INSPECTIONS | | | | 401 CLEMATIS STREET | | P.O.BOX 3366 | | WEST PALM BEACH, FL 33402 | | PHONE: 805-6666 EXT: 6666 | | FAX: 659-8026 | | E-MAIL: [email protected] | | SERVING SINCE SEP 30, 2001 | | EMPLOYMENT CATEGORY: FR | | SUPERVISOR: GATHRIGHT, RICHARD EUGENE JR | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2018-07-03 |
|
|
Cont ID |
|
Sent By |
AA |
Date |
2018-07-03 |
Time |
16:15 |
Rev Time |
|
Received By |
aaponte |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2018-07-03 16:15:35 | INTERIOR UNIT RENOVATION ONLY. |
|
|