Plan Review Details - Permit 18060261
Plan Review Stops For Permit 18060261
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-07-08 Cont ID  
Sent By shill Date 2018-07-08 Time 13:05 Rev Time 0.00
Received By shill Date 2018-07-08 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-07-20 Cont ID  
Sent By jpearson Date 2018-07-20 Time 08:16 Rev Time 0.00
Received By jpearson Date 2018-07-20 Time 08:16 Sent To  
Notes
2018-07-20 08:17:27FIRE ALARM NOT INCLUDED IN THIS APPROVAL.

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-07-20 Cont ID  
Sent By jpearson Date 2018-07-20 Time 08:31 Rev Time 0.00
Received By jpearson Date 2018-07-20 Time 08:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-13 Cont ID  
Sent By scaldero Date 2018-06-13 Time 10:53 Rev Time 0.00
Received By scaldero Date 2018-06-12 Time 13:02 Sent To  
Notes
2018-06-13 10:53:09PERMIT # 18060261
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SHEET FAC1-04-1: PROPER COORDINATION OF EXITSTING
 AND NEW FIRE ALARM SYSTEMS NEEDED TO ENSURE THAT THE
 INTEGRITY OF THE EXISTING FIRE ALARM SYSTEM IS
 MAINTAINED THROUGHOUT TO ENSURE THAT THE FULL BUILDING
 HAS PROPER FIRE ALARM COVERAGE AT ALL TIMES, UNTIL SUCH
 TIME AS BOTH SYSTEMS ARE COMBINED INTO ONE.
  
 3) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-01 Cont ID  
Sent By gjohnson Date 2019-03-01 Time 09:41 Rev Time 0.00
Received By gjohnson Date 2019-02-28 Time 16:54 Sent To  
Notes
2019-02-28 16:54:47NEEDS PLUMBING; SENT EMAIL TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-07-20 Time   Rev Time 0.00
Received By cpuell Date 2018-06-07 Time 15:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-07-10 Cont ID  
Sent By ccole Date 2018-07-10 Time 11:19 Rev Time 0.00
Received By ccole Date 2018-07-10 Time 11:19 Sent To  
Notes
2018-07-10 11:20:40MECHANICAL PROVISO:
 7/10/18
  
 PROVIDE MIAMI-DADE NOA #09-0804.05 FOR THE ROOF STAND.

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-03-01 Cont ID  
Sent By gjohnson Date 2019-03-01 Time 09:33 Rev Time 0.00
Received By gjohnson Date 2019-03-01 Time 09:33 Sent To  
Notes
2019-03-01 09:34:10PROVISO 18060261
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE A BACKFLOW ON THE ICEMAKERS, WATER FILTERS
 AND COFFEE MAKERS. PER FBC PL 608.3, 608.16.10
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
 3. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTORS
 APPROVAL.
 4. ALL PLUMBING WORK SHALL COMPLY WITH FBC PLUMBING 6TH
 EDITION 2017
 5. TRAP PRIMER REQUIRED ON THE FLOOR DRAIN. PER FBC PL
 1002.4.1
 6. THE NEW SINK DRAIN PIPING SHALL CONNECT TO BUILDING
 BRANCH DRAIN DOWN STREAM OF THE EXISTING BATHROOM
 GROUP. PER FBC PL 912.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-07-11 Cont ID  
Sent By shill Date 2018-07-11 Time 12:50 Rev Time 0.00
Received By shill Date 2018-07-11 Time 12:50 Sent To  
Notes
2018-07-08 13:06:127/8 UNABLE TO VERIFY SIGNATURES; SERVER ERROR SH
  