Plan Review Details - Permit 18060126
Plan Review Stops For Permit 18060126
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 14:41 Rev Time 0.00
Received By shill Date 2018-08-25 Time 14:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 16:26 Rev Time 0.00
Received By shill Date 2018-08-11 Time 16:20 Sent To  
Notes
2018-08-11 16:42:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE PREVIOUS LIST, ITEM #1 (SUBSTANTIAL IMPROVEMENT
 DETERMINATION).
  
 A DOCUMENT ENTITLED "INSURABLE VALUE: REPLACEMENT COST
 SUMMARY" WAS PROVIDED. SEE FEMA 758, 4.5.3, ACTUAL CASH
 VALUE (METHOD OF DETERMINING VALUE). IF YOU WISH TO USE
 THIS METHOD, PLEAE REVISE TO PROVIDE DATA CONSISTENT
 WITH FEMA'S GUIDELINES. ALSO PROVIDE INFORMATION ABOUT
 THE PREPARER.
  
 2.FBC B TABLE 1604.5, RISK CATEGORY III IS REQUIRED FOR
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN
 300, SHEET S2. SEE ALSO FBC EB 807.
  
 2ND REVIEW, THIS WAS REVISED, BUT BASED ON THE WIND
 MAPS (AND THE ATC WINDSPEED SITE) IT APPEARS THAT RISK
 CATEGORY III IS IN THE 180MPH WIND ZONE.
  
 3. OK
  
 4. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO
 CONTRACTOR.
  
 5. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 6. OK
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 19:33 Rev Time 0.00
Received By shill Date 2018-06-16 Time 19:33 Sent To  
Notes
2018-06-16 19:34:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THIS STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA. IT IS NOT CLEAR IF THIS IS A "SUBSTANTIAL
 IMPROVEMENT"; CUMULATIVE 5 YEAR IMPROVEMENTS EXCEED
 OVER 50% OF STRUCTURE VALUE. PROVIDE INFORMATION
 REGARDING THE PAST FIVE YEARS OF IMPROVEMENTS ON THIS
 STRUCTURE, VALUE OF THIS STRUCTURE, FBC B 1622. PLEASE
 FEEL FREE TO CONTACT ME IF YOU NEED ASSISTANCE.
 ALTERNATIVELY, YOU COULD SHOW COMPLIANCE WITH THE
 REQUIREMENTS FOR NEW STRUCTURES - FINISHED FLOOR AND
 ALL EQUIPMENT SERVICING THE BUILDING TO BE AT OR ABOVE
 14.2 NAVD88, OR PROVIDE DRY FLOODPROOFING TO 14.2
 NAVD88, EXTERIOR EQUIPMENT ELEVATED TO MINIMUM 14.2
 NAVD88.
  
 2.FBC B TABLE 1604.5, RISK CATEGORY III IS REQUIRED FOR
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN
 300, SHEET S2. SEE ALSO FBC EB 807.
  
 3. 553.79(5), AS THIS IS AN ASSEMBLY OCCUPANCY WITH AN
 OCCUPANT LOAD OVER 500, THIS IS CLASSIFIED AS A
 THRESHOLD BUILDING. ALL PLANS PREPARED BY THE ARCHITECT
 AND ENGINEER ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D).
  
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER 553 AND CHAPTER 633.
  
 4. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO
 CONTRACTOR.
  
 5. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 6. THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A).
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By jpearson Date 2018-07-30 Time 09:13 Rev Time 0.00
Received By jpearson Date 2018-07-30 Time 06:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By jpearson Date 2018-06-29 Time 12:19 Rev Time 0.00
Received By jpearson Date 2018-06-27 Time 10:51 Sent To I
Notes
2018-06-29 12:19:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL MAINS SHOULD BE GROUPED PER NEC 230.72. RISER
 SHOWS AN 800 AMP SERVICE IN ONE LOCATION, A 600 AMP
 SERVICE IN ANOTHER LOCATION, AND THEN THE ADDITION OF
 THE 1200 AMP SERVICE IN A THIRD LOCATION. THIS WILL NOT
 BE ACCEPTABLE PER CODE. PREVIOUS APPROVAL OF PLAN FOR
 1200 AMP SERVICE WILL NOT BE PERMITTED IN THIS
 LOCATION. PROVIDE CORRECTION SO THAT MAINS ARE GROUPED.
 NEC 230.72, 230.2
 2. PROVIDE JUSTIFICATION FOR ADDITIONAL 1200 AMP
 SERVICE. THE LOAD SHOWN ON THIS PANEL IS APPROXIMATELY
 112 AMPS, ALTHOUGH THAT IS INCORRECT BECAUSE NO VALUE
 HAS BEEN ADDED FOR PANEL LPA. SEE COMMENT 3 FOR LOAD
 CALCULATION INFORMATION. NEC 230.2
 3. PROVIDE LOAD CALCULATION FOR EACH SERVICE INCLUDING
 EXISTING AND PROPOSED LOADS TO SHOW WHETHER THE
 EXISTING SERVICE IS ADEQUATE OR NOT FOR THE ADDITIONAL
 LOAD. ADDITIONALLY, THE LOAD CALCULATION SHOULD BE
 COMPLETED FOR ALL THREE PHASES. CURRENTLY, ONLY TWO OF
 THE PHASES ARE SHOWN. NEC 220; WPB FBC 107.2.1
 4. RISER DIAGRAM SHOWS A NEW PANEL LP FEED FROM
 EXISTING 600 AMP SERVICE. WHERE IS THIS PANEL LOCATED?
 THERE IS NO PANEL SCHEDULE FOR THIS? PROVIDE DETAILS.
 WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-17 Cont ID  
Sent By scaldero Date 2018-07-17 Time 10:44 Rev Time 0.00
Received By scaldero Date 2018-07-17 Time 10:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-07 Cont ID  
Sent By scaldero Date 2018-06-07 Time 10:58 Rev Time 0.00
Received By scaldero Date 2018-06-07 Time 10:50 Sent To  
Notes
2018-06-07 10:58:49PERMIT # 18060126
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL COMMENTS:
  
 PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM, IF APPLICABLE.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-09-06 Cont ID  
Sent By shill Date 2018-09-06 Time 09:12 Rev Time 0.00
Received By shill Date 2018-08-29 Time 10:42 Sent To  
Notes
2018-08-31 10:43:08RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 14:43 Rev Time 0.00
Received By shill Date 2018-08-17 Time 16:07 Sent To  
Notes
2018-08-20 16:07:16RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 17:09 Rev Time 0.00
Received By shill Date 2018-07-06 Time 15:14 Sent To  
Notes
2018-07-09 15:14:54B32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-06-29 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-04 Time 16:18 Sent To  
Notes
2018-06-06 16:18:37B30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-06-29 Cont ID  
Sent By shill Date 2018-06-29 Time 09:35 Rev Time 0.00
Received By shill Date 2018-06-29 Time 09:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-06-20 Cont ID  
Sent By ccole Date 2018-06-19 Time 08:05 Rev Time 0.00
Received By ccole Date 2018-06-18 Time 18:15 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status N Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 16:17 Rev Time 0.00
Received By shill Date 2018-08-11 Time 16:17 Sent To  
Notes
2018-08-11 16:19:05INSURABLE REPLACEMENT COST PROVIDED ($5,148,527)
 COST OF CUMULATIVE 5 YEAR IMPROVEMENTS $236,424 +
 PROPOSED IMPROVEMENT $400,000 = $636,424
 NOT A SUBSTANTIAL IMPROVEMENT
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 19:19 Rev Time 0.00
Received By shill Date 2018-06-16 Time 19:19 Sent To  
Notes
2018-06-16 19:19:19SEE BUILDING REVIEW
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-09 Cont ID  
Sent By gjohnson Date 2018-08-09 Time 15:13 Rev Time 0.00
Received By gjohnson Date 2018-08-09 Time 11:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By gjohnson Date 2018-06-26 Time 12:10 Rev Time 0.00
Received By gjohnson Date 2018-06-26 Time 08:51 Sent To  
Notes
2018-06-26 13:17:481ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLUMBING PLAN SHOWING NEW PIPING FOR THE
 MISTER. PER WPB AMEND TO FBC 107.2.1
  
 2. SHOW LOCATION OF PLUMBING PIPES THAT ARE BEING
 CAPPED ON THE PLUMBING PLAN . PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 5 Status P Date 2018-09-18 Cont ID  
Sent By shill Date 2018-09-18 Time 09:26 Rev Time 0.00
Received By shill Date 2018-09-18 Time 09:26 Sent To  
Notes
2018-09-18 09:30:23ALLEN WIEDER, PE AND DAVID WRATISLAW, BN2762
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status F Date 2018-09-06 Cont ID  
Sent By shill Date 2018-09-06 Time 09:05 Rev Time 0.00
Received By shill Date 2018-09-01 Time 17:27 Sent To  
Notes
2018-09-06 09:09:00SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 107:
  
 THREE ORIGINAL SI AGREEMENTS REQUIRED, SEE POLICY AND
 PREVIOUS LIST.
  
 COPIES OF THE PAGES FOR THE CONTRACTOR AND OWNER WERE
 SUBMITTED (NO ORIGINALS).
  
 PLEASE PROVIDE THREE ORIGINAL AGREEMENTS. PROVIDE THREE
 IDENTICAL SETS, COLLATED IN ORDER.
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 14:41 Rev Time 0.00
Received By shill Date 2018-08-25 Time 14:41 Sent To  
Notes
2018-08-25 14:43:44SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 107:
 THREE ORIGINAL SI AGREEMENTS REQUIRED, SEE POLICY.
 THE SI AGREEMENT IS TO BE SIGNED BY THE OWNER AND
 CONTRACTOR IN ADDITION TO THE TWO SIGNATURES PROVIDED
 (ALLEN WIEDER, PE AND DAVID WRATISLAW, BN2762).
 SOME OF THE DOCUMENTS ARE UPSIDE DOWN. PLEASE PROVIDE A
 COMPLETE THRESHOLD AGREEMENT, WITH COPIES OF LICENSES
 AND RESUMES, IN THE SAME ORIENTATION.
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 16:53 Rev Time 0.00
Received By shill Date 2018-08-11 Time 16:53 Sent To  
Notes
2018-08-11 16:53:43SEE BUILDING REVIEW
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 19:29 Rev Time 0.00
Received By shill Date 2018-06-16 Time 19:29 Sent To  
Notes
2018-06-16 19:29:55SEE BUILDING REVIEW
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-24 Cont ID  
Sent By jroach Date 2018-07-24 Time 14:32 Rev Time 0.00
Received By jroach Date 2018-07-24 Time 14:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-22 Cont ID  
Sent By jroach Date 2018-06-22 Time 15:18 Rev Time 0.00
Received By jroach Date 2018-06-22 Time 15:18 Sent To  
Notes
2018-06-22 15:18:52ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.22.2018
 PERMIT NO.: 18060126
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO THE LEASE BETWEEN THE SCIENCE MUSEUM AND
 THE ZOO, ALTERATIONS TO THE PREMISES SHALL NOT BE
 PERMITTED WITHOUT PRIOR WRITTEN CONSENT OF THE LANDLORD
 (CITY). PLEASE PROVIDE DOCUMENTATION INDICATING
 APPROVAL OF THE ALTERATIONS BY THE CITY?S
 ADMINISTRATION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved