Plan Review Details - Permit 18060181
Plan Review Stops For Permit 18060181
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-29 Cont ID  
Sent By pvalenti Date 2018-07-26 Time 08:09 Rev Time 0.00
Received By pvalenti Date   Time   Sent To I
Notes
2018-07-29 07:42:59PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED PV
  
 THE CONTRACTOR PROVIDED ALL REQUIRED DOCUMENTATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-09 Cont ID  
Sent By pvalenti Date 2018-07-09 Time 16:08 Rev Time 0.00
Received By pvalenti Date   Time   Sent To I
Notes
2018-07-09 16:15:24****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107. THE SUBMITTED INFORMATION IS MISING THE
 DESIGN CALCULATIONS AND INSTALLATION DETAILS FOR SIGNS
 A AND B.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By pvalenti Date 2018-06-15 Time 18:01 Rev Time 0.00
Received By pvalenti Date 2018-06-15 Time 18:01 Sent To  
Notes
2018-06-15 18:01:52****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107. PLANS ARE NOT CONSISTANT. APPLICATION IS
 FOR KEISER UNIVERSITY AND 1601 FORUM AND PLANS ARE FOR
 2600 NORTH MILITARY TRAIL. PLANS SHOW 3 SIGNS (A, B, C)
 BUT SPECIFICATIONS ARE ONLY FOR SIGN C.
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2018-07-26 Cont ID  
Sent By fgiaquin Date 2018-07-08 Time 08:08 Rev Time 0.00
Received By pvalenti Date 2018-07-08 Time 08:07 Sent To B
Notes
2018-07-08 08:08:03NO ELEC WORK REVIEWED OR APPROVED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By fgiaquin Date 2018-06-15 Time 05:51 Rev Time 0.00
Received By fgiaquin Date 2018-06-15 Time 05:33 Sent To B
Notes
2018-06-15 05:50:30ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PERMIT APPLICATION SAYS KEISER UNIVERSITY BUT
 ADDRESS SAYS 1601 FORUM PLACE, PICTURES PROVIDED OF
 SITE ARE OF1601 FORUM PLACE. PLANS SAY 2600 MILITARY
 TRAIL.
 IF THIS APPLICATION IS FOR THE NEW ATHLETIC FACILITY
 BEING BUILT THE PERMITTED ADDRESS IS 2331 NORTHWOOD
 UNIVERSITY. CORRECT ADDRESS ISSUE.
  
 2. A PHYSICAL COPY OF AN ELECTRONICALLY OR DIGITALLY
 SIGNED, DATED AND SEALED DOCUMENT IS NOT A VALID
 SIGNED, DATED AND SEALED DOCUMENT. SIMILARLY, AN
 ELECTRONIC DOCUMENT (PDF, SCAN OR FAX COPY) OF A
 PHYSICALLY SIGNED, DATED AND SEALED DOCUMENT IS NOT A
 VALID SIGNED, DATED AND SEALED DOCUMENT.
 F.S. 471/F.A.C. 61G15-23.004 (3)(C)(3)
  
 3. VALUE TOO LOW, PROVIDE COPY OF SIGNED CONTRACT WITH
 SCOPE AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND
 LABOR. FBC 109.3
  
 4. DISCONNECT FOR 120V BEFORE IT ENTERS SIGN REQUIRED
 WITHIN SIGHT OF SIGN. NEC. 600.6A(1)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-29 Cont ID  
Sent By pvalenti Date 2018-07-29 Time 07:43 Rev Time 0.00
Received By pvalenti Date 2018-07-18 Time 14:40 Sent To I
Notes
2018-07-19 14:40:24RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-09 Cont ID  
Sent By pvalenti Date 2018-07-09 Time 16:20 Rev Time 0.00
Received By pvalenti Date 2018-06-28 Time 14:48 Sent To I
Notes
2018-07-02 14:48:21RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-15 Cont ID  
Sent By pvalenti Date 2018-06-15 Time 18:02 Rev Time 0.00
Received By pvalenti Date 2018-06-05 Time 12:47 Sent To  
Notes
2018-06-06 12:47:33ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-07-24 Cont ID  
Sent By mcruz Date 2018-07-24 Time 16:05 Rev Time 0.00
Received By mcruz Date 2018-07-24 Time 16:05 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-07-05 Cont ID  
Sent By mcruz Date 2018-07-05 Time 15:38 Rev Time 0.00
Received By mcruz Date 2018-07-05 Time 15:37 Sent To E
Notes
2018-07-05 15:37:58ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 REPEAT COMMENTS:
  
 1) AS THE ALLOWABLE SQUARE FOOTAGE OF THE SIGN IS BASED
 ON THE SQUARE FOOTAGE OF THE BUILDING FACADE, PLEASE
 INDICATE THE HEIGHT AND WIDTH OF THE FACADE ON WHICH
 THE SIGN IS TO BE MOUNTED. IF LEASING A SPACE, PROVIDE
 HEIGHT AND WIDTH OF LEASED SPACE.
  
 NOTES
 - MAXIMUM SUM TOTAL AREA OF ALL SIGNS MOUNTED ON THE
 FRONT FACADE OF A BUILDING: 75 PERCENT OF THE AREA
 PERMITTED BY SECTION 94-409.
 - MAXIMUM NUMBER OF SIGNS ON EACH BUILDING: ONE SIGN
 FOR EACH INDIVIDUAL BUSINESS OCCUPANT OF THE BUILDING,
 PLUS TWO ADDITIONAL SIGNS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-08 Cont ID  
Sent By mcruz Date 2018-06-08 Time 11:24 Rev Time 0.00
Received By mcruz Date 2018-06-08 Time 11:22 Sent To E
Notes
2018-06-08 11:24:14ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) AS THE ALLOWABLE SQUARE FOOTAGE OF THE SIGN IS BASED
 ON THE SQUARE FOOTAGE OF THE BUILDING FACADE, PLEASE
 INDICATE THE HEIGHT AND WIDTH OF THE FACADE ON WHICH
 THE SIGN IS TO BE MOUNTED. IF LEASING A SPACE, PROVIDE
 HEIGHT AND WIDTH OF LEASED SPACE.
  
 NOTES
 - MAXIMUM SUM TOTAL AREA OF ALL SIGNS MOUNTED ON THE
 FRONT FACADE OF A BUILDING: 75 PERCENT OF THE AREA
 PERMITTED BY SECTION 94-409.
 - MAXIMUM NUMBER OF SIGNS ON EACH BUILDING: ONE SIGN
 FOR EACH INDIVIDUAL BUSINESS OCCUPANT OF THE BUILDING,
 PLUS TWO ADDITIONAL SIGNS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  