Plan Review Stops For Permit 18060138 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-07-26 |
Time |
08:00 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-07-26 |
Time |
07:50 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-06-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-06-25 |
Time |
18:43 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-06-25 |
Time |
18:43 |
Sent To |
E |
|
Notes |
2018-06-25 18:49:26 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE 22KW GENERAC MODEL NUMBERS ON THE MANUFACTURER'S | | SPECIFICATIONS THAT WERE SUBMITTED (G007043-0 OR | | G007042-0) ARE NOT LISTED IN THE GENERATOR TABLE ON THE | | AMERICAST GENERATOR PAD ENGINEERING. FBC 107.2.1 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-07-23 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-07-23 |
Time |
07:06 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-07-23 |
Time |
07:02 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-06-26 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-06-26 |
Time |
06:36 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-06-26 |
Time |
06:17 |
Sent To |
I |
|
Notes |
2018-06-26 06:35:50 | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | FRANK GIAQUINTO | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2018-07-25 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-25 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-25 |
Time |
15:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-06-22 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-06-22 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-06-22 |
Time |
12:52 |
Sent To |
|
|
Notes |
2018-06-22 14:01:41 | 1) THE SHUTOFF VALVE FOR THE INTERIOR PIPING SHALL BE | | LOCATED UPSTREAM OF THE PRESSURE REGULATOR PER 2017 | | FBC-FUEL GAS SEC.409.4. | | 2) THE PIPE AT THE TEE FOR THE POOL HEATER IS SHOWN AS | | RIDGID GALVANIZED AND ALSO AS PE. CLARIFY. | | 3) INDICATE ON THE GAS PLANS WHICH SIZING TABLE IS | | BEING USED FOR THE LOW PRESSURE SCH. 40 METALLIC PIPE. | | 4) GAS PLANS ON FILE WITH THE CITY SHOW AN 1 1/4 INCH | | GALVANIZED LINE AT THE GAS METER OUTLET AND THE | | SUBMITTED PLANS SHOW AN EXISTING 3/4 INCH LINE. | | CLARIFY. | | 5) PLANS ON FILE WITH THE CITY SHOW A BTU LOAD OF | | 378,000 AND THE SUBMITTED PLANS SHOW AN EXISTING BTU | | LOAD OF 525,000. CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-07-26 |
Time |
08:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-07-16 |
Time |
14:38 |
Sent To |
|
|
Notes |
2018-07-17 14:38:37 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-06-26 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-06-26 |
Time |
06:36 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-06-05 |
Time |
12:49 |
Sent To |
I |
|
Notes |
2018-06-06 12:49:52 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2018-07-19 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-07-19 |
Time |
15:56 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-07-19 |
Time |
15:56 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-06-08 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-06-08 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-06-08 |
Time |
11:47 |
Sent To |
B |
|
Notes |
|
|